StyleCrest Revolv VMA3-50D36N Installation And Service Manual

StyleCrest Revolv VMA3-50D36N Installation And Service Manual

Gas fired high efficiency furnace
Table of Contents

Advertisement

GAS FIRED HIGH EFFICIENCY FURNACE
DOWNFLOW & DIRECT VENT (SEALED COMBUSTION)
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or
any other appliance.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone.
Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
:
If the information in these instructions is not followed exactly, a fire or explosion may
result causing property damage, personal injury, or loss of life.
: Improper installation, adjustment, alteration, service, or maintenance can cause injury or
property damage. Refer to this manual. For assistance or additional information, consult a qualified
installer, service agency, or fuel supplier.
: Do not use this appliance if any part has been underwater. Immediately call a qualified
service technician to inspect the appliance and to replace any part of the electrical or control system
that has been underwater.
PLEASE READ THESE INSTRUCTIONS PRIOR TO INSTALLATION, INITIAL FIRING, AND BEFORE PERFORMING
ANY SERVICE OR MAINTENANCE. THESE INSTRUCTIONS MUST BE LEFT WITH THE USER AND SHOULD BE
RETAINED FOR FUTURE REFERENCE BY QUALIFIED SERVICE PERSONNEL.
MG-518
ECN 0000-MA 151209
MODELS:
VMA3-50D36N, VMA3-75D36N,
VMC1-50D36N, VMC1-75D36N,
VMC1-50DV3N, VMC1-75DV3N
INSTALLATION AND SERVICE MANUAL
For installation in:
1. Manufactured Homes
2. Modular Homes/Buildings
3. Site Constructed—Residential (Single Story Dwellings)
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
STYLE CREST, INC.
2450 ENTERPRISE STREET
FREMONT, OH 43420
PHONE: (419) 332-7369
MADE IN USA

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Revolv VMA3-50D36N and is the answer not in the manual?

Questions and answers

Summary of Contents for StyleCrest Revolv VMA3-50D36N

  • Page 1 GAS FIRED HIGH EFFICIENCY FURNACE DOWNFLOW & DIRECT VENT (SEALED COMBUSTION) MODELS: VMA3-50D36N, VMA3-75D36N, VMC1-50D36N, VMC1-75D36N, VMC1-50DV3N, VMC1-75DV3N INSTALLATION AND SERVICE MANUAL For installation in: 1. Manufactured Homes 2. Modular Homes/Buildings 3. Site Constructed—Residential (Single Story Dwellings) FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
  • Page 2: Table Of Contents

    TABLE OF CONTENTS LIST OF SECTIONS BEGINNING PAGE SAFETY INFORMATION………………………………………………………………… 1 FURNACE SPECIFICATIONS………………………………………………………..7 VMA3 series……………………………………………………………………………… 7 VMC1 series……………………………………………………………………………... 8 Installation Parts Packages…………………………………………………………..10 III. GENERAL INSTRUCTIONS AND CLEARANCES…………………………………… 11 IV. GENERAL INSTALLATION……………………………………………………………… 13 Furnace Location………………………………………………………………………… 13 Base Installation………………………………………………………………………….. 15 Combustible Floor Base……………………………………………………………..
  • Page 3 Heat Exchanger………………………………………………………………………….. 50 Cleaning the Coil Air Side………………………………………………………..…. 50 House Air Blower………………………………………………………………………… 50 Return Air Filter…………………………………………………………………………... 50 Filter Maintenance Procedure……………………………………………………… 51 Filter Replacement…………………………………………………………………... 51 VIII. TROUBLE SHOOTING…………………………………………………………………... 51 Diagnostic Features……………………………………………………………………… 51 Troubleshooting Guide…………………………………………………………………... 53 APPENDIX-A REPLACEMENT PARTS……………………………………………… 58 APPENDIX-B WIRING DIAGRAM…………………………………………………….. 62 LIST OF FIGURES Combustible Floor Base……………………………………………………………..…………...
  • Page 4: Safety Information

