Airzone Supermaster controller (AZX6CSMASTER [S/E] [B/G]) ......................... 11 Airzone Hidronic production control board (AZX6CCPGAWI) .......................... 11 Airzone Production control board (AZX6CCP) ................................ 11 Airzone air to water HP gateway (AZX6GAW XXX) ..............................12 Airzone temperature metallic probe in sheath (AZX6SONDPROTECT) ......................12 General requirements ..........................................12 Introduction ..............................................
Page 5
Connection ............................................28 Airzone Production control board (AZX6CCP) ................................ 33 Assembly ............................................33 Connection ............................................34 Airzone air to water HP gateway (AZX6GAW XXX) ..............................37 Assembly ............................................37 Configuration ..........................................37 Assembly and connection evaluation ....................................38 System start-up ............................................38 Airzone Blueface and Airzone Think setup ................................
Page 6
Navigation Tree - Blueface Thermostat ..................................58 Navigation Tree - Think Thermostat .................................... 59...
WARNINGS AND ENVIRONMENTAL POLICY PRECAUTIONS For your security, and to protect the devices, follow these instructions: • Do not handle the system with wet or damp hands. • Disconnect the power supply before making any connections. • Take care not to cause a short circuit in any of the system connections. ENVIRONMENTAL POLICY Do not dispose of this equipment in the household waste.
SYSTEM ELEMENTS AIRZONE RADIANT365 MAIN CONTROL BOARD (AZRA6RADIANT) Configurable electronic board which manages the system through wired and wireless devices. Power supplied through the control module of radiant elements (AZRA6OUTPUT8Z). Device box (65 x 65 mm / Ø65 mm) mounting.
AIRZONE BLUEFACE COLOR THERMOSTAT WIRED (AZRA6BLUEFACEC) Color graphic interface with capacitive screen for controlling zones in Airzone systems. Powered by main control board. Finished in steel and glass. Available in white and black. Functionalities: • Available in Spanish, English, French, Italian, German and Portuguese.
WEBSERVER HUB AIRZONE CLOUD DUAL (AZX6WSPHUB) Webserver for controlling Airzone systems through Airzone Cloud platform. Accessible through browser or App (available for IOS and Android). Dual WiFi 2.4/5Ghz or Ethernet connection. Powered through domotic bus. Mounted on DIN rail or on wall.
AIRZONE SUPERMASTER CONTROLLER (AZX6CSMASTER [S/E] [B/G]) Monochrome LCD touch screen back-lighted controller for managing the system of the installation. Power supplied through the automation bus of the system. Wall-mounted (AZX6CSMASTERS) or wall-embedded (AZX6CSMASTERE). Available in white and grey. Functionalities: •...
• Perform all the connections with total abscense of power suppliance. • In order to connect the elements of the system, use Airzone cable: shielded twisted pair cable formed by 4 wires: 2x0,22 + 2x0,5mm (AWG 20 – 4 wired).
Page 13
• Respect the connection polarity of each device. A wrong connection may seriously damage the product. • For elements externally powered at 110 /230 Vac, for the communications, it is only necessary to connect the poles "A" and "B" of the bus. •...
INTRODUCTION Airzone systems enable the management of Master and Zone interfaces. Master thermostats enable mode management or define the efficiency level with the Eco-Adapt function. It is recommended the use of a Blueface thermostat as Master Interface, this enables time schedule management and more unique functionalities.
Airzone connection bus connectors The Airzone connection bus allows you to connect all the internal components independents of the Main Control Board to control up to 6 zones, (8 through the Production Control Board, AZX6CCP). These are the elements that can be connected: Airzone Thermostats: Blueface (AZRA6BLUEFACEC), Think (AZRA6THINKC) and Lite (AZRA6LITEC).
AIRZONE CONTROL MODULE OF RADIANT ELEMENTS (AZRA6OUTPUT8Z) Assembly The Airzone Control Module of Radiant Elements is mounted on DIN rail (Fig. 6). It is externally powered at 110/230 Vac. Location and installation of the module must comply the current electronic rules.
