3.3 Panel & Sensor Connections
The BundGuard is supplied in one of two connectivity configurations. Option 1 as detailed below:
! Installation should only be carried out by suitable trained personnel.
Option 1 Terminal Configuration
Term.
Name
o
N
Incoming Power connection
1
Input Neutral
2
Input Live
3
Input Earth
Pump Power connection
4
Pump 1 Neutral
5
Pump 1 Live
6
Pump 1 Earth
7
Pump 2 Neutral
8
Pump 2 Live
9
Pump 2 Earth
Common Alarm 230Vac Output Connections
10
Common Neutral
11
Common LIVE
12
Common Earth
Telemetry (relay) connections
13
Pump2 Disable Relay
14
Pump1 Disable Relay
15
Mains Fail Relay
16
High Oil Relay
17
System Fault Relay
18
High Water Relay
19
Relay Common
Sensor Connection
20
Oil +VE
21
Oil -VE
22
High Water Probe (red)
23
Start Probe (Yellow)
24
Stop Probe (blue)
25
Common probe (Black)
Auxiliary Equipment connections ( Filter /flow meters)
26
GND
27
+12V
28
Pressure 1 input
29
Pressure 2 input
30
Flow input
Description
RCD Mains Neutral
RCD Mains Live
Mains Earth
Un-switched neutral for pump 1
Switched live for pump 1
Un-switch earth for pump 1
Un-switched neutral for pump 2
Switched live for pump 2
Un-switch earth for pump 2
Un-switched neutral for beacon or sounder
Switched live for beacon or sounder
Un-switched earth for beacon or sounder
Pump 2 disable NO relay contact
Pump 1 disable NO relay contact
Mains failure NC relay contact
High oil NO relay contact
System fault NO relay contact
High water NO relay contact
Common connection to all alarm relays
Positive switch connection to oil float switch
Negative switch connection to oil float switch
High water probe from sensor unit
Start probe from sensor unit
Stop probe from sensor unit
Common probe from sensor unit
Control panel signal ground
Control panel signal +12V
Pressure 1 sensor 4-20mA or switched input
Pressure 2 sensor 4-20mA or switched input
Flow rate sensor 4-20mA input
Bundguard 5 12.01.2022 Rev.4 12