Signaling

A floating signal contact and two digital outputs are available
for preventive function monitoring of the power supply.
Depending on the configuration of the power supply, either
the two digital outputs or one digital and one analog output
can be selected. The signal outputs are electrically isolated
from the input and output of the power supply.
The current device status of the power supply is signaled
using four LED status indicators. The function of each LED
status indicator is assigned to a fixed event.
In addition, the power supply can be switched off and on via
an external circuit.
The signal outputs are configured on the software side using
the QUINT POWER software or the QUINT POWER app.
Upon delivery, the power supply is pre-allocated a default
configuration for the signal outputs.
109981_en_00
14.1
Location and function of the signaling elements
Figure 32
Position of signaling elements
U
Out
56V
13
14
Rem
9
SGnd
Out 1
Out 2
8
48V
> 100% Boost
7
> 75%
> 50%
6
DC OK
Key
No. Signaling elements
1
13/14 floating switch contact (N/O contact)
2
Rem, remote input (switch power supply off and on)
3
SGnd, signal ground (reference potential for signals
Out 1, Out 2)
4
Out 1 (digital output, function depends on the signal
option set)
5
Out 2 (digital or analog output, function depends on
the signal option set)
6
LED status indicator DC OK
LED on: U
> 90% x U
Out
LED flashing: U
Out
7
LED status indicator P
>480 W)
8
LED status indicator P
>720 W)
9
LED status indicator P
put power >960 W)
QUINT4-PS/1AC/48DC/20
Signal
1
2
3
4
P
5
Out
Set
 < 90 % x U
Set
>50 % (output power
Out
>75 % (output power
Out
>100 %, boost mode (out-
Out
PHOENIX CONTACT
38/51