Page 1
Installation and Maintenance Manual IM 1267-7 Group: Applied Terminal Systems Part Number: IM1267-7 Date: February 2023 PreciseLine® Air Handler Sizes 006 through 100...
Introduction Introduction Smoke Control and Management Systems Hazardous Information Messages WARNING CAUTION Improper smoke or fume air handling can result in severe personal injury or death. Caution indicates a potentially hazardous situations, which can result in minor injury or equipment damage if not avoided. A registered professional engineer must design and approve the air conditioner and air handler application to make sure smoke and fume WARNING...
Installation Installation Figure 2: Vertical Size 40 Unit - Disassembling Optional Mixing Box and Discharge Plenum Example Optional Mixing Box and Discharge Plenum Removal All PreciseLine mixing boxes ship attached, and horizontal units ship with pre-attached discharge plenums. However, the discharge plenum and/or mixing box may be removed if necessary to navigate constricted passageways.
Installation Service Clearances Figure 4: Size 100 Unit - Disassembling Optional Mixing Leave adequate space around the unit for piping, coils, and drains. Always have access to at least one side of the unit for regular service and maintenance. Refer to images on the following pages for servicing space requirements.
Page 7
Installation Figure 5: Clearance and Access Requirements for Horizontal Units (Sizes 006-050) Depth of Unit Width of Coil Section Cabinet Sizes: 030, 040, and 050 Filter Depth Filter Length Table 1: Bottom Filter Access Clearance 30L × 15W × 30L × 20W × 30L ×...
Page 8
Installation Figure 6: Clearance and Access Requirements for Vertical Units NOTE: AVD units require field-cut holes on the sides or back, depending on piping orientation. These holes should either be drilled prior to unit installation, or a clearance of 24" should be left on the side requiring field work.
Page 9
Installation Figure 7: Clearance for Filter Access from Top - Unit Size 030-050 Figure 8: Clearance and Access Requirements for Unit Sizes 060-100 www.DaikinApplied.com IM 1267-7 • PRECISELINE AIR HANDLER...
Installation Rigging (Unit Sizes 006-050) Rigging (Unit Sizes 060-100) Rig units using straps or a sling with a loop and buckle. Fasten WARNING strapping loop around the mounting brackets on the unit main A licensed and/or professional rigger is responsible for developing a safe lift section (Figure 9 &...
Installation Using a Forklift Hanging Unit from Ceiling (Horizontal Units) When using a forklift to transport units, make sure that forklift tongs enter from the ends of the pallet, not the sides. In cases WARNING where one end is heavier, enter the pallet from the heavier side (e.g.
Installation Positioning the Unit Before hanging, the unit should be rigged and completely assembled. The PreciseLine air handler main section should be positioned on the pallet to permit access to mounting holes in the structural cross bracing under the unit. The entire unit is then lifted on the pallet and secured with minimum 1/2"...
Installation Vibration Isolation (Accessory) Spring Mount—Sizes 030, 040, 050 Factory ordered spring isolators are recommended for Figure 13: Ceiling Hung with Rubber Isolators - Unit Sizes horizontal units, sizes 030, 040 and 050. The isolators should 006-050 (Sizes 006-020 shown). all be at the same height opening.
Installation Unit Leveling Figure 18: Mounting Rail Holes for Size 040 Units Install the unit on a flat and level surface (or verify that unit is level when hanging from the ceiling). Where the surface irregularities allow the equipment to distort, shim the appropriate base rails to straighten the unit.
Page 15
Installation Panels and Doors Baserail holes for unit sizes 060-100 are 0.5" in diameter. PreciseLine air handlers have hinged access doors or screw- Table 2: Baserail Hole Widths on panels that can be easily removed and handled. To gain Dimension Sizes 060-080 Size 100 access through a side panel, remove the fasteners along the...
Page 16
Installation Figure 24: Door Access Types (Sizes 060-100) Figure 27: Bottom Filter Access (Sizes 030-050 Horizontal) Figure 25: Side Filter Access (Sizes 030-050 Horizontal) Figure 28: Mixing Box Filter Access Door (Sizes 030-050 Vertical) Figure 26: Top Filter Access (Sizes 030-050 Horizontal) IM 1267-7 •...
