Requirements And Recommendations For The Hydraulic Circuit - Hitachi YUTAKI S80 R410A Series Installation And Operation Manual

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
!
CAUTION
• Check carefully for leaks in the water circuit, connections and circuit elements.
• Check that the water pressure in the circuit is lower than 7 bars.
• A pressure and temperature relief valve should be installed at the DHW inlet connection (See
"5.5.3 Additional hydraulic optional elements (For DHW)"
operate its relief valve to ensure that the water flows free through the discharge pipe.
• Fill in the circuit with tap water. The water in the heating installation must comply with
EN directive 98/83 EC. Non-sanitary controlled water is not recommended (for example,
water from wells, rivers, lakes, etc.)
5.3.4 Requirements and recommendations for the hydraulic circuit
• The maximum piping length depends on the maximum pressure availability in the water outlet
pipe. Please check the pump curves.
• The indoor unit is equipped with an air purger (factory supplied) at the highest location of the
Indoor Unit. If this location is not the highest of the water installation, air might be trapped
inside the water pipes, which could cause system malfunction. In that case additional air
purgers (field supplied) should be installed to ensure no air enters the water circuit.
• For heating floor system, the air should be purged by means of an external pump and an open
circuit to avoid air bags.
• When the unit is stopped during shut-off periods and the ambient temperature is very low,
the water inside the pipes and the circulating pump may freeze, thus damaging the pipes and
the water pump. In these cases, the installer shall ensure that the water temperature inside
the pipes does not fall below the freezing point. In order to prevent this, the unit has a self-
protection mechanism which should be activated (refer to the Service manual,
functions"
chapter).
• Check that the water pump of the space heating circuit works within the pump operating
range and that the water flow is over the pump's minimum. If the water flow is below 12 litres/
minute, alarm is displayed on the unit.
• An additional special water filter is highly recommended to be installed on the space heating
(field installation), in order to remove possible particles remaining from brazing which cannot
be removed by the indoor unit water strainer.
• When selecting a tank for DHW operation, take into consideration the following points:
✓ The storage capacity of the tank has to meet with the daily consumption in order to avoid
stagnation of water.
✓ Fresh water must circulate inside the DHW tank water circuit at least one time per day during
the first days after the installation has been performed. Additionally, flush the system with
fresh water when there is no consumption of DHW during long periods of time.
✓ Try to avoid long runs of water piping between the tank and the DHW installation in order to
decrease possible temperature losses.
✓ lf the domestic cold water entry pressure is higher than the equipment's design pressure (6 bar),
a pressure reducer must be fitted with a nominal value of 7 bar.
PMEN0648 rev.0 - 03/2023
section). If it is the case, manually
"Optional
5
34

Advertisement

Table of Contents
loading

Table of Contents