Contents Controller user guide ................................4 1.1. Control panel ..................................4 1.2. Main screen ................................... 5 1.3. Active components ................................5 1.4. Mode ...................................... 6 1.5. Operation program ................................7 1.6. Heat pump status ................................... 8 1.7. List of user menus ................................10 1.8.
This allows the user to access the selected menu. This is used to move from one adjustable parameter to another in the same screen. This is used to access the INFORMATION menu directly from the main screen. GEOSMART ENERGY...
Aerothermal fan activated Source pump activated Compressor in start-up phase Compressor activated Compressor in shut-down phase Production pump activated Heating units activated Cooling units activated Auxiliary heating unit activated HTR system activated Crankcase heating activated. GEOSMART ENERGY...
Note: After all the stages set in the floor drying program are completed, the heat pump returns to normal operation and this screen disappears. If there are requests for the enabled services, the heat pump deals with them. GEOSMART ENERGY...
The heat pump automatically switches between the WINTER/SUMMER operating programs, depending on the outside temperature. The temperatures and time required for the switch must be adjusted by the user. REMOTE Control WINTER / SUMMER program selection is triggered by an external signal. GEOSMART ENERGY...
The heat pump is off due to an active time schedule or calendar and is therefore not available to activate any of its functions. OFF status due to data bus signal The heat pump is off due to an external signal through the data bus and is therefore not available to activate any of its functions. GEOSMART ENERGY...
Page 9
The EVU signal is used in some countries by the electricity company to control electrical consumption. The EVU signal prevents energy production by the compressor and the auxiliary equipment. Circulator NOTE pumps, valves and other components can be activated to consume energy from the storage systems. GEOSMART ENERGY...
XXXXXX User menu XXXXXX Cooling DHW/Legionella prot. Pool User menu DHW/Legionella prot. Pool e-Manager User menu e-Manager Information Alarms User menu e-Manager Information Alarms User menu e-Manager Information Alarms Figure 1.3. Browsing through the list of user menus. GEOSMART ENERGY...
Summer/Winter change Winter: 12.0ºC to switch between the WINTER and SUMMER programs. Summer: 26.0ºC Time to change: The selected status of the heat pump can be changed automatically using the time schedule functions, calendar or using active alarms. NOTE GEOSMART ENERGY...
Holiday schedule Enable: This can be used to program up to 3 periods a year when the heat pump stays on or off. State: Swiched Off Sp. Season Start Stop 1.Month/Day 00/00 00/00 2.Month/Day 00/00 00/00 3.Month/Day 00/00 00/00 GEOSMART ENERGY...
Emergency: mode. Support: In EMERGENCY mode, the auxiliary system is activated automatically when any of the alarms are active. In SUPPORT mode, the auxiliary system is activated automatically for normal HEAT production, as programmed by the technical service. GEOSMART ENERGY...
DHW storage tank. It is also used to adjust the setpoint SetT 48.0ºC DTstart: 5.0ºC temperature for DHW heating with the HTR system. SetT HTR: 70.0ºC icon indicates that there is a time schedule activated in the DHW mode. GEOSMART ENERGY...
Information Alarms Enable surplus control Surplus control Used to enable the surplus electricity control. Enable: The surplus control tries to adjust the network balance (consumption and injection) at all times to the value configured in the installer menu. GEOSMART ENERGY...
There are separate screens for the heating and cooling outlet units. SG4: 35.0 35.1 94.6 DHW Tank This shows the setpoint temperature, the start-up temperature differential and the current RealT: 47.9ºC temperature of the DHW storage tank. SetT: 48.0ºC DTstart: 5.0ºC Start comp .T: 43.0ºC GEOSMART ENERGY...
Page 17
Used to display current values of the power consumed and injected into the grid. Consumption: 28.3kWh Injection: 6.3kWh Month/Year Month/Year SEPTEMBER Used to display for each month and annually the values of the energy consumed and Consumption: 28.3kWh injected into the grid. Injection: 6.3kWh GEOSMART ENERGY...
The heat pump is blocked and switches to EMERGENCY mode when a critical alarm goes Reset alarms: off more than 5 times a day. In these cases, the heat pump can be unblocked from this screen once the problem has been solved. GEOSMART ENERGY...
6. Default values 7. Change password Table 2.1. INSTALLER menu structure. 2.1. Language selection Installer menu a.Change language b.Configuration c.Information Language Language 1. Used to select the language of the heat pump controller. Language: ENGLISH ENTER to change GEOSMART ENERGY...
4. Used to adjust the source fluid temperature required to finish the defrost program. 5. Used to adjust the maximum defrost program operation time. Note: This screen is only available for aerothermal or hybrid source systems and with models that include integrated passive cooling. GEOSMART ENERGY...
DG1: NO-DI5 heating mode. SG2: NO-DI7 SG3: NO-DI9 A. NO: Contact closed to activate the request. SG4: NC-DI11 SG5: NC-DI13 B. NC: Contact open to activate the request. 2. Shows the connection terminal of each digital input (DIxx). GEOSMART ENERGY...
Page 22
Note: The calculation of the target outlet temperatures based on the heating curves of the Good outlet units is carried out using an attenuated outdoor temperature. The higher the insulation level, the higher the attenuation applied to the outdoor temperature. GEOSMART ENERGY...