Page 17
Installation Figure 29: Accessing Internal Filter (Sizes 006-020 Vertical) Figure 31: 2-Fan Fillter Top Removal (Sizes 006-020 Vertical) Figure 32: Filter Side Access (Sizes 060-100) Figure 30: Filter Side Access (Sizes 030-050 Vertical) www.DaikinApplied.com IM 1267-7 • PRECISELINE AIR HANDLER...
Installation Piping and Coils Horizontal Hydronic Coils with No Valve Package Follow applicable piping design, sizing, and installation information presented in ASHRAE Handbooks in the design Hydronic coil guidelines for units selected with the "No Valve and installation of piping. Observe all local codes and industry Package - Threaded Connections"...
Page 19
Installation Figure 35: Size 006 - 020 Hydronic Coil Drill Areas – Top Figure 37: AVD Hydronic Coils and Right Side All AVD Units (vertical units Size 06-20) have coil connections located in the unit. The connections are FPT as default, and M-SWT if selected.
Page 20
Installation Drain Pan Piping Direct Expansion (DX) Coils The drain pan requires a field-drilled hole made on the sides or Direct expansion coil connection guidelines are listed below. back, in-between the drain pan and bottom panel of the unit. 1. On unit sizes 006 - 020 the coil distributor and suction The drain pan connection is in the front-right corner, and must connections are inside the cabinet on the right-hand side be piped to the field-drilled hole.
Page 21
Installation Installation Figure 40: Horizontal Units Sizes 006 - 020 DX Coil Drill Figure 42: Horizontal Units Size 030 - 050 – DX Only and Area DX with Preheat Drill Area Table 6: Horizontal Units Sizes 006-020 DX Coil Drill Area Dimensions Unit Size 7.13...
Page 22
Installation Figure 44: Vertical Units Sizes 030-050 DX Coil Drill Area Table 9: Horizontal Drill Area Locations – DX with Reheat Single Circuit DX Primary with 1 Row Hydronic Reheat Unit Size 27.13 6.61 30.14 7.65 30.14 6.62 Interlaced DX Primary with 1 Row Hydronic Reheat 27.13 7.35 30.14...
Installation Condensate Drain Pan Traps Figure 46: Basic 2-Way Valve Package The condensate drain stub for sizes 006-050 is 0.75 OD. The condensate drain stub for sizes 060-100 is 0.138 OD. Drain lines and traps should run full size from the drain pan stub.
Page 24
Manual Circuit Setter: Pressure-compensated, manual flow control. Union: For easy removal of piping from coil. NOTE: Daikin Applied 3-way valves are equipped with a fixed balance orifice in the bypass line, eliminating the need for a separate balancing valve IM 1267-7 • PRECISELINE AIR HANDLER...
2 to 10 VDC / 4 to 20 mA Control 2 to 10 VDC / 4 to 20 mA Control Control Valve Parts Lists Table 11: ON/OFF Control Valve Part List Daikin P/N Valve Type Size Control Type Control Voltage...
Page 26
Installation Table 12: Modulating Control Valve Part List Daikin P/N Valve Type Size Control Type Control Voltage Spring Return Normal State Vendor PN (Belimo) 263940901 2 Way 0.50 FPT Modulating 0-10VDC B207B+TR24-SR DKN 263940902 2 Way 0.50 FPT 0.46 Modulating...
Installation Electric Heat The factory installed electric heat section (if equipped) consists of an open coil heater rack mounted to the unit's primary coil in the preheat position for horizontal units or reheat postion for vertical units. Electric heat is designed to operate only when the supply fan is running, heating the air as it passes through the heating elements.
Page 31
Installation Minimum Allowable Air Volume For Units With Electric Heat Table 17: Horizontal Minimum Allowable Air Volume With Electric Heat (unit sizes 006-020) Unit Size Air Volume - CFM 0.41 1000 1000 1000 1000 0.82 1000 1000 1000 1000 1.64 1000 1000 1000...
Page 32
Installation Table 18: Horizontal Minimum Allowable Air Volume With Electric Heat (unit sizes 030-100) Forward-Curved Fan Units Plenum Fan Units Air Volume - CFM Air Volume - CFM 7.36 1500 2000 2500 1800 2400 3000 1500 2000 2500 1800 2400 3000 1500 2000...
