Page 1
R410A Commercial Air Conditioners Service Manual B Series Model: MDV‐V28WDHN1(AtB) MDV‐V36WDHN1(AtB) MDV‐V42WDHN1(AtB) MDV‐V48WDHN1(AtB) MDV‐V56WDHN1(AtB) MDV‐V60WDHN1(AtB)
Page 2
Atom B Series VRF 50/60Hz CONTENTS Part 1 General Information ................ 3 Part 2 Component Layout and Refrigerant Circuits ........ 7 Part 3 Control .................... 15 Part 4 Field Settings .................. 23 Part 5 Electrical Components and Wiring Diagrams ........ 32 Part 6 Diagnosis and Troubleshooting ............ 45 ...
Page 4
Atom B Series VRF 50/60Hz Part 1 General Information 1 Indoor and Outdoor Unit Capacities ............4 2 External Appearance .................. 5 3 Combination Ratio ..................6...
Page 5
Atom B Series VRF 50/60Hz 1 Indoor and Outdoor Unit Capacities 1.1 Indoor Units Table 1-1.1: Indoor unit abbreviation codes Abbreviation code Type One-way Cassette Compact Four-way Cassette Four-way Cassette High Static Pressure Duct Medium Static Pressure Duct Wall-mounted Ceiling and Floor Table 1-1.2: Indoor unit capacity range...
Page 6
Atom B Series VRF 50/60Hz 2 External Appearance 2.1 Indoor Units Table 1-2.1: Indoor unit appearance One-way Cassette Four-way Cassette Compact Four-way Cassette Wall-mounted High Static Pressure Duct Medium Static Pressure Duct Medium Static Pressure Duct (Arc Series Duct) Ceiling and Floor 2.2 Outdoor Units...
Page 7
Atom B Series VRF 50/60Hz 3 Combination Ratio Sum of capacity indexes of the indoor units Combination ratio = Capacity index of the outdoor unit Table 1-3.1: Indoor and outdoor unit combination ratio limitations Type Minimum combination ratio Maximum combination ratio...
Page 8
Atom B Series VRF 50/60Hz ‐i Part 2 Component Layout and Refrigerant Circuits 1 Piping Diagrams .................. 8 2 Refrigerant Flow Diagrams ............... 11 7 ...
Page 9
Atom B Series VRF 50/60Hz 1 Piping Diagrams Figure 2‐1.1: 28 model piping diagram Gas pipe Liquid pipe Filter Temperature sensor Low pressure switch Temperature 4 way valve sensor Oil seperator Refrigerant Compressor radiator module return Temperature hole sensor Distributor Temperature sensor Accumulator Filter DC motor Oil return capiliary ...
Page 10
Atom B Series VRF 50/60Hz ‐i Figure 2‐1.3: 42 model piping diagram Gas pipe Liquid pipe Filter Temperature sensor Low pressure switch Temperature 4 way valve sensor Oil seperator Refrigerant Compressor radiator module Temperature sensor High pressure Temperatu re senso r switch Distributor Accumulator Electronic expansion valve Oil return capiliar y...
Page 11
Atom B Series VRF 50/60Hz Figure 2‐1.3: 60 model piping diagram Gas pipe Liquid pipe Filter Temperature sense Low pressure switch 4 way valve Temperature sense Oil seperator Refrigerant Compressor radiator modile Temperature sense High pressure switch Distributor Temperature sense Silencer(Reserved) Oil return capiliary DC motor ...
Page 12
Atom B Series VRF 50/60Hz ‐i 2 Refrigerant Flow Diagrams Cooling operation Figure 2‐2.1:28/36/42/48/56/60 models refrigerant flow during cooling operation Oil return operation in cooling mode Figure 2‐2.4: 28/36/42/48/56/60 models refrigerant flow during oil return operation in cooling mode 11 ...
Page 13
Atom B Series VRF 50/60Hz Heating operation Figure 2‐2.7: 28/36/42/48/56/60 models refrigerant flow during heating operation Oil return operation in heating mode Figure 2‐2.10: 28/36/42/48/56/60 models refrigerant flow during oil return operation in heating mode 12 ...
Page 14
Atom B Series VRF 50/60Hz ‐i Defrosting operation Figure 2‐2.13: 28/36/42/48/56/60 models refrigerant flow during defrosting operation 13 ...
Atom B Series VRF 50/60Hz Part 3 Control 1 General Control Scheme Flowchart ............ 16 2 Stop Operation .................. 17 3 Startup Control .................. 17 4 Normal Operation Control ............... 18 5 Protection Control ................... 19 6 Special Control .................. 21 15 ...
