Summary of Contents for Moso ST40KTL-M

  • Page 1 光伏并网逆变器 光伏并网逆变器 ST40KTL-M/ ST50KTL M/ ST50KTL-M/ ST60KTL-M 用户手册 用户手册 版本号 版本号 V2.0...
  • Page 2 版权声明 本手册的版权属于茂硕科技股份有限公司 (之后简称为“茂硕电 源”)。任何单位或者个人不允许复制或部分复制(包括电子版本等等) 本手册的内容,且不允许以任何形式或手段转制和分发。茂硕电源保留 所有权利,且拥有最终的解释权。所有相关信息有可能会被修改,但不 会另行通知,敬请谅解。...
  • Page 3: Table Of Contents

    目录 1.产品介绍 ........................ I 1.1 简述 ........................ I 1.2 装箱清单 ..............错误!未定义书签。 2.安全说明 ......................III 2.1 安全标志及认证标识 .................. III 2.2 使用须知 ...................... IV 3.操作界面 ....................... V 3.1 操作界面示意图 ..................VI 3.2 操作按键及状态指示灯 ................VI 3.3LCD 显示界面 ....................VII 4.产品储存 ......................VIII 5.产品安装...
  • Page 4: 产品介绍

    1.产品介绍 1.1 简 述 ST40-60KTL-M 三相组串式并网逆变器是将太阳能光伏组件的直流电 三相组串式并网逆变器是将太阳能光伏组件的直流电 能转化为交流电能,并输送到电网的一种新型发电装置。 能转化为交流电能,并输送到电网的一种新型发电装置。 逆变器型号如下: ST40KTL-M, ST50KTL-M, ST60KTL ST60KTL-M 图 1 ST40KTL-M, ST50KTL M, ST50KTL-M, ST60KTL-M 产品展示图...
  • Page 5 1.产品介绍 ST40-60KTL-M 逆变器装箱清单 序号 描述 单位 ST40/50/60KTL-M 逆变器 台 背挂板 件...
  • Page 6: 安全说明

    防盗螺丝 件 膨胀螺丝 件 直流连接器 组 说明书 份 并网资料 份 冷压 OT 端子 个 2.安全说明 请在使用前仔细阅读此说明书,不正确的使用可能会导致触电或烧伤 请在使用前仔细阅读此说明书,不正确的使用可能会导致触电或烧伤 的危险,在安装和维护过程中,必须按照本说明书上的指示进行操作。说明 的危险,在安装和维护过程中,必须按照本说明书上的指示进行操作。说明 书请妥善保管,以便日后参照。 2.1 安 全 标 志 及 认 证 标 识 安全标志是向工作人员警示的危险状况,指导人们采取合理行为。本 安全标志是向工作人员警示的危险状况,指导人们采取合理行为。本 说明书中使用的安全标志及认证标志如下: 标志如下: 符号意义:高温 符号意义:接地 逆变器通过机体外表 逆变器通过机体外表 逆变器机体需要进行 散热,请勿接触非正 请勿接触非正...
  • Page 7: 使用须知

    备损坏或人员伤亡 符号意义:放电延时 逆变器放电时间需 5 符号意义:交流电(AC) 分钟, 发电前自检时间 需 1-5 分钟 符号意义:中国 CQC 认 认 符号意义:CE 认证 证 表 示 该 产 品 已 通 过 表示该产品已通过中国 表示该产品已通过中国 TUV 认证 太阳能产品认证 符号意义:SAA 认证 符号意义:TUV 认证 表示产品已通过 SAA 表示产品已通过 CE 认 认 证...
  • Page 8: 操作界面

    光伏组件暴露在阳光下会形成高压直流电,慎防电 击。 请选用优良的铜线作为逆变器输出接线, 慎防劣质材 料造成人员财产损失。 请参照说明书制作逆变器直流输入接线, 慎防高压直 流线路接触不良造成人员财产损失。 逆变器运行时机体处于散热状态,慎防高温。 涉及到本逆变器的行为都需要专业人员来完成。 选用晶硅组件时逆变器正负极输入线路不能接地。 选 用薄膜组件时逆变器输入线路需要按组件要求接地, 并在输出增加隔离变压器, 避免设备损坏造成人员财 产损失。 请严格根据设备参数规格配置逆变器直流电和交流 电的配电设备, 参照说明书正确安装逆变器避免设备 损坏、工作不良,造成人员或财产损失。 所有包括但不限于不符合本说明书要求的行为所造 成的后果都不在本产品质保、责任范围内。 光伏组件阵列串并联设计对错涉及到系统运行稳定安 全与否。在逆变器接入组件容量过载运行方面,逆变器 对输入电流可以实现控制,但对输入的最大电压没法控 制。因此设计上应考虑光伏组件在低温-25℃时串联的 最大开路电压,我司建议 60 芯片型组件最大串联联数 量为 22 块,72 芯片型组件最大串联联数量为 18 块。 3.操作界面...
  • Page 9: 操作界面示意图

