NDM2 series of moulded case circuit breakers(Hereinafter referred to as the MCCBs), which is one of the self-developed new generation MCCB of Nader. According to the level of the rated ultimate short-c ircuit breaking capacity, the breaker can be classified into four types: Type C (Basic type), Type L (Stand ard type), Type M (Less high breaking type) and Type H (High breaking type).
Page 5
文件编号:NDT2920016 文件版本:4 M:较高分断型 type M:Less high breaking type H:高分断型 type C: High breaking type 无代号:手柄直接操作 no code represents direct handle operation 操作方式 P:电动操作 P: represents motor operation Operation mode Z:转动手柄 Z: represents rotary handle operation 极数 2、3、4 Pole number 0:无脱扣器 0: represents frame only without trip unit 脱扣器代号...
文件编号:NDT2920016 文件版本:4 表 6/ table 6 接线端子/安装螺钉拧紧扭力矩 Torsion value for wiring terminal 序号 壳架等级额定电流(A) 螺纹直径(mm) 扭力矩(N.m) Frame size rated current Thread diameter Torsion value 5. 接线方式/ Wiring Method 连接导线采用的截面积和相适应的额定电流见表 7 Table 7 of sectional area and applicable rated current adopted in wiring 额定电流(A) Rated 12.5...
文件编号:NDT2920016 文件版本:4 6. 产品外形及安装尺寸/ Shape dimension & Dimension 本产品可板前接线,也可板后接线,具体见图 1、图 2 This product can also be front plate connector, wiring on back of the board, specific see Figure 1, figure 图 1 板前接线/ Fig 1 Front connection NDM2-63-800 NDM2X-125 图 2 板后接线/ Fig 2 Rear connection NDM2-63~250 NDM2-400~800 地址:上海市浦东新区申江南路...
Page 14
文件编号:NDT2920016 文件版本:4 续表 8/ Table 8(continued) 注:未注公差尺寸的极限偏差按 GB/T 1804-c。 Note: The limit deviation not indicated with the tolerance dimensions is as per GB/T 1804-c. 地址:上海市浦东新区申江南路 2000 号 邮编:201315 电话:(021)68586699 传真:(021)23025796 第 14 页 共 24 页...
Page 15
文件编号:NDT2920016 文件版本:4 6.1 安装在金属小柜中的绝缘距离(单位:mm),如下图: 6.1 Insulation distance mounted in the metal cabinet (unit: mm), as shown below: A(进线端到柜面) 安装距离 A (inlet wire end to the cabinet Mounting distance B(侧面到柜面距 face) C(出线端到柜面距离) 离) C (outlet wire end to 带端子罩 B (distance from 不带端子罩...
Page 16
文件编号:NDT2920016 文件版本:4 6.3 断路器叠装之间最小距离 6.3 Minimum center distance between stacked circuit breakers H(断路器上下距离) H (distance of circuit breaker from bottom) 带端子罩 不带端子罩 With a terminal cover Without a terminal cover NDM2-63 NDM2(X)- 125 NDM2-250 NDM2-400 NDM2-630 NDM2-800 注:1、电缆绝缘联接 2、联接且无绝缘 3、产品通电前检查端子罩或相间隔板装配到位。 Note: 1.
文件编号:NDT2920016 文件版本:4 7. 安装方式/ Mounting Method 7.1 绝缘测试 本断路器出厂前已按标准规定绝缘测试。安装前如进行复测,必须按如下步骤: ① 用 500VDC 兆欧表 ② 在断路器处于断开状态,对进出连接板 1-2、3-4、5-6 之间,和 1、3、5 连接板与外壳之间(外壳 用金属箔覆盖)分别进行。 ③ 对接至主电路的欠电压脱扣器,在进线与断路器外壳间。 ④ 绝缘电阻不小于 20MΩ。 7.2 安装 请安装在金属阻燃物上,断路器可垂直安装,也可以水平安装。 7..1 Insulation test Insulation test has been already carried out on the breaker according to standard before leaving factory.
