Summary of Contents for Rockwell Automation 1794-AENTR, 1794-AENTRXT
Page 1
FLEX I/O Dual-port EtherNet/IP Adapters Catalog Numbers 1794-AENTR, 1794-AENTRXT User Manual Original Instructions...
Page 2
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
Added section on Enable or Disable the Web Server 21, 45 Added section on Log in to the Web Server Additional Resources These resources link to additional information about related products from Rockwell Automation. To download publications, click the link or visit rok.auto/literature and search for the publication numbers.
• Communication supported by RSLinx® software • IP address assigned via standard BOOTP/DHCP tools • I/O configuration via Studio 5000 Logix Designer application • No network scheduling required • No routing tables required Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Dual-port EtherNet/IP adapter with extended temperatures range Hardware and Software The adapters and the applications that are described in this manual are compatible with the following firmware revisions and software releases. Contact Rockwell Automation if you need Compatibility software or firmware updates to use this equipment.
I/O modules. If you use a rack- optimized connection to transfer the data, you only need a single connection – the connection to the adapter. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
I/O modules set up to use rack optimization communicates at the rate of the requested packet interval (RPI) configured for the 1794-AENTR or 1794-AENTRXT adapter. I/O modules that are configured for direct communication communicate at their own set RPIs and ignore the adapter RPI. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
DIN rail and connect it to the EtherNet/IP network. Module Components Figure 2 to identify the external features of the FLEX I/O EtherNet/IP adapter. Figure 2 - Dual-port EtherNet/IP Adapter – 1794-AENTR, 1794-AENTRXT Component Identification Dual-port EtherNet/IP adapter Module locking tab...
This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
When the adapter is locked onto the DIN rail, gently push the Flexbus connector into the adapter to complete the backplane. 8. Reinstall the module in the adjacent terminal base unit. Connect Wiring Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Use the pen-push thumbwheel switches on the adapter. Press either the + or the - button with a pen tip to change the number. • Use a Dynamic Host Configuration Protocol (DHCP) server, such as Rockwell Automation® DHCP. • Retrieve the IP address (if previously set) from nonvolatile memory.
The module has the following mounting dimensions. 1794-AENTR shown (1.96) 80.4 (3.16) 87.4 (3.44) 30.4 (1.19) (3.70) Millimeters 1794-AENTR, 1794-AENTRXT (Inches) 87.4 H x 94 W x 92 D (344 H x 3.7 W x 3.6 D) Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Page 16
Chapter 2 Install Your FLEX I/O Adapter Notes: Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Before you can use your 1794-AENTR or 1794-AENTRXT adapter, you must configure its IP address, and optionally, its subnet mask and gateway address. You can use the Rockwell Automation BOOTP/DHCP utility to perform the configuration. You can also use generic BOOTP software or, within some limitations, a DHCP server.
The gateway has two IP addresses (128.1.0.2 and 128.2.0.3). The first must be used by hosts on Network 1 and the second must be used by hosts on Network 2. To be usable, a host’s gateway must be addressed using a net ID matching its own. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
The FLEX I/O adapters support the following additional methods to change the IP address: IP Address • BOOTP/DHCP tool • RSLinx Classic software For more information on how to use these methods, see EtherNet/IP Network Devices User Manual, publication ENET-UM006. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Implicit Protected Mode. The following are example alerts that result from an attempt to set IP values on the adapter when the adapter is in Implicit Protected Mode: IMPORTANT Protected Mode is not configurable. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Disabling the web server in conjunction with using the Implicit Protected Mode decreases the possibility of a security breach. For more information on how to enable or disable the web server, see Enable or Disable the Web Server on page Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Page 22
Chapter 3 Configure the Adapter for Your EtherNet/IP Network Notes: Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Before You Begin You must complete the following tasks before you can configure the adapter and modules: 1. Create a Studio 5000 Logix Designer application project. 2. Add the ControlLogix 5580 controller to the project. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
For some modules, the Select Major Revision dialog box can appear. If the dialog box appears, choose the major revision of the module and click OK. c. Click Create. The New Module dialog displays. 4. Complete the following tasks on the General category page: Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
This example application uses I/O module default configurations. For more information, see FLEX I/O Digital Input Modules Installation Instructions, publication 1794-IN093 and FLEX I/O Digital DC Output Modules Installation Instructions, publication 1794-IN094. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Page 26
Slot Comm Format Rack Optimization Electronic Keying Compatible Module 4. Click OK to save the configuration. The digital input module appears in the I/O configuration that is indented under the 1794- AENTR adapter. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Page 27
1. From the I/O Configuration tree, right-click the remote 1794-AENTR adapter, and then select New Module. The Select Module Type dialog opens. 2. Select the 1794-OB16 module from the list, and then click Create. The New Module dialog opens. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Page 28
Enter the new tag here 2. Make sure you select the Edit Tags tab at the bottom of the Controller Tags dialog, and then create the following tag: Type Parts_Count Counter 3. Close the Controller Tags dialog. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
The Who Active dialog opens. 2. Select your Ethernet driver (for example, AB_ETH-1) and expand the tree through the backplane of the local ControlLogix chassis. 3. Highlight the 1756-L85E ControlLogix 5580 controller and click Download. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