Atom B Series VRF 50/60Hz 1 General Control Scheme Flowchart Sections 3-2 to 3-7 on the following pages detail when each of the controls in the flowchart below is activated. 2 Stop operation Abnormal shutdown System stop Thermo on 3 Startup control Compressor startup delay control Startup control for cooling operation Startup control for heating operation 6 Special control 4 Normal operation control Conditions met Component control during normal operation for oil return Oil return operation Compressor output control Conditions met Compressor step control for defrosting ...
Atom B Series VRF 50/60Hz 2 Stop Operation The stop operation occurs for one of the two following reasons: 1. Abnormal shutdown: in order to protect the compressors, if an abnormal state occurs the system makes a 'stop with thermo off' operation and an error code is displayed on the outdoor unit digital displays. 2. The system stops when the set temperature has been reached. 3 Startup Control 3.1 Compressor Startup Delay Control When the ODU is powered on again and the compressor delays about 7 minutes to start. After the compressor stops running, it takes about 4 minutes to restart, in order to prevent frequent compressor on/off and to equalize the pressure within the refrigerant system. 3.2 Startup Control for Cooling Operation Table 3‐3.1: Component control during startup in cooling mode Wiring Component 28‐60 model Control functions and states diagram label Controlled according to load requirement, operating Inverter compressor COMP ● frequency increased by 1 step / sec The outdoor unit fan start by 14 gears for 20 seconds before ...
Atom B Series VRF 50/60Hz 4 Normal Operation Control 4.1 Component Control during Normal Operation Table 3‐4.1: Component control during normal cooling operation Wiring diagram Component 28‐60 model Control functions and states label Inverter compressor COMP Controlled according to load requirement ● Fan speed controlled according to heat exchanger temperature DC fan motor FAN ● (T3), outdoor ambient temperature (T4),discharge temperature (T5)and compressor frequency. Electronic expansion valve EEV ● Controlled according to discharge temperature Four-way valve ST1 ...
Atom B Series VRF 50/60Hz 5 Protection Control 5.1 High Pressure Protection Control (exclude model 28) This control protects the system from abnormally high pressure and protects the compressors from transient spikes in pressure. Figure 3‐5.1: High pressure protection control Normal operation > 4.4MPa < 3.2MPa High pressure protection, error code P1 is displayed Notes: 1. P : Discharge pressure When the discharge pressure rises above 4.4MPa the system displays P1 protection and the unit stops running. When the discharge pressure drops below 3.2MPa, the compressor enters re-start control. 5.2 Low Pressure Protection Control ...
Page 21
Atom B Series VRF 50/60Hz 5.4 Compressor and Inverter Module Protection Control This control protects the compressors from abnormally high currents and protects the inverter modules from abnormally high temperatures. Figure 3‐5.4: Compressor current protection control Normal operation Current ≥ Current Current < Current Compressor current protection, error code P3 is displayed 5.5 Disable Cooling Control When the outdoor ambient temperature drops below or equal to -15°C, cooling mode is disabled to prevent low compression ratios which can result in insufficient compressor internal oil lubrication, and prevent humid compressed in low superheat of compressor bottom conditions. When the outdoor ambient temperature rises above or equal to -14°C, the ...
Atom B Series VRF 50/60Hz 6 Special Control 6.1 Oil Return Operation In order to prevent compressors from running out of oil, the oil return operation is conducted to recover oil that has flowed out of the compressor(s) and into the piping system. This operation is performed for all units including units that are in standby. Timing of oil return operation: When the initial cumulative operating time reaches every 8 hours. Tables 3-6.1 and 3-6.2 show component control during oil return operation in cooling mode. Table 3‐6.1: Outdoor unit component control during oil return operation in cooling mode Wiring diagram Component 28‐60 model Control functions and states label Inverter compressor COMP Fixed frequency ● DC fan motor FAN ● Normal control as cooling operation Electronic expansion valve EEV1 ● Position 300 (steps) Four-way valve ST1 ...
Page 23
Atom B Series VRF 50/60Hz 6.2 Defrosting Operation In order to recover heating capacity, the defrosting operation is conducted when the outdoor unit heat exchanger is performing as an evaporator. The defrosting operation is controlled according to outdoor ambient temperature, outdoor heat exchanger temperature, indoor heat exchanger temperature and outdoor unit running time. When the outdoor unit is running in defrosting, the digital display on outdoor main PCB will display “df”. Table 3‐6.5: Outdoor unit component control during defrosting operation Wiring diagram Component 28‐60 model Control functions and states label Inverter compressor COMP Fixed frequency ●...
