CR#
Attrib.
Register name
#111 O R/W Set value of CH4 lower bound
Symbols:
O: When CR#41 is set to H'5678, the set value of CR will be saved.
X: set value will not be saved.
R: able to read data by using FROM instruction.
W: able to write data by using TO instruction.
※ CR#43: Error status value. See the table below:
bit0
K1 (H'1)
bit1
K2 (H'2)
bit2
K4 (H'4)
bit3
K8 (H'8)
bit4
K16 (H'10) CH2 Conversion error
bit5
K32 (H'20) CH3 Conversion error
Note: Each error status is determined by the corresponding bit (b0 ~ b13) and there may be more
than 2 errors occurring at the same time. 0 = normal; 1 = error
※
Module Reset (Available for firmware v1.10 or above): When modules need reset, write H'4352 in
CR#0 then disconnect and turn on the power again. The resetting initializes parameter setups to
provide normal functions for other modules. Connect to only one module during reset, wait 1
second before disconnecting the power.
Explanation on Special Registers D9900~D9999
When DVP-ES2 MPU is connected with modules, registers D9900~D9999 will be
reserved for storing values from modules. You can apply MOV instruction to operate
values in D9900~D9999.
When DVP-ES2 MPU is connected with DVP04AD-E2, the configuration of special
registers is as below:
Module
Module
#0
#1
D1320
D1321
D9900
D9910
D9901
D9911
D9902
D9912
D9903
D9913
Note 1: D9900 ~ D9999 are average input values of CH1 ~ CH4 and the sampling range is K1 ~ K100.
When the sampling range is set to K1, the values displayed in D9900~D9999 are current values.
You can use: 1. ES_AIO Configuration Function of WPLSoft or 2. FROM/TO instructions (CR#8
~ CR#11) to set the sampling range as K1.
Adjust A/D Conversion Curve
Power supply error
Reserved
Upper/lower bound error bit10 K1024(H'0400) Sampling range error
CH1 Conversion error
Module
Module
#2
#3
D1322
D1323
D9920
D9930
D9921
D9931
D9922
D9932
D9923
D9933
Explanation
Description
bit6
K64 (H'40)
bit9
K512(H'0200)
bit11 K2048(H'0800)
bit12 K4096(H'1000)
bit13 K8192(H'2000)
Module
Module
#4
#5
D1324
D1325
D9940
D9950
D9941
D9951
D9942
D9952
D9943
D9953
- 5 -
CH4 Conversion error
Mode setting error
Upper / lower bound
setting error
Set value changing
prohibited
Communication
breakdown on next
module
Module
Module
#6
#7
D1326
D1327
D9960
D9970
D9961
D9971
D9962
D9972
D9963
D9973
Description
Model Code
CH1 average
input value
CH2 average
input value
CH3 average
input value
CH4 average
input value