RS-485 (DTE) serial port
Baud rate .................................... 110 to 115,200 bps
Data bits...................................... 5, 6, 7, 8
Stop bits...................................... 1, 1.5, 2
Parity .......................................... Odd, Even, Mark, Space
Flow control ............................... XON/XOFF
Wire mode .................................. 4-wire
Isolation voltage, port to earth ground
Continuous ........................... 100 V
Dielectric withstand ............. 740 V
Power Requirement
Power supply range........................... 11–30 VDC
Recommended power supply
cFP-BP-4 system ........................ 15 W
cFP-BP-8 system ........................ 20 W
Power consumption .......................... 6.1 W + 1.1 (I/O module power
Physical Characteristics
Screw-terminal wiring ...................... 16–26 AWG copper conductor wire with
Torque for screw terminals ............... 0.5–0.6 N · m (4.4–5.3 lb · in.)
Weight............................................... 278 g (9.8 oz)
© National Instruments Corporation
rms
, verified by 5 s test
rms
requirements)
7 mm (0.28 in.) of insulation stripped from
the end