Page 24
Atom B Series VRF 50/60Hz Part 4 Field Settings 1 Outdoor Unit Field Settings ..............24...
Page 25
Atom B Series VRF 50/60Hz 1 Outdoor Unit Field Settings Figure 4-1.1: 28 model outdoor unit main PCB Figure 4-1.2: 28 model outdoor unit communication switchboard...
Page 26
Atom B Series VRF 50/60Hz Table 4-1.1: 28 model outdoor unit main PCB switch settings Switch Switch Setting Description positions Press SW1 to enter the forced cooling function; Force cooling Press it again to exit the forced cooling function. Spot check...
Page 27
Atom B Series VRF 50/60Hz Figure 4-1.3: 36/42/48/56 model outdoor unit main PCB Figure 4-1.4: 36/42/48/56 model outdoor unit communication switchboard...
Page 28
Atom B Series VRF 50/60Hz Table 4-1.2: 36/42/48/56 model outdoor unit main PCB switch settings Switch Switch Setting Description positions Press SW1 to enter the forced cooling function; Force cooling press it again to exit the forced cooling function. Spot check...
Page 29
Atom B Series VRF 50/60Hz Table 4-1.2: 36/42/48/56 model outdoor unit main PCB switch settings (continued) Switch Switch Setting Description positions S4=0000 Network address of ODU: 0(default) S4=1000 Network address of ODU: 1 S4=0100 Network address of ODU: 2 S4=1100...
Page 30
Atom B Series VRF 50/60Hz Figure 4-1.3: 60 model outdoor unit main PCB Table 4-1.2: 60 model outdoor unit main PCB switch settings Switch Switch Setting Description positions Press SW1 to enter the forced cooling function; Force cooling press it again to exit the forced cooling function.
Page 31
Atom B Series VRF 50/60Hz Table 4-1.2: 60 model outdoor unit main PCB switch settings (continued) S2=0000 First on priority mode (by default) S2=1000 Cooling priority mode S2=0100 Automatic priority mode S2=1100 In response to heating mode only S2=0010 In response to cooing mode only...
Page 32
Atom B Series VRF 50/60Hz Table 4-1.3: Spot check display table (for all model) Parameters displayed on DSP Remarks Actual value = value displayed Operating frequency Operating mode Refer to Note 1 Operating fan speed level Refer to Note 2...
Page 33
Atom B Series VRF 50/60Hz Part 5 Electrical Components and Wiring Diagrams 1 Outdoor Unit Electric Control Box Layout ..........33 2 Outdoor Unit Main PCB ................35 3 Wiring Diagrams ..................42...
Page 34
Atom B Series VRF 50/60Hz 1 Outdoor Unit Electric Control Box Layout Figure 5-1.1: Front view of 28 model electric control box Power input and power filter Module board PFC module IPM module DC fan motor control module Output control assembly Main control board Figure 5-1.2: Front view of 36/42/48/56 model electric control box...
Page 35
Atom B Series VRF 50/60Hz Figure 5-1.3: Front view of 60 model electric control box Switching IPM module power supply module Power supply Power supply and Main control board power filter...
Page 36
Atom B Series VRF 50/60Hz 2 Outdoor Unit Main PCB 2.1 Ports Figure 5-2.1: 28 model outdoor unit main PCB ports Table 5-2.1: 28 model main PCB ports Label in Port code Content Port voltage Figure 5-1.1 CN6/CN6-1 Earth Power input...
Page 37
Atom B Series VRF 50/60Hz Figure 5-2.2: 36/42/48/56 model outdoor unit main board ports Table 5-2.2: 36/42/48/56 model outdoor unit main board ports Label in Code Content Port voltage Figure 5-1.2 CN27 communication port 0-5V DC Main board power supply port;...
Page 38
Atom B Series VRF 50/60Hz Figure 5-2.3: 28/36/42/48/56 model outdoor unit Communication converter board PCB Ports Table 5-2.3: 28/36/42/48/56 model communication converter board PCB ports Label in Port code Content Port voltage Figure 5-1.3 P Q E X Y E communication port 2.5-2.7V DC...
Page 39
Atom B Series VRF 50/60Hz Figure 5-2.4: 60 model outdoor unit main board ports Table 5-2.4: 60 model outdoor unit main board ports Label in Port code Content Port voltage Figure 5-1 CN502 Power input port AC 220V CN501 Power input port...
