S E R V I C E C O N F I G U R AT I O N S , C O N D U C TO R S
—
Conductors
NOTICE
The SPD unit's performance will be degraded if the
conductors are (a) too long, (b) are of too small a wire
gauge, (c) have too many bends or (d) have sharp bends.
Les performances du SPD seront dégradées si les
conducteurs sont (a) trop longs, (b) d'un calibre de fil
trop faible, (c) présentent trop de courbures ou (d) ont
des courbures trop prononcées.
The factors listed above should be addressed during the
design of an installation to reserve a suitable place for
the OVRHTP series unit next to its point of connection
to the electrical system. The selected mounting location
should allow for the shortest possible conductor runs
and a direct route with a minimum of bends. If bends are
required, they should be sweeping bends. Do not make
sharp 90° bends for appearance purposes because
they will decrease the effectiveness of the OVRHTP
series unit.
Binding or twisting conductors together using cable
ties or electrical tape improves the protection
performance of the device.
—
Wiring color installation guide
Voltage (V)
120
127
220
230
240
277
347
480
240/120
480/240
208Y/120
380Y/220
400Y/230
415Y/240
480Y/277
600Y/347
240Δ /120
208
240
380, 400, 415
480
600
230 (for TNC grounding systems)
230 (for TNS grounding systems)
230 (for IT grounding systems)
230 (for TT grounding systems)
Upstream overcurrent protection device (OCPD)
The OVRHTP series units can either be Type 1 or Type 2. Please refer
to the SPD types chart to determine the SPD type for the unit.
—
SPD types
Country SPD
is installed in
United States and
all other countries
Canada
The OVRHTP series unit is a one-port SPD and is to be connected in
parallel with the electrical system. It may be connected via a circuit
breaker, molded case switch, fused switch, or connected directly to
the bus of the panelboard or switchboard (local and national electric
codes take precedence). If direct bus connection is used, ABB
recommends installing the OVRHTP series unit behind a disconnect
switch or other disconnecting means for ease of serviceability.
If the unit is Type 2, the following OCPD is recommended:
Si l'unité est de type 2, il est recommandé d'utiliser le dispositif
suivant de protection contre les surintensités:
kA
60–100
120–200
240–400
A, L1
B, L2
–
Black
–
Black
–
Brown
–
Brown
–
Black
–
Black
–
Black
–
Black
Black
–
Brown
–
Black
Red
Black
Brown
Black
Brown
Brown
Orange
Brown
Orange
Black (A)
Black (B)
Black
Orange (HL)
Black
Red
Black
Red
Black
Brown
Brown
Orange
Black (A)
Black (B)
Brown
–
Brown
–
Brown
–
Brown
–
Polycarbonate enclosure
Metal and stainless steel enclosure
UL 1283
Not UL 1283
SPD Type 2
SPD Type 1
SPD Type 2
SPD Type 1
United States and all other countries
États-Unis et tous les autres pays
30 A max.
100 A max.
200 A max.
C, L1
Neutral
–
–
–
–
–
–
–
–
Red
Orange
Blue
Gray
Gray
Yellow
Yellow
Black (C)
Blue
Blue
Blue
Gray
Yellow
Black (C)
–
–
–
–
7
UL 1283
Not UL 1283
SPD Type 2
SPD Type 1
SPD Type 2
SPD Type 2
Canada
30 A max.
50 A max.
90 A max.
Ground
White
Green/yellow
White
Green/yellow
Blue
Green/yellow
Blue
Green/yellow
White
Green/yellow
White
Green/yellow
White
Green/yellow
White
Green/yellow
White
Green/yellow
White
Green/yellow
White
Green/yellow
Blue
Green/yellow
Blue
Green/yellow
White
Green/yellow
White
Green/yellow
White
Green/yellow
White
Green/yellow
–
Green/yellow
–
Green/yellow
–
Green/yellow
–
Green/yellow
–
Green/yellow
Blue
Green/yellow
Blue
Green/yellow
Blue
Green/yellow
Blue
Green/yellow