Figure 3-19
Signal Lamp Battery Check
3.8.4
•
Remove the signal lamp front cover as shown in Figure 3-17.
•
To perform signal lamp battery check, press the push-button for 2 s and release it.
•
The amber LED is turned ON for 2 s and turned OFF indicating the battery is healthy.
•
In low battery condition, amber LED shows 5 blinks (1 blink/s).
•
Reinsert the signal lamp front cover after performing the battery check operation.
SICAM, Earth Fault Indicator, Manual
E50417-H8940-C600-A3, Edition 12.2022
Battery Activation During Installation
Installation and Commissioning
3.8 Signal Lamp Dimensions and Procedures