Page 40
Atom B Series VRF 50/60Hz Figure 5-2.5: 60 model outdoor unit filter board Ports Table 5-2.4: 60 model filter board ports Label in Port code Content Port voltage Figure AC Power Input AC 220V AC Power Input AC 220V AC Power Output...
Page 41
Atom B Series VRF 50/60Hz 2.2 Components 2.2.1 LED indicator Table 5-2.5: LED indicator Indicator LED indicator function and status Inverter module operating indicator (red light). Continuously on if the compressor is LED101 running normally, quick flashing (5Hz) if an inverter module error has occurred slow flashing (1Hz) if the machine is in standby mode.
Page 42
Atom B Series VRF 50/60Hz 2.2.3 System check button On pressing Spot check button, the parameters listed in Table 5-2.6 will be displayed in sequence. Table 5-2.7: 28/36/42/48/56/60 model system check Parameters displayed on DSP Remarks Actual value = value displayed...
Page 43
Atom B Series VRF 50/60Hz 3 Wiring Diagrams Figure 5-3.1: 28 model wiring diagram Component code Description Component code Description CH1-CH4 Magnetic ring STF1 Four-way valve COMP Compressor Refrigerant radiator temperature sensor EEV1 Electronic expansion valve Power supply terminal DC fan...
Page 44
Atom B Series VRF 50/60Hz Figure 5-3.2: 36/42/48/56 model wiring diagram Component code Description Component code Description Rectifier bridge stacking Relay CH1-CH7 Magnetic ring STF1 Four-way valve COMP. Compressor Outdoor heat exchanger temperature sensor AC current transformer Outdoor ambient temperature sensor...
Page 45
Atom B Series VRF 50/60Hz Figure 5-3.3: 60 model wiring diagram Component code Description Component code Description 3-slot power supply terminal H-PRO High pressure switch Communication converter board L-PRO Low pressure switch CHI-CH6 Magnetic ring STF1 Four-way valve COMP. Compressor...
Page 46
Atom B Series VRF 50/60Hz Part 6 Diagnosis and Troubleshooting 1 Error Code Table ..................46 2 Troubleshooting ..................47...
Page 47
Atom B Series VRF 50/60Hz 1 Error Code Table Table 6-1.1: Error code table Error code Content Note Communication fault between main control board and communicate converter board 28-56 models Communication fault between main control board and communicate converter board...
Page 48
Atom B Series VRF 50/60Hz 2 Troubleshooting 2.1 Warning Warning All electrical work must be carried out by competent and suitably qualified, certified and accredited professionals and in accordance with all applicable legislation (all national, local and other laws, standards, codes, rules, regulations and other legislation that apply in a given situation).
Page 49
Atom B Series VRF 50/60Hz 2.2 C0: Communication fault between main board and communicate converter board (For 28-56 models) 2.2.1 Digital display output 2.2.2 Description Communication fault between main board and communicate converter board. The system stops running.
Page 50
Atom B Series VRF 50/60Hz 2.3 H0: Communication fault between main board and communicate converter board (For 60 model) 2.3.1 Digital display output 2.3.2 Description Communication fault between main board and motor control module. 2.3.3 Trigger / recover condition ...
Page 51
Atom B Series VRF 50/60Hz 2.4 E2: Communication error between outdoor unit and indoor units (For all models) 2.4.1 Digital display output 2.4.2 Description Communication error between outdoor unit and indoor units. The system stops running. Error code is displayed on the outdoor unit PCB.
Page 52
Atom B Series VRF 50/60Hz 2.4.5 Procedure Communication wires P Q E have short Reconnect the communication wires circuited or disconnected Communication wires P Q E are not Connect the communication wires in a connected in a daisy chain daisy chain...
Page 53
Atom B Series VRF 50/60Hz Switch Switch positions Description S1-2 is ON, forced clearing of IDU address S1-2 is OFF, Automatic addressing(default) Press indoor unit’s receiver button for 5 seconds, the indoor unit’s communication address code is displayed. Table 6-2.1: Communication address code...
Page 54
Atom B Series VRF 50/60Hz 2.5 E4: Temperature sensor (T3/T4) fault (For all models) 2.5.1 Digital display output 2.5.2 Description Outdoor heat exchanger temperature sensor (T3) error or outdoor ambient temperature sensor (T4) error. The system stops running.
Page 55
Atom B Series VRF 50/60Hz 2.6 E5: Abnormal power supply voltage (For all models) 2.6.1 Digital display output 2.6.2 Description Abnormal power supply voltage. The system stops running. Error code is displayed on the outdoor unit PCB.
