Step
Action
2
If the hardware catalog is not visible, select the "View > Catalog" menu command.
Open the "PROFIBUS DP > ET 200S" folder in the standard hardware catalog.
Configure all modules listed in the table "ET 200S motor starter hardware".
Adding the IM151-1 HF module:
Select the IM151-1 HF module in the ET 200S folder.
Drag & drop the module to the "DP master system".
The dialog box "Properties - PROFIBUS DP Slave" opens.
Enter the PROFIBUS address.
This is the same address as the address of the device station of the motor starter.
Double-click the module to open the "Properties - DP Slave" dialog and switch to the "Operating
Parameters" tab.
Set the DP Interrupt Mode to DPV1.
Click "OK".
The defaults are accepted.
DP slave properties
Once the other modules (Page 8) (e.g., motor starter) have been added to the station, configure them in the same
way.
Note:
Enable group diagnostics for all modules.
SIRIUS Motor Starter PCS 7 Library "V7.1+SP2"/ "V8 Migration V8.0+SP1"
Getting Started, 08/2013, A5E02897539020A/RS-AA/005
First steps for the project
2.2 Configuring the device hardware
15