Commissioning notes

Norms and standards
Service notes
Disposal notes
Siemens Building Technologies
HVAC Products
·
Commissioning work must be carried out by qualified staff
·
When commissioning the plant or when doing maintenance work, make the follow-
ing safety checks:
a)
Burner startup with flame detector dark-
ened
b)
Burner startup with flame detector ex-
posed to extraneous light
c)
Burner operation with simulated loss of
flame; for that purpose, darken the flame
detector during operation and maintain
that state
Conformity to EEC directives
- Electromagnetic compatibility EMC (immunity)
- Low-voltage directive
·
Maintenance work must be carried out by qualified staff
·
Each time a unit has been replaced, check to ensure that wiring is in an orderly
state and that the wires are firmly connected. Make the safety checks as detailed in
«Commissioning notes»
·
Use the service adapters KF8885 / KF8833 / KF8840 for only short periods of time
The unit contains electrical and electronic components and may not be disposed of
together with household waste.
Local and currently valid legislation must be observed.
Safety check
Anticipated response
Lockout at the end of «TSA»
Lockout after 40 seconds at the
latest
Repetition followed by lockout at
the end of «TSA»
89 / 336 EEC
73 / 23 EEC
3/12
CC1N7130en
15.10.2002