Page 56
Atom B Series VRF 50/60Hz 2.7 E6: DC fan motor error; Eb: E6 protection appears 6 times in one hour (For all models) 2.7.1 Digital display output E6 or Eb 2.7.2 Description E6:DC fan motor error; Eb: E6 protection appears 6 times in one hour ...
Page 57
Atom B Series VRF 50/60Hz 2.8 E9: EEPROM error (For all models) 2.8.1 Digital display output 2.8.2 Description EEPROM error The system stops running. Error code is displayed on the outdoor unit PCB. 2.8.3 Trigger / recover condition ...
Page 58
Atom B Series VRF 50/60Hz 2.9 E.9.: Compressor parameters mismatch (For all models) 2.9.1 Digital display output E.9. 2.9.2 Description Main control chip detect the power setting number mismatch the model, the unit will display E.9. error. The system stops running.
Page 59
Atom B Series VRF 50/60Hz 2.10 EF: PFC fault (For all models) 2.10.1 Digital display output 2.10.2 Description PFC fault protection. The system stops running. Error code is displayed on the outdoor unit PCB. 2.10.3 Trigger / recover condition ...
Page 60
Atom B Series VRF 50/60Hz 2.11 EH: Refrigerant radiator temperature sensor error (For all models) 2.11.1 Digital display output 2.11.2 Description Refrigerant radiator temperature TL sensor error. The system stops running. Error code is displayed on outdoor unit PCB.
Page 61
Atom B Series VRF 50/60Hz ℃ 2.12 EP: Outdoor ambient temperature is lower than -15 in cooling operation (For all models) 2.12.1 Digital display output 2.12.2 Description Outdoor ambient temperature is lower than -15℃ in cooling operation. The system stops running.
Page 62
Atom B Series VRF 50/60Hz 2.13 F1: DC bus voltage protection (for all models) 2.13.1 Digital display output 2.13.2 Description F1 indicates DC bus voltage protection. The system stops running. Error code is displayed on the outdoor unit PCB.
Page 63
Atom B Series VRF 50/60Hz 2.14 H4: L (L0/L1) fault occurs three times in one hour (For all models) 2.14.1 Digital display output 2.14.2 Description The L (L0/L1) fault occurs three times in one hour. The system stops running.
Page 64
Atom B Series VRF 50/60Hz 2.15 H7: The number of online indoor units have decreased/increased (For all models) 2.15.1 Digital display output 2.15.2 Description The number of online indoor units have decreased/increased. The system stops running. Error code is displayed on the unit with the error.
Page 65
Atom B Series VRF 50/60Hz 2.16 HF: Indoor unit and outdoor unit program mismatch (For all models) 2.16.1 Digital display output 2.16.2 Description Indoor unit and outdoor unit program mismatch. The system stops running. Error code is displayed on the unit with the error.
Page 66
Atom B Series VRF 50/60Hz 2.17 PL: Radiator surface high temperature protection (For all models) 2.17.1 Digital display output 2.17.2 Description Radiator surface high temperature protection. The system stops running. Error code is displayed on outdoor unit PCB.
Page 67
Atom B Series VRF 50/60Hz 2.18 P1: Discharge pipe high pressure protection (For all models) 2.18.1 Digital display output 2.18.2 Description Discharge pipe high pressure protection. The system stops running. Error code is displayed on the outdoor unit PCB.
Page 68
Atom B Series VRF 50/60Hz 2.18.5 Procedure High pressure sensor connection on main Ensure the sensor is connected properly PCB is loose High pressure sensor has short-circuited or Replace the sensor failed Discharge part of the refrigerant. Add oil if...
Page 69
Atom B Series VRF 50/60Hz 2.19 P2: Suction pipe low pressure protection (For all models) 2.19.1 Digital display output 2.19.2 Description Suction pipe low pressure protection. The system stops running. Error code is displayed on outdoor unit PCB.
Page 70
Atom B Series VRF 50/60Hz 2.19.5 Procedure the outdoor ambient temperature is too Stop the unit Low pressure sensor connection on main Ensure the sensor is connected properly PCB is loose Low pressure sensor has short-circuited or Replace the sensor...
Page 71
Atom B Series VRF 50/60Hz 2.17 P3: Compressor current protection (For all models) 2.19.6 Digital display output 2.19.7 Description P3 indicates current protection on compressor. The system stops running. Error code is displayed on the outdoor unit PCB.