Page 33
Installation Table 19: Vertical Minimum Allowable Air Volume With Electric Heat Unit Size Air Volume - CFM 0.82 1.64 1000 2.45 3.27 1000 1000 4.91 6.54 1000 1000 8.18 1000 1000 1000 1000 19.2 1100 Forward-Curved Fan Units Plenum Fan Units Air Volume - CFM Air Volume - CFM 1500...
Page 34
Installation Table 20: Horizontal Electric Heat kW Options by Unit Size Unit Size Voltage Horizontal kW 120/60/1 208/60/1 230/60/1 277/60/1 460/60/1 120/60/1 208/60/1 230/60/1 10.0 277/60/1 10.0 460/60/1 10.0 120/60/1 208/60/1 230/60/1 10.0 277/60/1 10.0 460/60/1 10.0 120/60/1 208/60/1 230/60/1 10.0 277/60/1 10.0...
Page 35
Installation Table 21: Vertical Electric Heat kW Options by Unit Size Unit Size Voltage Vertical kW 120/60/1 208/60/1 230/60/1 277/60/1 460/60/1 120/60/1 208/60/1 230/60/1 10.0 277/60/1 10.0 460/60/1 10.0 120/60/1 208/60/1 230/60/1 10.0 277/60/1 10.0 460/60/1 10.0 120/60/1 208/60/1 230/60/1 10.0 277/60/1 10.0...
Installation Field Power Wiring NOTE: All field wiring penetrations, for both power and controls wiring, must only be made at the factory DANGER designated locations on the top, side, or bottom panels. These locations are identified on the panels Improper ground may result in severe injury or death. with a 3/16"...
Page 38
Installation Table 24: Figure 57 Letter Dimensions Top or Left-Hand Right-Hand Unit Bottom Left-Hand Right-Hand Sizes Unit Sizes Entry 18.97 008, 010, 012, 17.51 1.92 17.51 1.92 Bottom 18.74 3.45 18.35 3.45 016, 018, 020 21.74 2.31 21.73 1.93 Figure 58: Horizontal Cabinet Sizes 030-050 Field Cut Bottom 21.03 3.44...
Page 39
Installation Figure 61: Vertical Cabinet Sizes 030-050 Field Cut Figure 63: Horizontal Cabinet Sizes 060 - 100 Field Cut Electrical Service Entry Pilot Hole Location Electrical Service Entry Pilot Hole Location (Electric Heat Section) Electric Heat Control 1. Electric heat control can be factory configured for either on-off or analog control.
Installation Field Control Wiring NOTE: Design may call for lower than a 10VDC max signal. 4. Unit sizes 030 – 050 are provided with a factory installed DANGER VFD programmed for analog motor speed control. LOCKOUT/TAGOUT all power sources prior to wiring or servicing the unit. A 0-10VDC signal applied to terminal FAN 0-10V on Electrical shock hazard that may cause severe injury or death.
Page 41
Installation Table 26: Potential Field Connections and Locations PreciseLine units operate with 115V and 24V control circuit (Sizes 060-100) power. All field control wiring connections are made at the class II terminal blocks TB2, TB4, and TB12 which is located in the Label Description Signal...
Installation Accessories and Sensors Integrated Thermostat Mounting considerations: • The device is suitable for semi-flush mounting with a recessed conduit box. • The unit should not be mounted in recesses, shelving, behind curtains or doors or above or near direct heat sources. •...
Page 43
Tests show that fluctuating and inaccurate signal levels are possible when AC power wiring is present in the same conduit as the signal lines. If you are experiencing any of these difficulties, please contact your Daikin Applied representative. www.DaikinApplied.com IM 1267-7 • PRECISELINE AIR HANDLER...
Page 44
Green to GND Terminal • Run 3-conductor wire from the sensor location to the unit. Daikin Applied recommends using shielded 22AWG for all connections. Larger gauge wire may be required for runs of greater than 250’. • Mount sensor on the supply duct near the location •...
Page 45
Tests show that fluctuating and inaccurate signal levels are possible when AC power wiring is present in the same conduit as the signal lines. If you are experiencing any of these difficulties, please contact your Daikin Applied representative. Entering/Leaving Water and Space •...
Page 46
Installation Air Flow Switch Figure 76: Sensor Mounting Location Installation • Two field provided duct pressure taps will be required to install this sensor. Locate one tap in the ductwork upstream of the fan and the second downstream of the fan.
