Voice Options

5.
Press * to add rows, Press ENTER to edit data.
panel number
report supervisories
6.3 Voice Options
6.3.1 Edit Timers
1.
Login to the panel. The panel will automatically access the Main Menu.
2.
Select 6 for Network Programming.
3.
Select 7 for Voice Options.
4.
Choose Site.
5.
Select 1 for Edit Timers
Control Lockout
The Control Lockout countdown timer is set to the programmed value when an LOC gains ECS Control. The timer starts over upon any key
press at the ECS Control LOC. While the Control Lockout timer is active, an LOC of equal priority must request ECS control. The Control
Lockout timer is cleared when ECS Control is relinquished. The Control Lockout Timer does not apply to ECS Super User control.
Select Immediate/Timer/Never
Range 0-720 min/0-59 sec
Auto Reset ECS MIC Triggered Event
If you select the Timer, the Event will automatically reset after being active for the programmed time. If Event Disabled is selected, the event
will not be allowed to be activated from an LOC Station. Selecting Never will require an Emergency System Reset to be performed to reset
the event.
Select Never/Timer/Event Disabled, Range from 1-240 min.
6.3.2 Edit Voice Commands
When a voice output group is selected to be activated by a zone, the cadence pattern choice does not apply. For voice output groups, one of
six system wide voice commands will activate instead of the cadence pattern.
1.
Login to the panel. The panel will automatically access the Main Menu.
2.
Select 6 for Network Programming Menu.
3.
Select 7 for Voice Options.
4.
Choose Site.
5.
Select 2 for Edit Voice Commands.
6.
Select the command you wish to edit:
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
primary account number
primary receiver number
P# ASTP Primary.... Test Secondary... Test
01:=03 YYYY R009:321456 N R013:987456 N
02:=02 NNYN R015:123456 N R014:654321 N
*
=Add Row
panel number
report event by point (Y=point, N=zone)
report alarms
report troubles
Figure 6.1 Communicator Reporting
ECS Timer
Control Lockout
Auto Reset ECS MIC Triggered Event
Auto Reset ECS Event 1
Auto Reset ECS Event 2
Auto Reset ECS Event 3
Auto Reset ECS Event 4
Auto Reset ECS Event 5
Auto Reset ECS Event 6
Auto Reset ECS Event 7
Auto Reset ECS Event 8
Table 6.1 Auto Reset ECS MIC Triggered Event Timer Menu
test primary
account
Option
Immediate/Timer/Never
Never/Timer/Event Disabled
Never/Timer/Event Disabled
Never/Timer/Event Disabled
Never/Timer/Event Disabled
Never/Timer/Event Disabled
Never/Timer/Event Disabled
Never/Timer/Event Disabled
Never/Timer/Event Disabled
Never/Timer/Event Disabled
Network Management
secondary receiver number
secondary account number
test secondary account
73