CHAPTER 6: SETPOINTS

S2 System Setup

S2 SYSTEM SETUP

CURRENT SENSING

POWER SYSTEM
TRANSFORMER
WNDG 1 BREAKER
WNDG 2 BREAKER
897765A1.cdr
Current sensing
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Courtesy of NationalSwitchgear.com
Figure 11: System Setup menu
PATH:
SETPOINTS > S2 SYSTEM SETUP > CURRENT SENSING
W1 PH CT PRIMARY
Range: 1 A to 6000 A in steps of 1 A
Default: 5 A
Enter the rated phase CT primary current of the three-phase current transformers
associated with Winding 1.
S2 CURRENT SENSING
W1 PH CT PRIMARY
W1 GND CT PRIMARY
W2 PH CT PRIMARY
W2 GND CT PRIMARY
S2 POWER SYSTEM
NOMINAL FREQUENCY
SYSTEM ROTATION
S2 TRANSFORMER
XFMR RATED LOAD
XFMR TYPE
PHASE COMPENSATION
W1 NOM VOLTAGE
W1 GROUNDING
W2 NOM VOLTAGE
W2 GROUNDING
S2 WNDG 1 BREAKER
52a CONTACT
52b CONTACT
BKR CONNECTED
S2 WNDG 2 BREAKER
52a CONTACT
52b CONTACT
BKR CONNECTED
S2 SYSTEM SETUP
W1 SENS GND PRIM
5 A
W2 SENS GND PRIM
5 A
6–47