Page 47
2. Differentiate between the duct pressure (HI) and reference pressure (LO) taps by using different color tubing or by tagging the tubes. Daikin Applied recommends 3/16ʺ I.D. plastic tubing. 3. Locate the duct pressure (HI) tap near the end of a long...
Page 48
Installation Discharge Air Temperature Sensor MicroTech® 4 Lite Portable Interface The discharge air temperature sensor should be installed WARNING in the supply air duct, downstream of the PreciseLine unit. Electric shock hazard. Can cause death, personal injury, Locate the sensor at a location that approximates the average or equipment damage.
Page 49
Installation Figure 84: Connection Port (Size 030 Shown) specific unit configuration are displayed. Figure 85: Portable Interface Main Features Keypad/Display Functions The keypad/display Information is organized into five main Using the Portable Interface menus or menus groups; Alarm Lists Menu, System Summary Menu, Standard Menus, Extended Menus and Advance Hardware Features Menus.
Page 50
Turning the wheel clockwise Figure 87: Password Main Page while the editable field is highlighted causes the value to be Daikin AHU increased. Turning the wheel counter-clockwise while the editable field is highlighted causes the value to be decreased.
MicroTech 4 Lite Unit Operation MicroTech 4 Lite Unit Compressor Operation Operation Single Compressor In this configuration a single output is used for compressor Preparing Unit for Operation control. When mechanical cooling is required, it will be energized. When mechanical cooling is no longer required, it Power-up will be de-energized.
Page 52
MicroTech 4 Lite Unit Operation Minimum Compressor On/Off Time Dehumidification Termination When a compressor is turned off, it must remain off for the Dehumidification is terminated if the selected variable, Relative duration of the Compressor Minimum Off Time. When a Humidity or Dew Point, drops below the appropriate humidity compressor is turned on, it must remain on for the duration setpoint by more than half its dead band plus the appropriate...
Page 53
MicroTech 4 Lite Unit Operation Servicing High Voltage Control Panel Initial Manual Mode Start-Up Components Initial Start-up should be performed in manual control mode before proceeding to the cooling/heating start up. DANGER Power Up LOCKOUT/TAGOUT all power sources prior to servicing the unit. Hazardous voltage may cause serious injury, death, and property damage.
Page 54
MicroTech 4 Lite Unit Operation Cooling/Heating Start up Alternativly individual outputs can be commanded on using the Output Override functionality. See the MicroTech 4 Lite NOTICE Operations Manual for more information. Operational Override using the Manual Ctrl Type commands should only be Setup for Normal Operation used by trained service technicians as several timing functions are reduced to speed system check out.
Page 55
Maintaining Control Parameter Records Daikin Applied recommends that the MicroTech 4 Lite controller’s setpoints and parameters be recorded and saved for future reference. If the Microprocessor Control Board requires replacement, this record facilitates entering the unit’s...
Example Wiring Diagrams Example Wiring Diagrams NOTE: Wiring diagrams are typical, always defer to the wiring diagram provided with the unit. 3 Phase Power, SCR Electric Heat, No Valve, Modulating Damper, VFD Fan Hot Wire Colors 480V = BLK/RED 575 = BLK MMP/Fuse 575V = Fuse 208/240/480V = MMP...
Page 57
Example Wiring Diagrams NOTE: Wiring diagrams are typical, always defer to the wiring diagram provided with the unit. 1 Phase Power, SCR Electric Heat, Modulating Valve, Modulating Damper, Modulating Fan Legend: (Devices may or may not be on unit) Mixing Box Damper Actuator Condensate Overflow Switch/Sensor Discharge Air Temperature Sensor Disconnect Switch...
Page 58
Example Wiring Diagrams NOTE: Wiring diagrams are typical, always defer to the wiring diagram provided with the unit. 1 Phase Power, On-Off Electric Heat, On-Off Valve, On-Off Damper, 3-Speed Fan Hot Wire Colors 115 = WHT 208 = RED 240 = ORG 277 = BRN Legend: (Devices may or may not be on unit) Mixing Box Damper Actuator...
Page 59
Example Wiring Diagrams NOTE: Wiring diagrams are typical, always defer to the wiring diagram provided with the unit 3-Phase Power, Welded Aluminum Airfoil Plenum Fan, On-Off Electric Heat, On/Off Damper, Fused www.DaikinApplied.com IM 1267-7 • PRECISELINE AIR HANDLER...