Connection The Control Module of Radiant Elements is a device which connects to the Airzone connection bus of the main board (Fig. 7). Nº Meaning Power supply LEDs of relay state Zone relays Airzone connection bus Cooling demand / Zone relay...
AIRZONE 3 SPEEDS/STAGES DEHUMIDIFIER CONTROL MODULE (AZRA6CMOD3V) Assembly The Airzone Control Module of Radiant Elements is mounted on DIN rail (Fig. 10). It is externally powered at 110/230 Vac. Location and installation of the module must comply the current electronic rules.
Fig. 13 Assembly The Airzone Control Module of Radiant Elements is mounted on DIN rail (Fig. 10). It is externally powered at 110/230 Vac. Location and installation of the module must comply the current electronic rules. Fig. 10 Note: To take the module away, pull the reed down to release it.
Speed 2 Speed 3 On / Off It has a 5-pin terminal to connect it to the Airzone connection bus of the main board . Attach the wires with the terminal screws following the color code (Fig. 12). Powe supply is connected to the module through a 3-pin terminal .
Note: To connect more than 4 Blueface, it is necessary an external power supply (AZX6POWER). These values can be altered depending on the separation distance among them. AIRZONE WIRELESS THERMOSTAT (AZRA6THINKR / AZRA6LITER) Assembly Wireless thermostats are mounted on the wall through a support. It is recommended not to locate it more than 40 meters away from the main control board.
WEBSERVER HUB AIRZONE CLOUD DUAL (AZX6WSPHUB) Nº Description Ethernet Modbus port Airzone connection bus 1 – DM1 Airzone connection bus 2 – DM2 Assembly The Webserver HUB is mounted on DIN rail or on wall. It is should be placed and mounted in accordance with the current electrotechnical regulations.
Configuration To configure it, follow the steps described in the Airzone Cloud Webserver installation manual, available at myzone.airzone.es (https://doc.airzone.es/producto/Gama_AZ6/Airzone/Comunes/Manuales/MI_AZCLOUD_MUL.pdf) WEBSERVER HUB AIRZONE-LUTRON (AZX6WSPLUT) Nº Description Ethernet Modbus port Airzone connection bus 1 – DM1 Airzone connection bus 2 – DM2 Assembly The Webserver HUB Lutron is mounted on DIN rail or on wall.
It is only necessary to connect one Lutron integration gateway per installation (control of up to 32 systems). All the system control boards must be correctly addressed. Configuration To configure it, follow the steps described in the Airzone Cloud Webserver installation manual, available at myzone.airzone.es (http://doc.airzone.es/producto/Gama_AZ6/Airzone/Comunes/Manuales/MI_AZ6_LUTRON_A4_EN.pdf) WEBSERVER AIRZONE CLOUD WI-FI DUAL 2.4-5G (AZX6WSC5GER) N˚...
To connect the Webserver HUB to the remaining main control boards, you can use the DM2 automation bus with its 2-pin terminal 2 x 0.22 mm (2 x AWG 23). AZX6WSC5GER Fig. 83 Configuration To configure it, follow the steps described in the Airzone Cloud Webserver installation manual, available at myzone.airzone.es (https://doc.airzone.es/producto/Gama_AZ6/Airzone/Comunes/Manuales/MI_AZCLOUD_MUL.pdf)
Place the sub-frame again. Make sure it is fixed properly. Connection The Supermaster controller connects to the domotic bus of the Main Control Board (Fig. 35 and 37). Important: This device is power supplied by the Airzone connection bus of the Main Control Board. AZX6CSMASTERS Fig. 35 For wall-mounted thermostats, use the tabs located on the back of the thermostats.
Page 27
(Fig. 38). Fig. 38 Note: To configure it, follow the steps described in the user's manual, available at myzone.airzone.es/productos Note: For a proper operation of this module, all the main control boards must be addressed (see section Advanced settings).
AIRZONE HYDRONIC PRODUCTION CONTROL BOARD (AZX6CCPGAWI) Assembly The production control board is supplied to be screwed to the wall. It should be placed and mounted in accordance with the current electrotechnical regulations. For the mounting of the main control board, follow the following steps: •...
