1 - GENERALITIES 1.1 - DESCRIPTION Gialix range boilers are confined under a compact casing with removable front panel for easy access to any components. includes stainless steel reinforced heating elements which are easy to access and to remove from the bottom of the boiler.
1.2 - Technical data description 36 kw 48 kw 72 kw 120 kw 196 kw maximum power (factory supply) 36 kw 48 kw 72 kw 120 kw 196 kw power steps power supply 400 V TRI 50 Hz adjustment of the max power by coupling P4 = 48 kw P4 = 96 kw P4 = 168 kw...
«Control settings» -§ 2.5.2) (Ref. 710043) ➠ Ambience thermostat (TH) with timer for weekly schedule. For ambience temperature monitoring without ➠ DHW temperature sensor (for Gialix MA). Supplied automatic temperature adjustment of the boiler’s (Ref. 710029) with Gialix MA Comfort + requested temperature (see «Control settings»...
36 kW – 48 kW – 72 kW 1.5 boiler description outgoing water return water electric suply 100°C overheat cut-out With manual reset terminals boiler sensor power contactors water presence detector terminals for control system control panel fuse over pressure relief valve electronic card 3 bars draining tape...
Page 10
196 kW return water outgoing water 100°C overheat cut-out with manual reset terminals power contactors water presence detector control panel terminals for control system draining tap electronic card 5 heating elements clamps for wires of the control accessories...
2.1 - BASIC HYDRAULIC CIRCUITS Gialix range electric boilers are designed for direct connection to radiators (Safety temperature limiter set at 100°C and maximum boiler temperature -TCMA parameter n° - set at 80°C). For connection to a underfloor water circuit, refer to «Setting for low temperature application» §1.1.1 and «Control settings»...
2.2 - Installation notice ➠ Disconnector NF ➠ Safety relief drain Depending on local existing regulation a disconnector Connections and pipes must be made of corrosion might be needed to prevent the heating water flowing resistant materials. back into the domestic water circuit. In this case this disconnector will be connected to sewage.
2.4.2.5 Connection of the accessories 3 way valve Heating and sanitary water heating using a for the sanitary water circuit 1 – 2 : TA(room thermostat) or SA(room temperature sensor) 3 – 4 : optional outdoor temperature sensor 5 – 6 : sanitary water thermostat or sensor 7 –...
Page 29
2.4.2.6 Connection of the load shedding devices when any non differential circuit breaker of 3 phase connection electricity meter 36 and 48 kW possible load shedding either on D1 or on D2 (single phase – 1 way) electricity board with 500 or 300 mA protection 72 kW to 196 kW possible load shedding either on D1 or on D2 or on D3 (single phase –...
Page 31
L1 – L2 – L3 = phase AQS = 100°C overheat cut-out with manual reset N = neutral K1 to K2 = power contactor 27A F = fuse, 4 amp, 5 x 20 mm T1 and T2 = heating elements 18 kw C1 = electronic card with digital display H = clock CC : pump...
2.5 - Starting the boiler 2.5.1 - Filling the installation ➠ Fill the boiler with water. ➠ Make sure that the installation is equipped with bleeders at highest points of the installation for an efficient drainage. Top display MAKE SURE NO AIR REMAIN INSIDE Summer LED Winter LED THE BOILER BEFORE CUT-OVER...
2.5.2 - Control settings For fitter’s use only ➠ Press (0 sec) to change the value of the ➠ Press (3 sec) to enter the setting menu parameter (on bottom display) for 4 minutes : ➩Parameter # starts flashing on top display ➠...
Page 51
2.5.2.2 Adjustment to another power than the nominal power using the parameters boilers are supplied with the maximum power (36 kW, 48 kW, 72 kW, 120 kW, 196 kW) it is possible to adjust to another power by modifying the parameters factory setting of paramater nr 15 : 1.
2.5.3.1 - Floor heating 2.5.3.2 - Radiators The boiler is delivered ex-work with a 100°C safety Do not change ex-work settings with 100°C safety aquastat aquastat. Example of use : Example of use Boiler outflow requested temperature TC (°C) Boiler outflow requested temperature TC (°C) TCMA = 70°C TCMA = 50°C TCMI = 40°C...
2.5.4 - TIMER INPUT PARAMETERING • Adjusting the parameter n°23 at 01, the boiler requested temperature lows to 1/8 of its value when the timer contact is closed (terminals 20 - 21) • Adjusting the parameter n°23 at 02, the boiler requested temperature lows to 1/4 of its value when the timer input contact is closed (terminals 20-21) •...
2.5.5 - TEMPERATURES DISPLAY 2.5.6 - DISPLAY AND ADJUSTMENT STATUS OF CONNECTED OF AMBIENCE REQUESTED THERMOSTATS OR TEMPERATURE WITH AQUASTATS AMBIENCE SENSOR During standard operating the boiler’s temperature is displayed on top. Adjustments below are only possible if parameter # is set Below displays are only possible if parameters # •...
2.6 - Maintenance and Troubleshooting 2.6.1 - Meters display The control is equipped with 6 meters to count heating cycles (the unit is 100 cycles). Time to Parameter on top Value down Requested value Press button(s) Signification push of the display the display Access to meters 3 sec.
2.6.2 - Maintenance We recommend to have the boiler checked once a year by a qualified technician. ➠ The water pressure inside the heating circuit will be checked on a regular basis (The water pressure displayed on bottom display will never reach a value below zero when cold). ➠...
Troubleshooting Trouble Reason ➠ Slightly unscrew the pump without leakage ➠ Screw back according to folowing instructions : Partly screw to opposite screws with a 3Nm torque. Partly screw the other two opposite screws with a 3 Nm torque. The pump is to The pump is noisy strongly tight Fully screw the first two screws with a 5Nm...
2.6.5 - Temperature sensors 2.6.5.1 - Boiler sensor (SC) and 2.6.5.2 - Outside temperature DHW sensor (SECS) sensor (SExt) Ohmic values (10kΩ at 25°C) Temp.°C R Ohms Temp.°C R Ohms Temp. Résistance Element Temp. R Ohms 412135 7686 Ω Ω °C °C 383178...