ZoneSense
Operation & Programming
MAN1564-3

Advertisement

Table of Contents
loading

Summary of Contents for Haier Ampac ZoneSense PLUS

  • Page 1 Fire detection and evacuation solutions that save lives. ZoneSense Operation & Programming MAN1564-3...
  • Page 2: Table Of Contents

    MAN1564-3 Contents Introduction ........................... 5 Controls – Front Panel ........................5 System Controls & Indicators ....................5 Levels Of Access ........................5 FireFighter Facility Controls ....................6 System Controls ........................7 Normal Operation ........................7 Indicators – Front Panel ........................8 Status Indicators ........................
  • Page 3 MAN1564-3 Responding To An Alarm 1. Indicators - Zone Alarm Indicator ( flashing ) - Common Alarm Indicator ( flashing ) - First Zone in Alarm is Displayed on LCD. Z7 ZONE SEVEN 2. To Isolate External Bell To Isolate Warning System Press ...
  • Page 4 MAN1564-3 Isolating a Zone (Example below isolates Zone 2) Press Press Press TEST MENU FAULTS STATUS  AMPAC   ENTER SU 00 : 15 Default Screen Moving to the ISOLATE MENU Press Press Press MENU MENU ZONE 1 ISOLATES ZONES ...
  • Page 5: Introduction

    MAN1564-3 1 Introduction Using 3 levels of access the ZoneSense PLUS Fire Alarm Control Panel ( FACP ) is controlled and programmed through the keypad on the front panel.  Note: To assist in the programming process the screens or Menus presented to the operator are diagrammatically shown as an Appendix at the end of this document.
  • Page 6: Firefighter Facility Controls

    MAN1564-3 Level3: ( Pre-commissioning Password factory set at 3333 ) Level 3 SYSTEM and PROGRAM menus can only be accessed by a set Level 3 password that can not be deleted. Panels fitted with a key switch have access to level 2 with the switch enabled and then 3 via the password.
  • Page 7: System Controls

    MAN1564-3 2.4 System Controls For the purposes of this explanation the following indicators perform these functions Enter or Menu is used to access the various menus and sub-menus and update the program MENU ENTER once the control settings have been set within a menu. MENU Move Left allows the operator to move left through a menu or the options to be set.
  • Page 8: Indicators - Front Panel

    MAN1564-3 3 Indicators – Front Panel All indicators are clearly visible at all times. If flashing indicators are used the on / off periods are >0.25 seconds and the flash frequencies are not less than: ↓ 1Hz for Alarm indications. ↓...
  • Page 9: Zone Indicators

    MAN1564-3 FAULT Fault – Amber Is a general fault indicator that flashes if a fault is present on any part of the system. ISOLATED Isolated – Amber Is a general isolate indicator that is illuminated if a Zone, Bell, Warning System or ACF is isolated.
  • Page 10: Liquid Crystal Display

    MAN1564-3 3.4 Liquid Crystal Display The panel is fitted with an 8 x 2 LCD. Its primary purpose is to display Zone alarm / fault / isolate information and prompts for system commands come programming. Alarm, Fault and Isolate information is accessed through the Main Menu. When the FACP is in its normal state a default screen will be displayed.
  • Page 11: Level 1 Access

    MAN1564-3 4 Level 1 Access Is a read only menu that allows the operator to reset latched Ancillary Control Facility outputs (IF FITTED). In the event an ancillary device trips out or is operated for some reason the latching control of the device has to be reset to re-establish normal functionality of that device.
  • Page 12 MAN1564-3 Meaning: The O/P is either On (activated ) and Normal, or Off (de- activated ) and Normal, or On (activated) and Isolated, or Off (de- activated ) and Isolated. Brigade Press Enter then Move Right or Move Left to view the Brigade screen. Press Enter then Move Right or Move Left to view the Status of the Alarm 1 &...
  • Page 13 MAN1564-3 Agent Press Enter then Move Left or Move Right to select the Agent OR press Move right to access Sounders. The LCD indicates the Agent Release Board status / release progress. AGENT AGENT AGENT NORMAL ISOLATED STG 1 Sample Agent Normal, Isolated Release in Stage 1 Screens Sounders Press Enter then Move Left or Move Right to select the required Sounder (1–8).
  • Page 14: Faults