Page 29
Power supply connector This connector powers the main control board and all the elements connected to it. Externally powered at 110/230 Vac. It is connected through a 3-pin terminal. Attach the wires with the terminal screws following the color code. For added security, secure the wires using the turret.
Page 30
Digital inputs The production control board has 4 digital inputs to externally control the Airzone systems. These input are configured as normally open. It is recommended to use a shielded cable to connect it. DI4_ACS: This input activates the DHW mode: all the Acuazone/Innobus Pro32 systems working on Air heat will stop and the message DHW will be displayed by the zone thermostats.
Page 31
The UI bus allows you to connect multiple gateways of for air-to-water equipment installed. These are the elements that can be connected: Airzone aerothermal gateway (AZX6GAW xxx). In order to connect these gateways, disconnect the terminal of the UI bus and fit in the connector and the fixing post of the gateway.
3/4 pipes RadianT* *Only for Airzone RadianT365 system (AZRA6). Important: The control relays operation logic can be configured from SW2 or from the Production Parameters section on the advanced configuration menu. Configuration from the menú always has priority over SW2.
Connection It connects to the domotic bus of the main control board (Fig. 47). Nº Description Power Digital inputs … External domotic bus 2 Internal domotic bus External domotic bus 1 FRIO_Y Cooling mode CALOR_W Heating mode AIRE_Y Cooling air demand Control relays RADIANTE_Y...
Page 35
Digital inputs The production control board you have 4 digital inputs to externally control the Airzone systems. These inputs are configured as normally open. It is recommended to use a shielded cable to connect it. ACS: This input activates the DHW mode: all the Acuazone/Innobus Pro32 systems working on Air heat will stop and the message ACS will be displayed by the zone thermostats.
Page 36
Communication gateway for electromechanical units (AZDI6MCIFR [C/R]) in Acuazone and Innobus Pro32 systems configured as zoning or combined systems. Airzone infrared individual unit zone module (AZDI6MCIFRC) in Acuazone and Innobus Pro32 systems configured as zoning or combined systems. Airzone individual unit modules (AZDI6MCxxxC) in Acuazone and Innobus Pro32 systems configured as zoning or...
Assembly The Airzone air to water gateway is integrated into the domotic bus of the Cloud Ethernet Production Control Board, (AZX6CCPGAWI). It has a 4-pin terminal. Disconnect the terminal to which you want to connect to the Webserver and fit the connector (Fig.
Select your language and country. These are the available languages: Spanish, English, French, Italian, Portuguese and German. To associate a wireless Think, press Airzone to start seeking and then confirm the wireless association. Verify the range is correct (30% minimum) and confirm.
Page 39
Blueface Think Important: Use to confirm and to return.
AIRZONE LITE SETUP Zone address Select the zone associated to the thermostat pulling up the microswitch of the corresponding zone. Associated outputs If required, select other control outputs associated to the zone. The address zone will be the one with a lower value.
• Zone state: Displays information about the zone state and settings • Weather forecast: Only available with Airzone Cloud (AZX6WSC5GER / AZX6WSPHUB) • AC unit consumption: Only available for some configurations. • If you deactivate the information feature, only the time and zone state will be displayed.
Zone navigation. Access any zone and turn it on/off, check the information of the zone or change the set point. In master Airzone Think thermostats, it is also possible to change the Operation mode from the control bar. This is the list of available modes: Stop.
ADVANCED SETTINGS To access the advanced configuration menu of the thermostat and Blueface Think follow the following steps: Blueface Press and hold Think Important: Use to confirm and to return. Press and hold Press once Press and hold From this menu you can change the system and zone parameters. SYSTEM PARAMETERS •...
• Radio channel. It activates/deactivates the wireless association module of the system. • Condensation protection (only available for thermostat Blueface on installations with cooling radiant control). Enables to select the protection level against condensation: Very high, high, medium (by default), low and very low. If necessary, it can be activated for 1h.
