SYSTEM INSTALLATION CHECKLIST
Suggested order of operations for installation & commissioning a typical
sound masking system.
Mount, Install and Cable all components
Power & test emitters/speakers
Define emitter/speaker type per output (must be connected to
the controller via QT X software or Qt X web interface)
Adjust Zone on front panel to a low but audible level
as necessary
Walk emitter / loudspeaker locations to verify sound masking
signal is present at each
Attach peripherals (paging, audio sources, life safety panel...)
Verify proper operation of each source and contact closures
Discover controllers connected to the network
Configure the system
Configure controller's IP Address, Network Operation Mode
(single / dual network cable)
Add all controllers by serial number to proper location
(Qt X software)
Update firmware for all controllers
Create zones as required
Assign controller outputs to zones
Create music paging Audio Sources and assign to Zones
(ensure emitter / loudspeaker type in use supports
audio sources)
Define behaviors of input and outputs
Set zone sound masking levels (42dBA SPL to 48dBA SPL)
using a calibrated sound pressure meter. Measure at 4ft. (1.2m)
above the finished floor.
Qt X Sound Masking System
Adjust masking spectrum equalizer for each output as necessary
to meet project requirements. Qt X 300/600 models have
preconfigured spectrums, Qt X 800/805 require spectrum tuning
Set system security / user levels and document passwords
Go through each zone testing / adjusting levels, checking behavior
Set Audio Source levels
Capture final sound masking spectrum and sound pressure level
measurements for reporting if required
Set soft start, schedules, etc., as necessary
Save / backup system configuration using Qt X software