    All installations and services must be performed by qualified service personnel. I. SAFETY INFORMATION This and the following page contain reproductions of the various warning and instruction labels placed on the Condensing Gas Furnaces. Please read and comply with the contents of these labels.
  • Page 5 All installations and services must be performed by qualified service personnel. This and the previous page contain reproductions of the various safety and instruction labels placed on Condensing Gas Furnaces. Please read and comply with the contents of these labels.
  • Page 6 All installations and services must be performed by qualified service personnel. This and the previous page contain reproductions of the various safety and instruction labels placed on the Condensing Gas Furnaces. Please read and comply with the contents of these labels.
  • Page 7 All installations and services must be performed by qualified service personnel. The following safety information should be read, understood, and followed by the installer. 1. Use only with type of gas approved for this furnace. Refer to furnace rating plate. 2.
  • Page 8 All installations and services must be performed by qualified service personnel. The vent and air intake elbows must be kept away from bushes, shrubs or any vegetation that may restrict the flow of flue products. It must also be kept clear of any leaves, weeds or other combustible materials. Keep the vent hood clear of snow.
  • Page 9 All installations and services must be performed by qualified service personnel. : Copper and brass tubing and fittings (except tin lined) shall not be used if the gas contains more than a trace (0.3 grains per 100 cubic ft.) of hydrogen sulfide gas.
  • Page 10: Furnace Specifications

    All installations and services must be performed by qualified service personnel. II. FURNACE SPECIFICATIONS MODEL VMA3-50D36 VMA3-75D36 INPUT IN BTUH 50,000 75,000 OUTPUT IN BTUH 48,000 72,000 MAIN ORIFICE-NAT. MAIN ORIFICE-LP GAS SUPPLY PRESSURE L.P. MINIMUM 11” IN.W.C. NAT. MINIMUM 4.5”IN.W.C.
  • Page 11: Vmc1 Series

    All installations and services must be performed by qualified service personnel. MODEL VMC1-50D36 VMC1-75D36 INPUT IN BTUH 50,000 75,000 OUTPUT IN BTUH 48,000 72,000 MAIN ORIFICE-NAT. MAIN ORIFICE-LP GAS SUPPLY PRESSURE L.P. MINIMUM 11” IN.W.C. NAT. MINIMUM 4.5”IN.W.C. L.P. MAXIMUM 14”...
  • Page 12 All installations and services must be performed by qualified service personnel. MODEL VMC1-50DV3 VMC1-75DV3 INPUT IN BTUH 50,000 75,000 OUTPUT IN BTUH 48,000 72,000 MAIN ORIFICE-NAT. MAIN ORIFICE-LP GAS SUPPLY PRESSURE L.P. MINIMUM 11” IN.W.C. NAT. MINIMUM 4.5”IN.W.C. L.P. MAXIMUM 14”...
  • Page 13: Installation Parts Packages

    All installations and services must be performed by qualified service personnel. INSTALLATION PARTS PACKAGES VMA3-50D36N VMA3-75D36N PARTS PKG# VS00S4248 VS00S4249 DESCRIPTION PART # PART # J-box cover V350020 V350020 Wire nut V300132 V300132 3" stainless steel hose clamp V300276 V300276 2-3/8"...
  • Page 14: General Instructions And Clearances

    All installations and services must be performed by qualified service personnel. III. GENERAL INSTRUCTIONS AND CLEARANCES – READ BEFORE START OF INSTALLATION 1. The BTU output capacity of the furnace proposed for installation should be based on a heat loss calculation made according to the manuals provided by the Air Conditioning Contractors of America (ACCA) or the American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc.
  • Page 15 All installations and services must be performed by qualified service personnel. c. American National Standard (ANSI-Z223.1/NFPA-54) for all gas-fired furnaces. d. American National Standard (ANSI-C1/NFPA-70 Electric Code for all electrical field wiring. e. These gas-fired units have been investigated under standards ANSI Z 21.47 CAN/CGA Z223-2001 Central Furnace test standards.
  • Page 16: General Installation

    All installations and services must be performed by qualified service personnel. IV. GENERAL INSTALLATION A. FURNACE LOCATION 1. For best performance, locate the furnace so that it is centralized with respect to the duct system. 2. The furnace installation is only intended for free air return through the furnace door louvers.
  • Page 17: Cottage Base

