Summary of Contents for Schiedel RITE-VENT ICID PLUS
Page 1
ICID PLUS INSTALLATION INSTRUCTIONS 100 - 200mm Internal Diameter Twin Wall Insulated Chimney System for gas, oil, wood and multi-fuel applications (including condensing applications) Part of Standard Industries SAP Version 3 940002165 September 2018...
BS EN 15287-1 ACCEPTABLE ALTERNATIVE METHODS OF CONNECTION NOTE: These alternative methods do not apply to Republic of Ireland. Solid Wall Wall Band Solid Wall Wall Band Wall Sleeve Wall Sleeve Twin Wall Twin Wall Chimney System Chimney System Trim Collar Trim Collar Inspection Bend Inspection Bend...
Page 6
For minimum distance for Measured from back For minimum distance for Measured from back this configuration check of connecting flue this configuration check of connecting flue manufacturers distance pipe to outside manufacturers distance 450mm MAX pipe to outside 450mm MAX to combustibles surface of chimney to combustibles...
Page 14
Initial installation Removal of stove for servicing...
Page 15
Re-installation of stove after servicing...
Page 16
Increaser This component is used to increase from one diameter to the next diameter (e.g.) 125mm to 150mm. The component Anchor Plate brick or masonry chimney stack, an anchor plate must be used. The liner of the Anchor Plate chimney stack, or if TecnoFlex Plus liner has been used, inside the chimney as a liner, use the anchor plate with screw type connections.
Page 17
93˚ Tee including Drain Cap This component must be used in place of a 90° tee to connect from a connecting 93˚ condensate can drain down through the system to a drain point. This component is installed as per a standard pipe section. Int Ø...
Page 18
OFFSET DIMENSIONS with Standard Pipe Length 1460 Eff A 1642 1644 1644 960 Eff A 1155 1159 1161 1161 1165 750 Eff A 460 Eff A 293 Eff A 160 Eff A with Standard Pipe Length 1460 Eff A 1494 1509 1520 1535...
Page 19
FIRESTOP COMPONENTS Ventilated Support Plate Ventilated Support Plate Ventilated Firestop Plate Ventilated Firestop Plate Installation In Situ Non-Ventilated Bungalow Firestop Non-Ventilated Bungalow Firestop Support Plate with S/S Clamp Band Fire stop Plate...
Page 20
Wall Band 60mm 60mm Wall Band Wall Band and...
Page 21
Structural Wall Band Type W1 Structural Wall Band Structural Wall Band Structural Wall Band with Type W1...
Page 22
Base support Plate with Drain Top Plate Side Plates Wall Support Side Plates C min - Type 570...
Page 23
Arms Please note: It is the responsibility of the installer to ensure that the joist to which the roof support is being attached is load bearing and capable of withstanding the weight of the system being installed.
Page 24
1.5 metres maximum Ceiling Hanger Ceiling Hanger...
Page 26
Ignis-Protect IMPORTANT! Window and door lintels and their support areas, as well as other bearing elements must not be weakened! In case of uncertainty consult a structural engineer. TIP: The dimensions of the IGNIS-PROTECT wall bushings have already been matched to the standard centre-to-centre dimensions of wooden stud walls!
Page 27
NOTE: Ignis-Protect must not be NOTE: Ignis-Protect must shortened on site! not be shortened on site! IMPORTANT: follow the safe working notes on page 29. TIP: No gaps should be left in the studwork or the surrounding thermal insulation!
Page 28
TIP: The Ignis-Protect inner protection pipe and the outer protection pipe are basically designed for 24mm wall planking! NOTE: The vapour barrier must IMPORTANT: follow the safe not be damaged! working notes on page 29. TIP: The inner protection pipes and the assembly cap (A) remain in place until the stove connection pipe is in...
Page 29
Many building products, including chimney elements are manufactured using natural raw materials which contain proportions of crystaline quartz. During the mechanical processing of products, such as cutting and drilling, quartz Protection measures are required when dust is released which can get into the lungs. cutting and drilling.
Page 30
New Housing Airtightness Requirements Installation Support bracket Insulation Ø455 Protect Box Ø255 Sealing Tape Application Plasterboard 600 x 600 (EPDM) Vapour barrier Wooden substructure for plasterboard Support bracket Insulation Ø455 Protect Box Ø255 EPDM seal EPDM is fixed to the vapour barrier with tape and screwed to the wooden structure...
Page 31
Terminals Anti Splash Raincap Tapered Terminal Terminal OUTLET SITING Location Pressure Vapourising Burner 600mm 1000mm 750mm 2300mm 600mm 1000mm 1500mm less less than 600mm than 600mm 600mm 600mm 1500 1500 Chimney should Chimney should not penetrate 600 min not penetrate 600 min within the within the...
Page 32
TYPICAL EXTERNAL INSTALLATIONS Floor Mounted Installation Wall Mounted Installation with Base Drain Section Int Ø...
Page 33
LOAD BEARING DATA Internal Diameter Diagram A Diagram B COMPONENT WEIGHTS 1460 100mm 125mm 150mm 200mm...
For recommended fuels listings, please refer to the HETAS Guide www.hetas.co.uk In the event of a fault developing in the product due to defective materials or faulty manufacture Schiedel Chimney Systems undertake to replace the product only. Schiedel Chimney Systems cannot accept liability nor take any responsibility for the installation, building or redecorating costs or any other consequential losses arising.
Page 36
Complementary products and services from Schiedel Chimney Systems Schiedel Chimney Systems SCHIEDEL TRAINING ACADEMY Crowther Estate Based in Tyne & Wear, the HETAS Approved Training Washington Centre has a number of courses for chimney knowledge, Tyne & Wear NE38 0AQ maintenance and installation.