4.
Connection and Settings
Setting the ETERNUS DX/AF
Connection CM
Select the controllers (CM#0 and/or CM#1) of the ETERNUS DX/AF that are connected to the power synchro-
nized unit with the RS232C cable.
Select "CM#0" when the power synchronized unit is connected to the PWC port on controller 0. Select "CM#1"
when the power synchronized unit is connected to the PWC port on controller 1.
When different power synchronized units are connected to controller 0 and controller 1 in a duplicated config-
uration, select both "CM#0" and "CM#1".
Delay until Shutdown
Do not change the default setting (0 minute).
Set management unit interface
Select "Power Synchronized Unit".
Power Failure Signal
"Positive" (positive logic) is automatically set.
Low Battery Signal
"Negative" (negative logic) is automatically set.
UPS Shutdown Signal
Do not select the "Enable" checkbox.
"Positive" (positive logic) is set by default.
■ ETERNUS DX900 S5, ETERNUS DX8900 S4, and ETERNUS DX8700 S3/DX8900 S3
This section explains the setting items on the power synchronization setting screen for the ETERNUS DX900 S5,
ETERNUS DX8900 S4, and ETERNUS DX8700 S3/DX8900 S3.
Figure 12
ETERNUS DX900 S5, ETERNUS DX8900 S4, and ETERNUS DX8700 S3/DX8900 S3 setup (Setup
Power Management screen)
Auto Power
Select "Disable".
Power Resume
Select "Disable".
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
45
Copyright 2019 FUJITSU LIMITED
P3AM-8012-14ENZ0