    All installations and services must be performed by qualified service personnel. Coil Cabinet Model: VE113S / VE213T Note: Coil cabinet cannot be utilized as a cottage base. VE113S VE213T Figure 1B. Cottage Base Model: VCOT-BASE For VMA3 models only. NOTE: Serves as a plenum for single story applications with exposed supply air systems.
  • Page 18: Base Installation

    All installations and services must be performed by qualified service personnel. B. BASE INSTALLATION – VMA3 models only 1. Combustible Floor Base Model: V70-BASE (for VMA3 models only) Use the base bottom panel as a template to mark floor opening locations (see Figure 2).
  • Page 19: Cottage Base

    All installations and services must be performed by qualified service personnel. connector duct. Remove the bottom panel. Cut an opening in the distribution duct slightly larger than the connector duct. (refer to Figure 2 for location of this cut.) Cut the connector duct to length. Install the connector duct. Bend over each tab. Insure an airtight seal by using high temperature sealant or tape on the joint.
  • Page 20: Alcove Installation

    All installations and services must be performed by qualified service personnel. C. ALCOVE INSTALLATION In this application, a minimum of 18 inches of clearance must be provided to the front of the unit. See Figure 4. Note – access to diagnostic view port. VMA3 SERIES VMC1 SERIES Figure 4.
  • Page 21 All installations and services must be performed by qualified service personnel. VMA3 SERIES VMC1 SERIES Figure 5. Do not obstruct any return air openings, including the return grille on the furnace. To do so may cause the furnace to activate the high limit and shut down.
  • Page 22: Fuel Piping

    All installations and services must be performed by qualified service personnel. E. FUEL PIPING Sizing and installation of fuel lines must be in accordance with Federal, State & Local regulations. Including the National Fuel Gas Code NFPA 54/ANSI-Z233.1 (Latest Edition). NOTE: These furnaces are designed to be gas piped through the left side or the bottom.
  • Page 23: General Venting Requirements

    All installations and services must be performed by qualified service personnel. occurs. Wait at least 24 hours for the circuit to fully dry before energizing the system. The furnace and its gas valve must be disconnected from the gas supply during pressure testing of the gas supply system at pressures in excess of 1/2 PSIG or 14 inches w.c F.
  • Page 24: Maximum Vent Length

    All installations and services must be performed by qualified service personnel. MAXIMUM VENT LENGTH VENT SIZE 2 IN. PVC FURNACE VENT EXHAUST COMBUSTION AIR INTAKE MODEL LENGTH VENT ELBOWS (NO.) (FT.) ELBOWS (NO.) VMA*/VMC* *Note the drain elbow supplied with furnace count as 1 elbow. **Note the two 45°...
  • Page 25: Connecting Exhaust Vent And Combustion Air Intake

    All installations and services must be performed by qualified service personnel. G. CONNECTING THE EXHAUST VENT AND COMBUSTION AIR INTAKE Figure 6. shows the typical exhaust vent and combustion air intake connection for VMA/VMC furnace. Figure 6. Models VMA and VMC have a removable top front panel that will allow for improved access to assist installation of the exhaust vent and combustion air intake connection to the top of the furnace.
  • Page 26 All installations and services must be performed by qualified service personnel. the conclusion of the vent pipe installation. This will insure a leak free return air compartment. Refer to Figure 6A. Figure 6A. NOTICE: The exhaust vent pipe must be supported every 4 feet. After making sure the length of the piping is correct glue all connections in place.
  • Page 27: Direct Venting Through A Sidewall

    All installations and services must be performed by qualified service personnel. gas flame. Should acid compounds form in your furnace, it may reduce the life of the furnace. H. Direct Venting Through a Sidewall 1. Vent And Combustion Air Pipes Vent and combustion air pipes may pass through a maximum wall thickness of 18 inches.
  • Page 28: Exhaust Vent Terminal Location Clearance Requirements