    MAN1564-3 Software Displays the installed version of software. ( This is for information only ) SOFTWARE Ver A1 . 2 End of Sub - Menu Returning to STATUS in the Main Menu Move Right to access FAULTS 4.2 Faults Pressing Enter will display all faults in a sequential order. If there is more than one fault on the system the operator can scroll through each fault by using the Move Left and Right keys.
  • Page 15: Level 2 Access

    MAN1564-3 5 Level 2 Access At this level the operator is expected to have under gone training so as to be able to; ➢ test crucial elements of the system and; TEST ➢ isolate dedicated facilities that may be in fault. ISOLATE In the Main Menu From FAULTS Move Right for TEST 5.1 Tests...
  • Page 16 MAN1564-3 Fault Test of each Zone Once the test is commenced the Buzzer will rapidly turn on and off and the common Fault and Zone Fault LED’s will flash. Press Acknowledge, the Buzzer will be silenced and the common Fault and Zone Fault LED’s will continue to flash.
  • Page 17 MAN1564-3 Lamp Test Press the Move Right and / or Move Left key to move to the Lamp Test menu, press Enter and each LED on the panel will be sequentially turned on for one second and then off again. The Buzzer will sound at the start and completion of the test.
  • Page 18: Isolates

    MAN1564-3 5.2 Isolates To display the number of Isolates press Enter to access the menus then Move Left or Move Right to select the required menu. The number of isolates will be displayed for each step. Zone [ Main Brd ] Monitored Outputs Relay [ Relay Brd ] Sounder [ Sndr Brd ]...
  • Page 19 MAN1564-3 BELL BELL ISOLATED Active If the: ➢ Bell is Isolated the External Bell LED will be illuminated. ➢ Warning System is Isolated the Warning System LED will be illuminated. ➢ ACF is Isolated the ACF Fault / Isolate LED will be illuminated. ➢...
  • Page 20: Level 3 Access Programming

    MAN1564-3 6 Level 3 Access Programming Level 3 is a technical level that allows a technician to; ➢ initialise the FACP so it is capable of recognising how the system is constructed; and SYSTEM ➢ program how it will present information as well as how it will react to a change of state of an input and / or output.
  • Page 21: System

    MAN1564-3 6.2 System After entering the Level 3 Password and moving to the SYSTEM menu press Enter and the; Zone ISOLATE LED’s will illuminate; common ISOLATED LED will flash; and the LCD will display; BUZZER SYSTEM DISABLED SYSTEM DISABLED And then BUZZER Ignoring Buzzer, Mimic and Code menus ( explained below ) use the Move Right or Move Left keys to move through the menu and the Move Up key to set YES or Move Down key to set No.
  • Page 22 MAN1564-3 Buzzer Press Enter to access the Sub – Menu then theMove Left orMove Right key to select either; Resound, Alarm or Alarm Buzzer then Enter. Set the Resound, Alarm by using the Move Up key to Yes (activate on alarm ) or Move Down key for No ( not activate on alarm ). ALARM RESOUND Resound Set to YES...
  • Page 23: Program

    MAN1564-3 6.3 Program  Reminder: From the Zones Menu use the Move Right key to advance through the PROGRAM Menu. Pressing Enter to access the Program Menu will again disable the panel and the LED’s will illuminate as they did in the Systems Menu. The PROGRAM Menu consists of;...
  • Page 24 MAN1564-3 Clock To set the day and time press Enter and the day will be highlighted. Use the Move Up or Move Down keys to step through the days of the week, then the Move Right key to access the hours and minutes.
  • Page 25 MAN1564-3 Set the Reset / Buzzer output option so as the output acts as a Reset or Buzzer function as per the system design configuration. RST / BZ RESET Screen Showing the Output Set to Reset If the output is used set as a Reset or Buzzer function by using the Move Up for Buzzer or Move Down keys for Reset.
  • Page 26 MAN1564-3 Fire Fan FAN 2 The sub menu consists of; Alarm Inhibit Function Latch ACF Isolate For: Alarm Inhibit Press Enter then use the Move Right and / or Move Left keys to select the Fire Fan that will be controlled by the selected functions in the sub - menu .
  • Page 27 MAN1564-3 Press Enter and the cursor will flash over YES or NO and then the Move Up key for Yes to set the card to be latching or Move Down key for No to set the card for non-latching on alarm. LATCHING LATCHING Press Enter to update the Program and Cancel to back out of the Menu.
  • Page 28 MAN1564-3 Examples of the different “ Styles “ available through the Indicate Menu are shown above. Note only the top display is shown in the first 2 examples where as the first 3 top displays are shown in Style 3 Once the “Style has been selected press Enter to update the Program and Cancel to back out of the Menu Display...
  • Page 29: Appendix A: As 4428 Menu Structure & Programming

