16x AC 12...230 V / DC 12...115 V
Product and function description
The N 263E11 binary input device is a 6 module units
wide DIN rail mounted device in N-System dimensions
with 16 inputs for AC voltage ranging from 12...230 V or
DC voltage ranging from 12...115 V. It enables both
statuses (voltage is applied or not) and changes in status
(voltage is incoming or outgoing) to be recorded, as well
as voltage impulses. It can therefore be used, for exam-
ple, to monitor voltages (whether mains voltage is pre-
sent), to record circuit or operating states (whether a
miniature circuit-breaker or a residual-current circuit-
breaker has been released, a plant is switched on or off,
a malfunction or an alarm is being signalled), to record
the change of status when switching on or switching off
a voltage (whether a switch or a pushbutton was acti-
vated, whether it was activated for a shorter or longer
period, whether the voltage was switched on or off due
to the activation) and to record and count voltage pulses
with a minimum voltage on-time of 50 ms and a max.
pulse succession of up to 5 pulses per second, without or
with monitoring of the number of pulses counted until a
predetermined threshold has been reached or exceeded.
At each input a red LED shows whether a voltage is ap-
plied or not. The N 263E11 has an integrated 230 V
power supply in order to supply the electronics. This
power supply enables switching statuses to be displayed
on the inputs even when there is no bus voltage present.
Note: The device is without function after the application
program has been "unloaded" with the ETS. The status of
the inputs is also no longer displayed in this case.
Application program
The "25S16 Binary Input Device 980D03" application
program, which can be downloaded with the ETS3.0f,
supports a multitude of applications and enables one of
the following functions to be assigned to every input:
Siemens AG
Building Technologies
Control Products and Systems
P.O. Box 10 09 53, D-93009 Regensburg
- Switching status / binary value transmission
- Switching, edge-triggered
- Switching, short / long operation
- 1-button dimming
- 1-button solar protection control
- 1-button group control (sequence control)
- 1-bit Scene control
- 8-bit Scene control
- 8-bit value, edge-triggered
- 8-bit value, short / long operation
- 16-bit floating point value, edge-triggered
- 16-bit floating point value, short / long operation
- 8-bit pulse counting without threshold check
- 8-bit pulse counting with threshold check
- 16-bit pulse counting without threshold check
- 16-bit pulse counting with threshold check
- 32-bit pulse counting without threshold check
- 32-bit pulse counting with threshold check.
Using the ETS, one of the following functions can be al-
located to one input pair, i.e. to two neighbouring in-
puts:
- 2-button dimming with stop telegram
- 2-button solar protection control.
Connection example
N 263E11, 4 pages
ã Siemens AG 2014
Subject to change without further notice
GAMMA instabus
Technical Product Information
November 2014
5WG1 263-1EB11
Technical Manual
Update: http://www.siemens.com/gamma-td
2.7.4.1/1

Advertisement

loading

Summary of Contents for Siemens N 263E11

  • Page 1 - 32-bit pulse counting without threshold check - 32-bit pulse counting with threshold check. The N 263E11 binary input device is a 6 module units wide DIN rail mounted device in N-System dimensions Using the ETS, one of the following functions can be al- with 16 inputs for AC voltage ranging from 12...230 V or...
  • Page 2 GAMMA instabus Technical Product Information November 2014 Binary input device N 263E11 5WG1 263-1EB11 16x AC 12…230 V / DC 12...115 V · Input signal delay: Installation notes - at rising edge of input signal: · The device can be used for permanent installation in max.
  • Page 3 The bus terminal (D2) is located on the upper side of dressing mode for transferring the physical address the binary input device N 263E11 (D1). A2 LED for displaying normal mode (LED Off) or ad- The bus terminal (D2) consists of two sections (D2.1, dressing mode (LED On);...
  • Page 4 Any faulty device is to be sent together with a return de- · The locating clamp (E3) encloses the contact system livery note of the local Siemens office. (E2) on the rear of the device (E1). If you have further questions concerning the product ·...

This manual is also suitable for:

5wg1 263-1eb11