    All installations and services must be performed by qualified service personnel. b. The bottom edge of the vent termination elbow must be installed at least 12-inches above the outlet of intake termination elbow. c. The horizontal distance between the inlet and exhaust terminations should be minimized, when possible, and should never exceed 24- inches.
  • Page 29 All installations and services must be performed by qualified service personnel. • where wetting of components by condensate, or water vapor, could be detrimental to the operation of pressure regulators, relief valves, or any other equipment. d. The vent terminal shall be installed a minimum of 14-inches from any obstruction and 3-feet from an inside corner of an L-shaped structure.
  • Page 30: Vent Terminal Location Guidelines

    All installations and services must be performed by qualified service personnel. 4. Vent Terminal Location Guidelines : Bushes, shrubs, or any vegetation that may restrict the flow of flue products must be kept away from vent and air intake terminations. Terminations must also be kept clear of any leaves, weeds, combustible materials, snow, and ice build-up.
  • Page 31: Connecting The Furnace To Roof Vent/ Intake Terminations

    All installations and services must be performed by qualified service personnel. Figure 10: Typical Construction Details of Sidewall Vent and Air Intake Terminations 3. Finish the vent installation by caulking the annulus to seal around the two (2) holes where the thermoplastic pipes pass through the wall. 4.
  • Page 32 All installations and services must be performed by qualified service personnel. The furnace may be vented vertically through the roof. The outlet/inlet of the vent and air intake terminations shall be a minimum of 12 inches above highest anticipated snow level. The vent outlet must be installed a minimum of 12 in. above the air intake inlet.
  • Page 33: Condensate Drain Line And Trap Assembly

    All installations and services must be performed by qualified service personnel. CEILING: Frame out area around where PVC pipe is to penetrate ceiling. Cut a 2-3/8” diameter hole for 2” PVC in the ceiling and a corresponding hole in a firestop to be made of a minimum of 18 gauge galvanized metal large enough to cover the entire framed area.
  • Page 34: Electrical Wiring

    All installations and services must be performed by qualified service personnel. L. ELECTRICAL WIRING All wiring shall be performed by a qualified electrician or service person. The wiring must comply with local codes, the instructions in this manual, and in the absence of codes with the National Electrical Code ANSI/NFPA-70 (LATEST EDITION).
  • Page 35 All installations and services must be performed by qualified service personnel. IMPORTANT: The room thermostat should be installed 4 to 5 feet above the floor on an interior wall which is relatively free from direct sources of heat (sunlight or supply airflow) or exposure to cold (drafts from open windows and doors).
  • Page 36: Blower Motor Speed Wiring

    All installations and services must be performed by qualified service personnel. 4. BLOWER MOTOR SPEED WIRING Figure 15. BLOWER DELAY SETTINGS To delay fan Set Switch turn-on by: 15 sec. 30 sec. 45 sec. *60 sec. To delay fan Set Switch turn-off by: 60 sec.
  • Page 37 All installations and services must be performed by qualified service personnel. VMA3-50D36 ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE COOLING UNIT HTG Speed Recommended CLG Speed 24,000 MED-LOW 30,000 MED-HIGH 36,000 HIGH Furnace Airflow (CFM) vs. External Static pressure (in. WC.) Speed Tap \ Static Pressure...
  • Page 38 All installations and services must be performed by qualified service personnel. VMA3-75D36 ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE HTG Speed Recommended CLG Speed COOLING UNIT 24,000 MED-LOW MED-LOW 30,000 MED-LOW MED-HIGH 36,000 MED-LOW HIGH Speed Tap \ Furnace Airflow (CFM) vs.
  • Page 39 All installations and services must be performed by qualified service personnel. VMC1-50D36 ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE COOLING UNIT HTG Speed Recommended CLG Speed 24,000 MED-LOW 30,000 MED-HIGH 36,000 HIGH Furnace Airflow (CFM) vs. External Static pressure (in. WC.) Speed Tap \ Static Pressure...
  • Page 40 All installations and services must be performed by qualified service personnel. VMC1-75D36 ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE HTG Speed Recommended CLG Speed COOLING UNIT 24,000 MED-LOW MED-LOW 30,000 MED-LOW MED-HIGH 36,000 MED-LOW HIGH Speed Tap \ Furnace Airflow (CFM) vs.
  • Page 41 All installations and services must be performed by qualified service personnel. VMC1-50DV3 ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE COOLING UNIT HTG Speed Recommended CLG Speed 24,000 MED-LOW 30,000 MED-HIGH 36,000 HIGH Furnace Airflow (CFM) vs. External Static pressure (in. WC.) Speed Tap \ Static Pressure...
  • Page 42 All installations and services must be performed by qualified service personnel. VMC1-75DV3 ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE HTG Speed Recommended CLG Speed COOLING UNIT 24,000 MED-LOW MED-LOW 30,000 MED-LOW MED-HIGH 36,000 MED-LOW HIGH Speed Tap \ Furnace Airflow (CFM) vs.
  • Page 43: Field And Replacement Wiring