4 pipes RadianT (Recommended for RadianT365 systems) Note: See section cloud ethernet Airzone production control board to check the operation logic in each configuration. • Activation delay. It allows to set a delay time in the power on of the production unit, configurable in minutes, from 0 to 7.
SELF-DIAGNOSE AIRZONE RADIANT365 MAIN CONTROL BOARD (AZRA6RADIANT) Airzone RadianT365 Main Control Boards have integrated LEDs that detect unusual operations. Meaning Data reception from automation bus Blinking Green Data transmission from automation bus Blinking Main control board activity Blinking Green Data transmission from Airzone connection bus...
Leds of relay state Blinking Green AIRZONE BLUEFACE AND THINK THERMOSTATS (AZRA6BLUEFACEC / AZRA6THINK [C/R]) Blueface and Think Thermostats Warnings Thermostat displays all the system warnings on the screensaver. If there is any error, it will be displayed on the screensaver, on the main screen and on “About errors”, in user settings.
Main control board status: Airzone connection bus LEDs are operating properly. Connection: Verify the polarity of the main control board and thermostat connectors. Wiring: Disconnect the terminal from the Airzone connection bus and check that the voltage between the poles (A/-) and (B/-) is about 0.65 Vdc.
Page 49
Error 1: Wireless thermostat-Main control board communication error This incident blocks the control of the zone. Check this error is not common to all thermostats. If so, verify the proper operation of the main board. To solve this incident check: Thermostat status: Check the signal range of the thermostat with the main control board through the Information parameter (see section Advanced settings, system settings) or approach the thermostat to the main control board if the thermostat recovers the communication, it is necessary to relocate it as it was out of range.
Page 50
Check which Lite thermostat is not working properly. To solve this incident check: Connection: Check the polarity of the main control board and thermostat connectors. Wiring: Disconnect the terminal from the Airzone connection bus and check that the voltage between the poles (A/-) and (B/-) is about 0.65 Vdc.
Page 51
Error 12: Main Board-Webserver communication error The system loses the communication with the webserver. Check the connection of the webserver to the Main board domotic bus. AZX6WSCLOUDDIN [C/R] AZX6WEBSCLOUD [C/R] Check the webserver is properly plugged to the production control board as well as the connection between the production control board AZX6CCP and the system main board.
Page 52
This incident blocks the control of the zone. To solve this incident check: Status of the control module of the radiant elements: Correctly powered. Status of the control module of the radiant elements and the main control board: Airzone connection bus LEDs are operating properly.
Page 53
Connection: Check the polarity of the connectors of the Main Control Board and the dehumidifier control module Wiring: Disconnect the terminal from the Airzone connection bus and check that the voltage between the poles (A/-) and (B/-) is about 0.65 Vdc.
Main control board status: Airzone connection bus LEDs are operating properly. Connection: Verify the polarity of the main control board and thermostat connectors. Wiring: Disconnect the terminal from the Airzone connection bus and check that the voltage between the poles (A/-) and (B/-) is about 0.65 Vdc.
Page 55
Status LED blinking red quickly: Wireless Lite Thermostat-Main control board communication error This incident blocks the control of the zone. Check that "Error 1" not appear in all thermostats. If so, verify the proper operation of the main board. To solve this incident, please check: Thermostat status: Check the signal range of the thermostat with the main control board through the Information parameter from remote zones or approach the thermostat to the main control board if the thermostat recovers the communication, it is necessary to relocate it as it was out of range.
Switch on Configured as Fixed IP address Switch off Solid Power supply AIRZONE HYDRONIC PRODUCTION CONTROL BOARD (AZX6CCPGAWI) Airzone cloud production control board incorporate LEDs that detect malfunctioning. Meaning Receiving data from domotic bus Blinking Green Transmitting data from domotic bus...
Data transmission from integration bus Blinking Data reception from integration bus Blinking Green AIRZONE PRODUCTION CONTROL BOARD (AZX6CCP) Airzone production control boards incorporate LEDs that detect malfunctions. Meaning Power supply Solid Blinking Microswitch performance Green Blinking Data transmission from AC unit bus...