This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes.
Installation Instructions Original Instructions Stratix 2500 Lightly Managed Switches Catalog Numbers 1783-LMS5, 1783-LMS8 Topic Page Parts List Required Tools/Components Enclosure Requirements Site Requirements Mount the Switch Ground the Switch Wire the DC Power Source Install the Power Connector on the Switch Connect to 10/100 Ports Confirm Installation Remove the Switch from a DIN Rail...
Page 2
Indien de apparatuur wordt gebruikt op een wijze die niet is gespecificeerd door de fabrikant, dan bestaat het gevaar dat de beveiliging van de apparatuur niet goed werkt. Rockwell Automation Publication 1783-IN011B-EN-P - April 2023...
Page 3
EN IEC 60079-0) and used in an environment of not more than Pollution Degree 2 (as defined in EN 60664-1) when applied in Zone 2 environments. The enclosure must be accessible only by the use of a tool. • This equipment shall be used within its specified ratings defined by Rockwell Automation. • The instructions in the user manual shall be observed.
Page 4
WARNING: When you press the Express Setup button while power is on, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Rockwell Automation Publication 1783-IN011B-EN-P - April 2023...
Temperatures inside the enclosure must conform to device specifications, as described in the Stratix Ethernet Device Specifications Technical Data, publication 1783-TD001. IMPORTANT When the switch is installed in an industrial enclosure, the temperature within the enclosure is greater than normal room temperature outside the enclosure. Rockwell Automation Publication 1783-IN011B-EN-P - April 2023...
The torque must not exceed 0.51 N•m (4.5 in•lb). Ground-lug Screws Attach the other end of the ground wire to a grounded bare metal surface, such as a ground bus, a grounded DIN rail, or a grounded bare rack. Rockwell Automation Publication 1783-IN011B-EN-P - April 2023...
Connect the other end of the positive wire to the positive terminal on the DC power source, and connect the other end of the return wire to the return terminal on the DC power source. Rockwell Automation Publication 1783-IN011B-EN-P - April 2023...
• The device at the other end is not be turned on. • There is a cable problem or a problem with the adapter installed in the attached device. If necessary, reconfigure and restart the connected device. Rockwell Automation Publication 1783-IN011B-EN-P - April 2023...
Pull the bottom of the switch away from the DIN rail, and lift the hooks off the top of the DIN rail. Pull down on DIN rail release latch. Remove the switch from the DIN rail. Rockwell Automation Publication 1783-IN011B-EN-P - April 2023...
Torque, functional ground lug screw 0.51 N•m (4.5 in•lb) North American temp code ATEX temp code Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Description Stratix Ethernet Device Specifications Technical Data, publication 1783-TD002 Provides specification information for Ethernet switches and other devices.
Page 12
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur Allen-Bradley, expanding human possibility, Rockwell Automation, Rockwell Software, and Stratix are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.