文件编号:NDT2920016 文件版本:4 8. 附件说明书/ Accessory 8.1 欠压脱扣器 断路器带有欠压脱扣器时,应使欠电脱扣器先通电,断路器才允许合闸. 根据外挂欠电压模块上的接线端子编号接入电源(直流电源不必区分正负极) 当电源电压下降到欠压脱扣器额定工作电压的 35%~70% 范围内时,欠压脱扣器能可靠的分断断路器;当电源电压 低于欠压脱扣器额定工作电压的 35%时,欠压脱扣器能防 止断路器闭合;当电源电压高于欠压脱扣器额定工作电压 欠压脱扣器接线图 的 85%时,欠压脱扣器能保证断路器可靠闭合。 Wiring diagram of under-voltage release 8.1Undervoltage tripper When the breaker has an undervoltage tripper, the undervoltage tripper should be electrified, and then the breaker allows switch on. Power supply is accessed according to wiring connector number on the external undervoltage module (anode and cathode of DC power supply are not differentiated).
Page 19
文件编号:NDT2920016 文件版本:4 8.3 辅助触头、报警触头 8.3.1 辅助、报警触头接入相应外围控制电路 8.3 Auxiliary contact, alarm contact 8.3.1 Auxiliary and alarm contacts accessed into relative external control circuit/ 约定发热电流 Ith(A) 额定工作电流(A) 分 类 壳架电流(A) Conventional thermal Rated working current Category Frame current (A) current (A) 辅助触头 1.5A(AC400V) Auxiliary contact 0.15(DC220V)
文件编号:NDT2920016 文件版本:4 8.5 Manual operating mechanism 8.5.1 Before installation, a switch cabinet door for installing operating handle is holed in accordance with the diagram. Distance between the holed part and the hinge is greater than 200 mm. 8.5.2 The breaker with an operating mechanism fixed on cover is installed on the installation panel and slightly fixed then.
Page 21
文件编号:NDT2920016 文件版本:4 9.2 试运行 Pilot run 按 9.1 条各项全部确认无异常情况后,可以进行试运行。 (1)扳动操作手柄,投入电源。 (2)断路器主电路带电后,按紧急脱扣按钮,断路器应脱扣,操作手柄处于脱扣位置。如果试运行都能满 足,可投入运行。 Carry out pilot run after all items in rule 9.1 are assured normal. (1) Pull the operating handle and switch power supply on. (2)Press emergency release button after main circuit of the breaker is electrified. Then, the breaker should be released and the operating handle is at released position.Operation can be carried out if pilot run successes.
文件编号:NDT2920016 文件版本:4 (1) Fasten, close and break the breaker. Release the breaker by a release button when it is closed. The breaker should be fastened, closed, broken and released reliably again after the above operations are carried out for five times; (2)Remove dust on the surface and connection part of the breaker (by clean and dry cloth);...
Page 23
文件编号:NDT2920016 文件版本:4 10.3 保修期与售后服务 本产品是在完善的品质管理体系下制造的,当万一发生故障时,对保修期与售后服务特作如下说明: 保修期 在用户遵守保管和使用条件下,从本公司发货之日起,不超过 36 个月,断路器封印完好,产品如因 制造质量问题而发生损坏或不能正常使用时,本公司负责无偿修理或更换。但是,如由于下述原因引起的 故障,即使在保修期内亦作有偿修理或更换。 (1)由于使用错误、自行改装及不适当的维修等原因。 (2)超过标准规范的要求使用。 (3)购买后由于摔落及安装过程中发生损坏等原因。 (4)地震、火灾、雷击、异常电压、其他天灾及二次灾害等原因。 售后服务 (1)出现故障时,请与供货商或本公司售后服务部门联系。 (2)保修期内的修理或更换:由于本公司制造上的问题所造成的故障,作无偿修理,以至更换。 (3)超过保修期后的修理或更换:在修理后能维持功能的场合下,作有偿修理,否则可作有偿更换。 10.3 Warranty period and after-sales service This product is manufactured in a fine quality management system. In case of error, warranty period and after-sales service are explained in the followings: Warranty period The company is responsible for free maintenance or exchange within 18 months from the delivery...
文件编号:NDT2920016 文件版本:4 订货须知/ Accessory list and installation 用户务必确认对本产品技术资料已有详细了解,并应根据断路器将来使用的场合,按“订货规范”表订货。 Customer should have a knowledge of technical documents of this product and maker order by an “Ordering rule” table in accordance with the future practical use of breaker 上海良信电器股份有限公司 Shanghai Liangxin Electrical CO.,LTD. 上海市浦东新区申江南路...
Need help?
Do you have a question about the NDM2 Series and is the answer not in the manual?