ActronAir ADVANCE CRV140S Troubleshooting Manual page 23

Split ducted unit r-410a/r-32
Hide thumbs Also See for ADVANCE CRV140S:
Table of Contents

Advertisement

Troubleshooting Guide
Fault Code
E18 Suction Temp.
The reading of the suction temperature sensor
Sensor Error
(Sst) is not within the specified sensor range.
(Open/short
circuit)
E22 Ambient
The reading of the ambient temperature sensor
Temp. Sensor
is not within the specified sensor range.
Error (Open/
short circuit)
E26 VSD Supply
The drive has encountered an over current
Over Current
event and has stopped operation.
E27 VSD Supply
The drive has encountered an over voltage
Over Voltage
event.
E28 VSD
The drive has encountered an over temperature
Temperature
condition and has stopped operation.
High
E29 VSD Low
The drive has encountered an under-voltage
Supply Voltage
event.
E30 VSD Trip Lock Certain faults have a trip limit
E41 VSD DC Link
The drive has encountered an DC bus voltage
Voltage Low
low.
Description
Troubleshooting Guide - Advance Split Ducted Unit
Doc. 9590-2015-03 Ver. 3 221111
Advance Split Ducted Unit
Possible Causes
Suction temperature sensor
is open or short circuit.
Faulty sensor.
Ambient temperature sensor
is open or short circuit.
Faulty sensor.
An over current can be
triggered by low voltage.
Check if the compressor is
operating within specified
pressure limits.
Faulty drive.
Measure the input voltage
to the drive. It should not be
more than 575VAC.
Check if the compressor is
operating within specified
pressure limits.
Verify proper airflow over
the heat-sink of the drive.
Check if the compressor is
operating within specified
pressure limits.
Check the mounting screws
on the drive, If the problem,
still persists replace the
drive.
Measure the input voltage to
the drive. It should not drop
below 295VAC.
Check if the compressor is
operating within specified
pressure limits.
VCD Drive trips lock because
of multi errors. Refer to
Ourdoor Board history to
diagnose more for related
error code
Check the AC power supply.
Check if the compressor is
operating within specified
pressure limits.
Remedies
Replace suction temperature
sensor.
Check the sensor resistance.
Replace ambient
temperature sensor.
Check the sensor resistance.
Rectify low voltage power
supply.
Find the root cause for not
operating the compressor in
the specified limits.
Replace drive if the problem
still persists.
Input voltage should be
rated value range.
Find the root cause for not
operating the compressor in
the specified limits.
Remove any obstructions.
Find the root cause for not
operating the compressor in
the specified limits.
Make sure they are tight.
Input voltage should be
rated value range.
Find the root cause for not
operating the compressor in
the specified limits.
Reset the power supply
Make correct supply
voltage.
Find the root cause for not
operating the compressor in
the specified limits or restart
the drive again.
23