1794-OB16 output module turn off. For more information, see FLEX I/O Digital Input Modules Installation Instructions, publication 1794-IN093 and FLEX I/O Digital DC Output Modules Installation Instructions, publication 1794-IN094. This completes the rack-optimized Discrete I/O example. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Perform the following steps to create the example application: Application 1. Start the Studio 5000 Logix Designer application. 2. From the main dialog File menu, select the project file from the previous chapter (for example, FLEX_IO_Controller). Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Add the Analog Input Module to the I/O Configuration 1. Right-click the 1794-AENTR adapter under the I/O Configuration folder, and then select New Module. The Select Module Type dialog opens. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Page 33
6. On the Configuration tab, use the drop-down list to set the Voltage/Current Range for Channel 0 to 0…10V – Binary. This range allows you to monitor the output with a voltmeter when you test the application. Leave the other channels at their default values. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
1794-AENTR adapter. Add the Analog Output Module to the I/O Configuration 1. Under the I/O Configuration folder, right-click the remote 1794-AENTR adapter, and then select New Module. The Select Module Type dialog opens. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Page 35
The two rack connected digital I/O modules continue to communicate at the RPI of the rack connection. 6. Click Apply to save the configuration. 7. Click the Fault/Idle Action tab. For this example, leave these parameters at the default setting. For an explanation of these parameters click Help. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Enter the new tag here Make sure you select the Edit Tags tab at the bottom of the Controller Tags dialog, and then create the following tag: Type Analog_Test_Signal Timer Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
2. Save the program. Download the Program To download the program to the controller do the following: 1. Click the Communications menu, and then select Who Active. The Who Active dialog opens. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
1. Connect analog output channel 0 on the 1794-OF4I/A module to analog input channel 0 on the 1794-IF4I/A input module. 1794-IF4I 1794-OF4I 2. Restore the Studio 5000 Logix Designer application window and place the controller in Run mode. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Page 39
For information on wiring and troubleshooting the I/O modules, see FLEX I/O Isolated Analog Output Module Installation Instructions, publication 1794-IN037 and FLEX I/O Isolated Analog Input Module Installation Instructions, publication 1794-IN038. This completes the direct connection analog I/O example. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Page 40
Chapter 5 Analog I/O with Direct Connection Notes: Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
The faceplates of the 1794-AENT and 1794-AENTRXT adapters are provided with status indicators that display the Module Status, Network Status, and Link Status for both links. Status Indicators Figure 5 - 1794-AENTR, 1794-AENTRXT Module Network status Module status Link 1 status...
Page 42
Duplicate IP address. Adapter has detected that its IP address is already in use. Configure the adapter with a unique IP address. Flashing red/green Self-test. Adapter performing power-up self-test. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
You can download and install RSLinx software from the Product Compatibility and Download Center at rok.auto/pcdc. Configure the AB_ETH Driver To configure the AB_ETH Ethernet communication driver perform the following steps: 1. Start RSLinx. 2. From the Communications menu, select Configure Drivers. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Page 44
7. When you are done entering the IP addresses, click Apply and then click OK to close the Configure driver dialog. The new driver appears in the list of Configured Drivers. Your list displays the drivers that you have configured on your workstation. 8. Close RSLinx. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
2. Set the switches to the desired IP address and cycle power to the module. 3. In your web browser, enter the IP address of the adapter. The web server home page does not display. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
To display and work with the adapter diagnostics home page, follow these procedures. the Web Server IMPORTANT Make sure that your PC Internet LAN setting and your TCP/IP settings are configured to access the subnet on which your adapter communicates. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Connection Statistics and Refresh Rate by clicking Diagnostic Overview on the navigational panel on Information the left. Click tabs to see the corresponding page. Click Diagnostics options to see corresponding pages. Type a refresh rate. Download EDS files for your adapter. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
To use the Ethernet Statistics page for information about the Ethernet link and interface and media counters, click Ethernet Statistics tab at the top of the page or from the panel on the left. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
1. From the home page, click Configuration or Expand to see the Configuration options, if needed. 2. From the Configuration page, click one of the following: • Identity • Network • Services Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
To use the Device Identity page to make entries for the device name, device description, and device location, click Device Identity from the tab at the top of the page or panel on the left. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
To use the Services page to change the password for the Configuration webpage or disable the web server, click Device Services tab at the top of the page or panel on the left. Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Page 52
Appendix C Adapter Web Dialogs Notes: Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Page 54
I/O module 7 network cable 14 indicators network scheduling 7 status 11 networking input data 33 consumer 9 input module 9 node address 15 install set 15 physically 11 Internet Protocol IP 14 Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Page 55
19 IP address 17 unique IP address 17 web dialogs configuration 49 ethernet statistics 48 home page 46 I/O connections 49 network settings 48 password 50 user name 50 web server 45 Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Page 56
Index Notes: Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Page 57
FLEX I/O Dual-port EtherNet/IP Adapters User Manual Rockwell Automation Publication 1794-UM066C-EN-E - April 2023...
Page 58
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec. Allen-Bradley, ControlLogix, expanding human possibility, FactoryTalk, FLEX, FLEX I/O-XT, Logix 5000, Rockwell Automation, RSLinx, RSLogix 5000, Studio 5000 Logix Designer, and TechConnect are trademarks of Rockwell Automation, Inc.
Need help?
Do you have a question about the 1794-AENTR, 1794-AENTRXT and is the answer not in the manual?
Questions and answers