    All installations and services must be performed by qualified service personnel. : TURN OFF THE ELECTRICAL POWER to the furnace before attempting to change blower speed wiring. The furnace is factory wired to the ignition control with standard heating and cooling speeds. When changing motor speeds, simply switch the needed speed to either the heating or cooling terminal as applicable on the module to obtain the desired CFM.
  • Page 44: Starting The Unit

    All installations and services must be performed by qualified service personnel. V. STARTING THE UNIT A. SEQUENCE OF OPERATIONS AT ANY TIME THE CONTINUOUS SAFE OPERATION CHECK GAS VALVE IS IF FLAME SIMULATION CONDITION NOT ENERGIZED PRESENT OR ROLL-OUT SWITCH OPENS, SYSTEM ENERGIZES INDUCER FAN FOR 15 SECONDS AND CIRCULATOR BLOWER AT HEATING SPEED UNTIL SITUATION CORRECTION START...
  • Page 45 All installations and services must be performed by qualified service personnel. AFTER DELAY-TO-FAN-ON THE RETRY SEQUENCE MAIN PERIOD ENDS, CIRCULATING PROVIDES A 60 SECOND BURNER AIR FAN IS ENERGIZED AT WAIT BEFORE IGNITION OPERATION HEATING SPEED. THE (OPTIONAL) RETRY. RETRY IS ELECTRONIC AIR CLEANER ATTEMPTED WITH AN AND HUMIDIFIER ARE...
  • Page 46: Initial Start Up

    All installations and services must be performed by qualified service personnel. B. INITIAL START UP: This furnace does not have a pilot. It is equipped with a hot surface igniter which automatically lights the burner. Do not attempt to light the burner by hand. Check the following items before the initial start-up.
  • Page 47: Adjustment Of Btu Input Rate

    All installations and services must be performed by qualified service personnel. C. ADJUSTMENT OF BTU INPUT RATE: The orifice for this furnace was sized: 1) for natural gas having a heating value of 1025 BTU per cubic foot and a specific gravity of .65, or 2) for liquefied propane gas with a heating value of 2500 BTU per cubic foot and a specific gravity of 1.55.
  • Page 48: Burner Adjustment

    All installations and services must be performed by qualified service personnel. GAS PRESSURE CHART FOR VMA*/VMC* MODEL FURNACES SUPPLY PRESSURE MANIFOLD PRESSURE MAX 14” WC 3.5 + .3” WC MIN 4.5” WC MAX 14” WC PROPANE 10.0” + .3” WC MIN 11”...
  • Page 49: Setting Temperature Rise

    All installations and services must be performed by qualified service personnel. Figure 16. The VMA/VMC furnace models are direct vent design and do not require an air shutter adjustment (air shutters are not used) for proper flame characteristics. Burner box access cover must always be secured with all screws in place and tightened before operating furnace.
  • Page 50: Furnace Checkout Procedure

    All installations and services must be performed by qualified service personnel. F. FURNACE CHECKOUT PROCEDURE Before any system of gas piping is finally put into service, it shall be carefully tested to assure that it is gas tight as indicated in the Fuel Piping Section of this Furnace Manual.
  • Page 51: Installer's Instructions To User

    All installations and services must be performed by qualified service personnel. VI. INSTALLER'S INSTRUCTIONS TO USER: After completing the installation, the installer shall inform and/or demonstrate to the homeowner: 1. The location of all the instructions in the furnace and that the instructions must be kept along with instructions for any accessories in the plastic pouch.
  • Page 52: Electrical