    MAN1564-3 7 Appendix A: AS 4428 Menu Structure & Programming STATUS FAULTS TESTS ISOLATE SYSTEM PROGRAM Status PRESS ENTER TO GO TO SUB MENU, PRESS THESE KEYS PRESS CANCEL AT MENU CANCEL SET MENU OR UPDATE PROGRAM TO SET YES / NO, OFF / ON, ANY TIME TO BACK STATUS ENTER...
  • Page 30 MAN1564-3 Faults PRESS CANCEL AT ANY TIME TO BACK MENU CANCEL LEGEND: PRESS ENTER TO GO TO MENU OUT OF THE MENU OR STOP TEST ENTER FAULTS MENU ENTER PRESS TO VIEW DETAILS OF EACH FAULT MENU CANCEL ENTER FAULTS F 1 / 2 F 2 / 2 MENU...
  • Page 31 MAN1564-3 Isolate MENU CANCEL LEGEND: PRESS CANCEL AT ANY TIME TO BACK OUT OF THE MENU PRESS ENTER TO ACCESS MENU ENTER ISOLATE MENU ENTER PRESS MOVE FORWARD / BACKWARD THROUGH THE MENU MENU CANCEL PRESS TO MAKE ACTIVE PRESS TO ISOLATE ENTER ZONE 2 Z ONES...
  • Page 32 MAN1564-3 System ( Password required ) ENTER ALARM MENU RESOUND MENU MENU SYSTEM BUZZER ENTER PASSWORD ENTER ENTER YES / NO YES / NO FACTORY DEFAULT EXAMPLE PASSWORD IS 3333 SET RESOUND TO YES THEN MOVE TO ALARM EXAMPLE OF Y E S EARTH MON ENTERING...
  • Page 33 MAN1564-3 Program Agent Notes: If only one trigger zone is allocated a zone then the system will be activated by one zone only. Any trigger zone may be allocated to any zone. However when a trigger zone has been allocated eg T1 to zone 1 then only the remaining trigger zones T2, T3 or T4 are each available to be PROGRAM allocated one of the remaining detector zones.
  • Page 34: Appendix B: As4428 Abs Front Panel Configuration Labelling

    MAN1564-3 8 Appendix B: AS4428 ABS Front Panel Configuration Labelling WARN SOUNDER SOUNDER SOUNDER SOUNDER SOUNDER SOUNDER SOUNDER SOUNDER ZONE CONFIGURATION BELL ALARM B ALARM 1 B ALARM 2 RELAY 1 RELAY 2 RELAY 3 RELAY 4 RELAY 5 RELAY 6 RELAY 7 RELAY 8 FAN 1 FAN 2 FAN 3...
  • Page 35: Appendix C: Simple Example Wiring Diagram Of A Basic Facp

    MAN1564-3 9 Appendix C: Simple Example Wiring Diagram of a Basic FACP Front of Main Card Illustrated External Cabling EOL Termination Values Fault Input Terminate all 3 I/P's Zone 10uf, 3K3, Resistor with EOL Resistor 4K7, 6K8, 10K Maximum of 40 Monitored O/P's = 10Kohms Devices per Zone...
  • Page 37 UNCONTROLLED DOCUMENT NOTE: Due to AMPAC’s commitment to continuous improvement specifications may change without notice.