Brine pump: Used to enable use of the collector circulator pump for the passive cooling service. Note: The passive cooling system is enabled by requests coming from indoor terminals, even in installations with a cooling buffer storage tank. GEOSMART ENERGY...
Page 24
SUMMER program, the heat pump will change automatically to the SUMMER program and vice versa. Note: This configuration is associated to the heating and cooling services. If it is modified for the heating service, it will automatically change for cooling. GEOSMART ENERGY...
Page 25
Cooling buffer Cooling Buffer 1. Allows adjust the minimum settable cooling buffer setpoint. This is the setpoint in case Min.SetP: 7 ºC of surplus for the SG states. GEOSMART ENERGY...
1. Used to adjust the target temperature difference between the production circuit DTpool: 5.0ºC outlet and inlet in pool mode. Pool Pool 1. Allows adjust the maximum settable pool setpoint. This is the setpoint in case of Max SetP: 30 ºC surplus for the SG states. GEOSMART ENERGY...
(1 phase) or three-phase (3 phases). Address: NOTE: The default meter address is 100. If you change the meter address on the display, Connection type: you must also change it physically on the meter as per the manufacturer's instructions in the manual. GEOSMART ENERGY...
1. Used to enable the indoor auxiliary resistor for heating, DHW and/or pool services. In Internal elec. heater the USER level, its use must be enabled as SUPPORT and/or EMERGENCY for the Enable: DHW: heating, DHW and/or pool services. Heating: Pool: Production pump: GEOSMART ENERGY...
Page 29
Note: In the USER level, its use must be enabled as SUPPORT and/or EMERGENCY for the heating, DHW and/or pool services. Note: If it is enabled for DHW, it will also be used for the LEGIONELLA PROTECTION programs. GEOSMART ENERGY...
SG2 Mode 1. Used to adjust the temperature differential for each service on the heat pump Valley setpoints, when the stat SG2 "Reduced tariff" is active. DHW: 2 ºC Heating: 5 ºC Cooling: -2 ºC Pool: 5 ºC GEOSMART ENERGY...
Page 31
BAUDRATE: 4 STOP BIT: 2 Note: This port can be used to connect indoor bus terminals with MODBUS MASTER PARITY: None configuration. Note: This port can be used to access the controller remotely with MODBUS SLAVE EXTENDED configuration. GEOSMART ENERGY...
The minimum source temperature must be at least 5ºC higher than the freezing temperature of the fluid used. If you are not sure of the freezing temperature of the fluid used, check it with a refractometer. GEOSMART ENERGY...
1. Display the type of probe installed in each analogue input and their current value. Probe type: 2. Used to enter a correction of the probe readings. Value: 4.1ºC Note: There are screens for all temperature and hydraulic pressure probes and for the Correction: 0.0ºC external temperature probe. GEOSMART ENERGY...
This shows the current status of all digital inputs. DI2: DI9: DI3: DI10: DI4: DI11: DI5: DI12: DI6: DI7: AO Signals AO signals AO1: 100.0 This shows the current status of all analog outputs. AO2: 87.4 AO3: 56.9 AO4: 32.9 AO5: 46.5 AO6: GEOSMART ENERGY...
Delete data logger: 2.18. Default values Installer menu e.Alarm log f.Default values g.Change password Initialization Initialization 1. Used to delete the settings in the USER and INSTALLER menus and restore default Delete user settings and set default factory settings. values: GEOSMART ENERGY...
Note: This option is only available for heat pumps with Danfoss compressors. 2.19. Change password Installer menu e.Alarm log f.Default values g.Change password New password New password 1. Used to change the password to access the INSTALLER menu (PW1). Insert new installer (PW1): 0000 password GEOSMART ENERGY...
Production safety valve DHW Recirculation HTR system retention valve DHW storage tank Source drain valve DHW coil Production discharge valve Manual trap HTR system discharge valve Storage tank drain valve DHW valve DHW temperature probe Passive cooling production valve GEOSMART ENERGY...
Page 38
Installer manual NETZERO NETZERO BW H B NETZERO BW P B 33 34 31 32 33 34 31 32 NETZERO BW R B NETZERO BW B B 33 34 31 32 33 34 31 32 GEOSMART ENERGY...
NETZERO 9 kW / NETZERO 12 kW / NETZERO 22 kW -7; 65 35; 65 -25; 40 35; 10 -25; 10 Source / Cooling outlet temperature (ºC) Maximum speed of compressor is not able in all the areas of the operation map. NOTE GEOSMART ENERGY...
Q ≥ 1.2 x P , where: i. Q= flow in litres per minute. ii. P = cooling power at 25% of compressor, see operating curve graphs. 11. Only for NETZERO CW GEOSMART ENERGY...
Page 64
GEOSMART ENERGY 1-650 Jamieson Parkway, Cambridge, ON N3C 0A5 T: 1.866.310.6690 P: 519-624-0400 F:1-866-533-3889 800791 E: info@geosmartenergy.com http://www.geosmartenergy.com/ Technical service manual version 01/2022 The manufacturer reserves the right to make modifications without prior notice.
Need help?
Do you have a question about the NETZERO BW Series and is the answer not in the manual?
Questions and answers