    All installations and services must be performed by qualified service personnel. Label wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. A. ELECTRICAL: 1. Check diagnostic code through view port prior to removing access door. 2.
  • Page 53: Gasket/Sealing Materials

    All installations and services must be performed by qualified service personnel. necessary, clean the accessible portions of the housing and blower with a damp cloth. Vacuum to remove any lint or dust from the motor assembly. 5. GASKETS/SEALING MATERIALS Inspect all visible gaskets for signs of degradation or liquid seepage, especially any seals which were removed as part of the inspection.
  • Page 54: Filter Maintenance Procedure

    All installations and services must be performed by qualified service personnel. assure proper furnace operation. Follow the cleaning, removal and replacement procedure below. FILTER MAINTENANCE PROCEDURE The filter is located inside front door of the VMA/VMC. Remove filter retaining rod and remove dirty filter.
  • Page 55 All installations and services must be performed by qualified service personnel. If the sensed failure is in the system (external to the control), the LED will flash in the following flash-pause sequences to indicate failure status (each flash will last approximately 0.25 seconds, and each pause will last approximately 2 seconds).
  • Page 56: Troubleshooting Guide

    All installations and services must be performed by qualified service personnel. TROUBLESHOOTING GUIDE THE SYSTEM IS STARTED BY SETTING THE THERMOSTAT TO CALL FOR HEAT. THE FOLLOWING SHOULD HELP ESTABLISH THE TYPE OF MALFUNCTION OR DEVIATION FROM THE NORMAL OPERATION. TO USE THIS DIAGRAM, YOU JUST NEED TO FOLLOW THE INSTRUCTIONS IN THE BOXES.
  • Page 57 All installations and services must be performed by qualified service personnel. IS THERE LINE VOLTAGE CHECK THE INTEGRATED ACROSS INDUCER POWER CONTROL DIAGNOSTIC LED TERMINALS "IND" & "IND N" LAMP. RESET BY INTERRUPTING AT THE INTEGRATED CONTROL? POWER TO CONTROL FOR MORE THAN ONE SECOND.
  • Page 58 All installations and services must be performed by qualified service personnel. AFTER GAS VALVE CHECK FOR PROPER ADJUST TO 3.5" FOR NATURAL GAS OPENS, DO THE MANIFOLD PRESSURE. OR 10.0" WC FOR LP GAS BURNERS IGNITE? IS IGNITOR REPOSITION TO POSITIONED CORRECTLY? CORRECT LOCATION.
  • Page 59 All installations and services must be performed by qualified service personnel. DOES SYSTEM RUN UNTIL IS LED LIGHT CHECK ALL THERMOSTAT IS SATISFIED? ON INTEGRATED WIRING FOR CONTROL FLASHING? LOOSE CONNECTIONS. DOES BURNER SHUT OFF CHECK FOR SHORT IN WIRE TO WHEN THERMOSTAT IS THERMOSTAT AND CORRECT SATISFIED?
  • Page 60 All installations and services must be performed by qualified service personnel. IF LED LIGHT FLASHES: 1 FLASH, THEN PAUSE SYSTEM LOCKOUT 2 FLASHES, THEN PAUSE PRESSURE SWITCH STUCK CLOSED 3 FLASHES, THEN PAUSE PRESSURE SWITCH STUCK OPEN 4 FLASHES, THEN PAUSE OPEN LIMIT SWITCH OR ROLLOUT SWITCH 6 FLASHES, THEN PAUSE 115 VOLT AC POWER REVERSED...
  • Page 61: Appendix-Areplacement Parts

    All installations and services must be performed by qualified service personnel. APPENDIX – A REPLACEMENT PARTS...
  • Page 62 All installations and services must be performed by qualified service personnel.
  • Page 63 All installations and services must be performed by qualified service personnel.
  • Page 64 All installations and services must be performed by qualified service personnel.
  • Page 65: Appendix-Bwiring Diagram

    All installations and services must be performed by qualified service personnel. APPENDIX – B WIRING DIAGRAMS...