Rio3-Pba (Profibus Network Adapter); Rio3-Pba Specification - Hitachi HX-RIO3 Series User Manual

Profibus network adapter
Hide thumbs Also See for HX-RIO3 Series:
Table of Contents

Advertisement

8

3. RIO3-PBA (PROFIBUS Network Adapter)

3.1. RIO3-PBA Specification

Interface Specification, RIO3-PBA
Communication Interface Specification
Redundancy
Repeater Control Signal
Freeze mode
Sync mode
Auto baudrate
Fail safe mode
Station type
FMS support
Max. Network Node
Max. Expansion Slot
I/O Data Size
Indicators
Communication Rate
Communication Speed
Bus Connection
Other Serial Port
Serial Configuration (RS232)
Module Location
Field Power Detection
General Specification
UL System Power
System Power
Power Dissipation
Current for I/O Module
Isolation
UL Field Power
Field Power
Not supported
RS-485 Signal
Support
Support
Support
Support
Slave
Not supported
125 Nodes
63 Slots
Input : 244bytes / Output : 244bytes
6 Status LEDs
1 Green/Red, Module Status (MOD)
1 Green/Red, Network Status (NET)
1 Red, Diagnostic Status (DIA)
1 Green/Red Expansion I/O Module Status (IOS)
1 Green, System Power Status
1 Green, Field Power Status
9.6K~12M(1.2Km~100m)
9.6 ~12000Kbps (Auto baudrate selection)
9 Pin D-Sub Connector
RS232 for MODBUS/RTU, Touch Panel or IOGuide
Node
:
Baud Rate
: 115200 (Fixed)
Data bit
:
Parity bit
: No parity (Fixed)
Stop bit
:
Starter module left side of HX-RIO3 Series System
About 14Vdc
Supply voltage : 24Vdc Nominal, Class 2
Supply voltage : 24Vdc nominal
Supply voltage range : 16~30Vdc
Protection : Output current limit (Min. 1.5A)
Reverse polarity protection
100mA @24Vdc
1.5A @5Vdc
System power to internal logic : Non-Isolation
System power I/O driver : Isolation
Supply voltage : 24Vdc nominal, Class 2
Supply voltage : 24Vdc typical (Max.30Vdc)
1 (Fixed)
8 (Fixed)
1 (Fixed)
HX-RIO3 Series