Inputs / outputs
Configuring option module analog outputs using ION Setup

Digital inputs

Digital input applications

IRIG-B time synchronization

7EN05-0336-03
If your meter's analog output range does not match the range of the connected analog
sensor, you must calculate the full scale and zero scale values by analyzing the
system.
See the ION Reference, available from www.usa.siemens.com/pds for detailed
information about the Analog Output module and full scale and zero scale calculations.
You can configure option module analog outputs using ION Setup.
Analog outputs are available on the optional I/O modules you can connect to the base
of your meter.
Calculate your zero scale and full scale values based on the measured value and the
analog output range of your meter.
Make sure that the analog output port that you want to use is properly connected to an
analog receiver.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to Expansion Module > Option I/O Modules and select the module tab
that corresponds to the option module with the analog output you want to
configure.
4. Select the analog output channel and click Edit. The setup screen for that analog
output is displayed.
5. Configure the analog output by selecting the parameter and clicking Edit.
Parameter
Value/Range
Zero scale
0 to ±10
Full scale
0 to ±10
Port
Mode
Voltage, current
Related Topics
Option I/O modules configuration
Digital inputs are typically used for monitoring the status of contacts, such as status
contacts on circuit breakers.
They can also be used for pulse counting or input metering applications, such as
WAGES (water, air, gas, electricity, steam) monitoring, or conditional energy
applications, or IRIG-B time synchronization.
You can use a digital input to synchronize the meter time to an IRIG-B time source.
Description
9
The minimum source value that matches the minimum
analog output signal.
9
The maximum source value that matches the maximum
analog output signal.
The physical analog output port connection.
Determines whether the analog output is monitoring
voltage or current.