Page 60
Example Wiring Diagrams NOTE: Wiring diagrams are typical, always defer to the wiring diagram provided with the unit MicroTech 4 Lite Controller for Sizes 006-050 IM 1267-7 • PRECISELINE AIR HANDLER www.DaikinApplied.com...
Page 61
Example Wiring Diagrams NOTE: Wiring diagrams are typical, always defer to the wiring diagram provided with the unit MicroTech 4 Lite Controller for Sizes 060-100 www.DaikinApplied.com IM 1267-7 • PRECISELINE AIR HANDLER...
Page 62
Example Wiring Diagrams NOTE: Wiring diagrams are typical, always defer to the wiring diagram provided with the unit MicroTech 4 Lite Controller for Sizes 060-100 IM 1267-7 • PRECISELINE AIR HANDLER www.DaikinApplied.com...
Physical Data Table 32: Horizontal Fan and Motor Data (Plenum Supply Fans) Plenum Fan Data Unit Size Fan Quantity Fan Type Plenum Fan Plenum Fan Plenum Fan Fan Size 355 mm 355 mm 355 mm Maximum RPM 3300 3300 3300 EC Motors Poly Phase EC Motors...
Physical Data Vertical Filter Data Table 36: Filter Data for Main Unit and Optional Mixing Box Main Unit Filters External Unit Size Quantity Height Width Nom. Face Velocity (FPM) Internal Filter Rack Quantity Height Width (Optional) Mixing Box Filters Quantity Height Width Table 37: Filter Pressure Drop...
Page 68
Physical Data Table 40: Hydronic Coil Size and Type with No Piping Option Unit Size Connection Type M-SWT (OD) 2-Row Cooling 0.625 0.625 0.625 0.875 0.875 4-Row Cooling 0.625 0.625 0.875 0.875 1.125 6-Row Cooling 0.625 0.875 0.875 1.125 1.125 8-Row Cooling ─...
Page 69
Physical Data Table 45: DX Coil Size and Type (Horizontal and Vertical) Circuits Connection Size (M-SWT (OD)) Unit Size Rows Number Type Distributor Suction Normal 0.500 0.750 Normal 0.500 0.750 Normal 0.500 0.875 Normal 0.500 0.875 Normal 0.500 1.125 Normal 0.625 1.125 Normal...
Physical Data Thermal Expansion Valve (TEV) Optional Mixing Box Damper or Discharge Plenum Loss For each unit size there are two TEV options available (Table 46). TEV Option 1 is optimized for the standard For reference, losses are similar to those used in custom entering air and suction temperatures while option 2 is openings, however, their coefficients are multipliers of velocity pressure based on opening size.
Dimensional Data Dimensional Data Size 006-050 Horizontal Unit Dimensions Figure 89: Left-Hand, Single and Dual Fan (Sizes 006-020)) Cabinet Width Cabinet Width AIR FLOW AIR FLOW Cabinet Cabinet Length Length Cabinet Sizes: Cabinet Sizes: 006, 008, 010, 012 016, 018, and 020 Top View Top View .563 Mntg Holes (4)
Page 77
Dimensional Data Figure 90: Left-Hand, Single Fan (Sizes 030-050) Cabinet Width AIR FLOW Notes: 1. Refer to submittal drawings in Daikin Applied SelectTools Cabinet for piping connection dimensions. Length 2. Left hand unit shown, right hand unit values same as left but opposite.
Page 78
Dimensional Data Table 50: Hydronic Unit Dimensions - Dimension Letter Reference for Figure 90 on page 77 8-Row 2-Row Cooling / Primary 4-Row Cooling / Primary 6-Row Cooling / Primary Cooling / Primary Preheat Reheat Preheat Reheat Preheat Reheat Unit Size Dimension 1-Row 2-Row 1-Row 2-Row 1-Row 2-Row 1-Row 2-Row...
Page 79
Dimensional Data Table 52: DX Unit Dimensions - Dimension Letter Reference for Figure 90 on page 77 Single Circuit DX Interlaced DX Preheat Reheat Preheat Reheat Unit Size Dimension 1-Row 2-Row 1-Row 2-Row 1-Row 2-Row 1-Row 2-Row 25.69 25.69 25.61 23.95 23.88 24.38...