Page 72
Atom B Series VRF 50/60Hz The condenser heat exchange is poor Inspect the system and fix the error The high pressure side is blocked, caused Inspect the system and fix the error by crushed or bent pipe or blocked EXV...
Page 73
Atom B Series VRF 50/60Hz 2.18 P4: Discharge temperature protection (For all models) 2.18.1 Digital display output 2.18.2 Description Discharge temperature protection. The system stops running. Error code is displayed on the unit with the error. 2.18.3 Trigger / recover condition ...
Page 74
Atom B Series VRF 50/60Hz 2.18.5 Procedure Discharge pipe temperature sensor Ensure the sensors and switch are connected and/or discharge temperature switch properly connections on main PCB are loose Compressor top temperature sensor and/or discharge pipe temperature Replace the faulty sensor(s)
Page 75
Atom B Series VRF 50/60Hz 2.19 P5: Outdoor heat exchanger temperature protection (For all models) 2.19.1 Digital display output 2.19.2 Description Outdoor heat exchanger temperature protection. The system stops running. Error code is displayed on the unit with the error.
Page 76
Atom B Series VRF 50/60Hz 2.19.5 Procedure Outdoor heat exchanger temperature Ensure the sensor is connected properly sensor connection on main PCB is loose Outdoor heat exchanger temperature Replace the sensor sensor has short-circuited or failed Make sure the combination ratio is less than...
Page 77
Atom B Series VRF 50/60Hz 2.20 P8: Typhoon protection (For all models) 2.20.1 Digital display output 2.20.2 Description P8 indicates strong wind protection. The system stops running. Error code is displayed on the outdoor unit PCB. 2.20.3 Trigger / recover condition ...
Page 78
Atom B Series VRF 50/60Hz 2.21 P9: Poor reversing of four-way valve (For all models) 2.21.1 Digital display output 2.21.2 Description P9 indicates poor reversing of four-way valve. The system stops running. Error code is displayed on the outdoor unit PCB.
Page 79
Atom B Series VRF 50/60Hz 2.22 PE: Evaporator high temperature protection (For all models) 2.22.1 Digital display output 2.22.2 Description Evaporator high temperature protection The system stops running. Error code is displayed on the outdoor unit PCB.
Page 80
Atom B Series VRF 50/60Hz 2.23 L0/L1/L2/L4/L5/L7/L8/L9: L category of inverter module protection (For all models) 2.23.1 Digital display output L0/L1/L2/L4/L5/L7/L8/L9 2.23.2 Description Compressor inverter module protection. The system stops running. Error code is displayed on the outdoor unit PCB.
Page 81
Atom B Series VRF 50/60Hz 2.23.6 L5: Zero speed protection There is abnormal noise of Replace the compressor compressor when startup or running Replace the inverter module 2.23.7 L7: Phase sequence error Reconnect cables based Compressor wiring is loose on wiring diagram...
Page 82
Atom B Series VRF 50/60Hz 2.23.8 L8 / L9 troubleshooting L8/L9 Reconnect the cables based on Compressor wiring is not properly wiring diagram The resistance between 3 phases of compressor is over 5Ω Replace the compressor The insulation resistance of compressor is less than 100Ω...
Page 83
Atom B Series VRF 50/60Hz 2.23.9 L1: DC bus low voltage protection Voltage of power supply is 166-265V? Provide normal power supply Check the wiring between main control board and Connect again filter board is correct or not. Repower on and waiting for 10S,and then test the voltage of CN4 port "RL"...
Page 84
Atom B Series VRF 50/60Hz 2.23.11 Compressor replacement procedure Step 1: Remove faulty compressor and remove oil Remove the faulty compressor from the outdoor unit. Before removing the oil, shake the compressor so as to not allow impurities to remain settled at the bottom.
Page 85
Atom B Series VRF 50/60Hz 2.23.12 Specific error codes for inverter module protection The specific error codes L0, L1, L2, L4, L5, L7, L8 and L9 can alsobe obtained from the inverter module LED indicators. If an inverter module error has occurred, one of inverter module LED indicators is continuously on and the other one of inverter module LED indicators flashes Table 6-2.3: Errors indicated on LED...
Page 86
Ver. 2021‐09 Midea Building Technologies Division Midea Group Add.: Midea Headquarters Building, 6 Midea Avenue, Shunde, Foshan, Guangdong, China Postal code: 528311 mbt.midea.com / global.midea.com Note: Product specifications change from time to time as product improvements and developments are released and may vary from those in this document. ...