Page 80
Dimensional Data Figure 91: Horizontal Mixing Box – Top and End Damper, Left Hand Sizes 006–020 and Right Hand Sizes 030–050 – Side Filter Access TOP VIEW K (Filter Access Door) AIR FLOW .563 (2) 1.00 Cabinet Width 30.00 Damper Actuator 1.00 Cabinet Height...
Page 81
Dimensional Data Figure 92: Horizontal Mixing Box – Bottom and End Damper, Left Hand Sizes 006–020 and Right Hand Sizes 030–050 – Side Filter Access Cabinet Length 1.00 Cabinet Height 1.00 Base 2.00 SIDE VIEW Cabinet Width NOTE: Dimensions for right hand cabinets sizes 006–020 and cabinets sizes 030–-50 with side access filters are similar but opposite.
Page 82
Dimensional Data Figure 93: Horizontal Mixing Box Dimensions – Left Hand Sizes 006–020 and Right Hand Sizes 030–050 – Bottom Filter Access AIR FLOW .563 (2) Cabinet Width Cabinet Length Actuator Access Panel 1.00 Cabinet Height 2.00 Filter Access Door 1.00 Distance Required For Filter Access...
Page 83
Dimensional Data Figure 94: Horizontal Discharge Plenum (Sizes 006-050) AIR FLOW Notes: 1. Discharge opening is offered on any one particular side, but is shown here on all available surfaces for Optional Top dimensioning purposes only. Discharge Opening 2. A discharge plenum is also available without discharge openings.
Dimensional Data Size 006-050 Vertical Unit Dimensions Figure 95: Left-Hand, Single and Dual Fan (Sizes 006-020) Disconnect Switch Disconnect Switch Top View – 1-Fan Top View – 2-Fan A (Max. Length) B (Max. Width) Field piping access pilot holes (both sides) See manual for field hole diameter and Field piping access...
Page 85
Dimensional Data Figure 96: Vertical Unit Dimensions (Sizes 030-050) 2.00 Top View B (Max Width) 1.00 A (Max Length) Cabinet Width Cabinet Length 2.00 Disconnect Switch T- Dia. Optional (2) 12.00 Field Duct Flange is Shipped Flat Field Access Cabinet Area 1.50 S- Dia.
Page 86
Dimensional Data Table 59: General Vertical Unit Dimensions for Figure 96 on page 85 Units with Forward-Curved Fans DCold Water SIZE 30 35.36 49.5 61.5 42.5 5.54 30.49 12.3 15.32 5.29 13.66 24.5 SIZE 40 35.36 53.5 65.5 46.5 34.49 15.09 17.82 5.25...
Page 89
Dimensional Data Figure 97: Vertical Mixing Box - Top and End Damper. Sizes 030-050 - Side Filter Access. Table 63: Mixing Box Dimension Letter Reference Vertical Mixing Box SIZE 30 42.5 26.31 2.87 38.27 9.82 18.37 34.5 36.76 70.12 18.37 14.19 SIZE 40 46.5...
Page 90
Dimensional Data Figure 98: Vertical Discharge Plenum (Sizes 030-050) Top View – Discharge Plenum (Main cabinet removed for clarity) Field Duct Flange Cabinet Length Cabinet Width 1.00 Discharge Plenum Cabinet shown for reference. Use for both AVD and Vertical cabinets Front View Side View Table 64: Discharge Plenum Dimension Letter Reference...
Startup Checks Startup Checks Before Starting the Unit □ Make sure that fan electrical power source is disconnected When performing startup and service, always take thorough and locked in the OFF position before entering fan section. safety precautions. Start-up functions must be performed by trained, experienced personnel.
Maintenance Maintenance Figure 111: Slide Coil Out 1. For maximum performance, the coil must be clean. Check once a year under normal operating conditions and brush or vacuum clean if necessary. Use a chemical coil cleaner on multiple row coils. Read and follow the chemical cleaner instructions since some cleaners may contain harsh chemicals.
Page 107
Maintenance Hydronic Coil Removal - Vertical Unit 3. Remove 2 screws holding coil. Sizes 006 - 020 1. Remove screws on the inside right (3) and inside left (3), holding external filter frame. 4. Slide out coil assembly. 1. Remove screws holding internal filter brackets and bottom panel assembly.
Page 108
Maintenance Hydronic Coil Removal - Horizontal Unit 6. Remove screws along back of coil at bottom and top holding coil. Sizes 030 - 050 1. Remove coil section panels. Figure 113: Remove Panel Screws and Panels 7. Remove coil support top. 2.
Page 109
Maintenance Figure 115: Remove Screws Holding Coil Sections 2. Remove screws and remove bottom access panel. Together and Connectors On Each End 3. Remove screws and remove coils stop plate. 8. For units with the electric heat option, the electric heat rack is attached to the cooling coil in the preheat position.
Page 110
Maintenance Hydronic Coil Removal: Sizes 060 - 100 5. Slowly pull out the 1st position coil assembly using caution to not damage cap tubes. (Primary Coil and Optional Secondary Coil Shown) 1. Remove screws securing the access panel to the cabinet, then remove the access panel.
Page 111
Maintenance 3. Pull to slide the entire coil assembly out of the cabinet. If using support straps/hooks, pull the coil assembly out partially and secure the supports to any of the available lift holes. DANGER COIL ASSEMBLY IS HEAVY! Failure to use the proper lifting equipment to support the weight of the assembly can cause property damage, personal injury or death.
Maintenance Fan Motor Removal Figure 117: Slide Out The Blower Assembly Horizontal Units Size 006-020 1. Unplug the wires going from the control box to motor. 2. Remove the top and bottom screws on the downstream side of the control box and loosen the top and bottom screws on the upstream side.
Page 113
Maintenance Figure 119: Loosen The Motor Shaft Set Screw Figure 121: Remove VFD Mounting Bracket 4. Remove the five screws holding the fan sled to the cabinet bottom panel; two screws on the access panel Figure 120: Loosen Belly Band Bolt And Remove From side and three on the upstream side of the sled.
Page 114
Maintenance Horizontal Unit Sizes 030 - 050 Figure 123: Fan Shaft Set Screw Locations (Welded Aluminum Airfoil Plenum Fans) 1. Turn the switch disconnect handle to the off position. 7. Remove the four motor mounting bolts using a wrench to NOTE: Single fan model shown.
Page 115
Maintenance 4. SIZE 030 ONLY: detach wires connecting the circuit 7. Remove the fan sled assembly from the cabinet and breaker to the terminal block. lower onto a flat surface. 5. Remove the screws holding the fan sled assembly in 8.
Page 116
Maintenance Vertical Unit Sizes 006 - 020 4. Loosen set screw holding fan to fan shaft. (DWDI Forward-Curved Fans) 1. Remove 2 screws. 5. Remove motor and mounting assembly. 2. Slide out fan and motor assembly. 3. Remove motor mount leg bolts. 6.
Page 117
Maintenance Vertical Unit Sizes 030 - 050 4. Slide out motor and fan assembly sled. (DWDI Forward-Curved Fans) 1. Remove 4 screws holding VFD controller. 5. Loosen fan wheel set screws (2) on either side of the fan wheel central plate. 2.
Page 118
Maintenance 7. Slide out motor from fan housing. 3. Detach the low-voltage and power wires from the motor by releasing the plastic connectors. NOTE: Remember the motor orientation when installing a new fan. Matching the motor orientation will ensure wires can reach the connectors of the new motor. 4.
Page 119
Maintenance Horizontal Unit Sizes 060 - 100 4. If equipped, remove the sound baffle from each fan by unscrewing the mounting screws. (Welded Aluminum Airfoil Plenum Fans) 1. Open the cabinet access door by turning the quarter-turn latches. 5. Secure supports to the metal bar frame. DANGER NOTE: Dual fan model shown.
Maintenance Warranty Consult your local Daikin Applied representative for warranty details. To find your local Daikin Applied representative, go to www.DaikinApplied.com. Warranty Return Material Procedure Defective material may not be returned without permission of authorized factory service personnel of Daikin Applied in Minneapolis, Minnesota, (763) 553-5330.
Page 122
Now that you have made an investment in modern, efficient Daikin branded equipment, its care should be a high priority. For training information on all Daikin branded HVAC products, please visit us at www. DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.
Need help?
Do you have a question about the PreciseLine Series and is the answer not in the manual?
Questions and answers