    3.1 操 作 界 面 示 意 图 图 2 操作界面 3.2 操 作 按 键 及 状 态 指 示 灯 逆变器的前面板上有四个操作按键,三个状态指示灯。左边是电源指示灯 (绿色)显示逆变器的直流电源输入状态,并网指示灯(绿色)显示工作的状 态,右边的警示灯(红色)显示逆变器的报警状态。详细状态说明如下所示: 按键 说明 取消/退出菜单 上一页/上一项/减 下一页/下一项/加 确定/进入下一级菜单 状态 说明 指示灯 亮 逆变器检测到直流电压 灭 直流输入电压过低或没有 亮 逆变器发电正常 灭...
  • Page 10: Lcd 显示界面

    3.3LCD 显 示 界 面 LCD 显示屏位于逆变器的前面板,信息显示量为 2 行。通过按键可进行 翻页查看信息及进入下一级菜单查看信息,还可以进入设置页面对逆变器参数 进行调整。功能树状图如下:...
  • Page 11: 产品储存

    图 3 操作流程 4.产品储存 如果逆变器不是立即投入运行,则需要将逆变器存放在特定的环境条件下: 逆变器需要原包装箱重新打包。  包装箱需要使用胶带进行密封。  逆变器需要存放在清洁干燥的地方,并防止灰尘及水汽的侵蚀。 ...
  • Page 12: 产品安装

    存储地点的温度应该保持在-25℃ ℃-60℃, 相对湿度应保持在 0 到 95%之间,  且无冷凝。 多台逆变器叠放,建议最大可累计层数不超过 多台逆变器叠放,建议最大可累计层数不超过 4 层。  避开化学腐蚀性物质,否则可能会腐蚀逆变器。 避开化学腐蚀性物质,否则可能会腐蚀逆变器。  存储期间,需要定期检查,发现虫蛀鼠咬等情况 ,需要定期检查,发现虫蛀鼠咬等情况,需要及时更换包装材料。  包装箱不可倾斜或者倒置。  长期存放后,逆变器需要经过专业人员的全面检查和测试才能投入运行使 长期存放后,逆变器需要经过专业人员的全面检查和测试才能投入运行使  用。 5.产品安装 5.1 选 择 安 装 位 置 选择一个良好的安装位置,是光伏系统运行稳定、安全、友好的关键,选 选择一个良好的安装位置,是光伏系统运行稳定、安全、友好的关键,选 择位置要考虑 2 个关因素:散热、噪音。 个关因素:散热、噪音。 请勿将逆变器安装在不通风的密闭空间 请勿将逆变器安装在不通风的密闭空间,确保逆变器周围空气的流动性,...
  • Page 13 逆变器平躺安装、倾斜安装都是禁止的,逆变器正确的安装方式是垂直壁挂安 装。安装方式如下图。 图 4 多台横向安装 图 5 多台田字型安装 逆变器通过附件中的背挂板安装在墙面或者金属支架上,使用背挂板参考或者 按照下面尺寸来开孔固定背挂板。安装尺寸如下: ST40/50/60KTL-M 安装参数:...
  • Page 14 图 6 ST40/50/ 40/50/60KTL-M 背挂板尺寸 图 7 ST40/50/ 40/50/60KTL-M 背挂示意图...
  • Page 15: 电气连接

    5.3 电 气 连 接 逆变器设计了快速连接端子口, 电气连接时不需要打开上盖。 相应逆变器箱 体底部的标识的含义在下表中。所有电气连接需要符合国家相关标准。 标识 说明 光伏组件正极接入端 光伏组件负极接入端 PV1,PV2,PV3 分别对应 MPPT1,2,3 的输入端子 DC SWITCH 直流开关 RS485 RS485 通讯端口 RS485 通讯接线口 A RS485 通讯接线口 B WIFI WIFI 模块安装口 GPRS GPRS 模块安装口 AC OUTPUT 交流接线口 火线接线端 火线接线端 火线接线端...
  • Page 16 图 8 直流征集配对 图 9 直流负 极配对 2)MC4 直流端子组装的步骤如下所列: 组装的步骤如下所列: 将直流电缆线护套剥开约 7mm 插入端子芯, 插入端子芯,如图所示:...
  • Page 17: 交流端连接

    “插芯是铜柱加厚型 材料,能实现大电流 载量。建议使用方形 压线配线压接” 图 10 MC4 端子压线制作 图 5.3.2 交 流 端 连 接 ST40,50,60KTL-M 交流接线示意图 交流接线示意图: 交流电缆压接铜鼻后,直接通过螺丝锁在机器内部 交流电缆压接铜鼻后,直接通过螺丝锁在机器内部 PCB 上,机壳接地位置位于 如图机身右下方侧面...
  • Page 18 图 11 ST40/50/60KTL-M 交流接线示意图 铜线线缆线径对照 机型 ZRC-YJV-3*三相+地线 ST40,50,60KTL-M ZRC-YJV-3*25mm2+16mm2; 备注:逆变器交流侧可以不接 N 线,常规地线规格是火线一半线径,零线与火 线规格一致。 5.3.3 监 控 安 装 RS485 通讯方式 逆变器共有 3 种监控方式:RS485,WIFI,GPRS。 多用于 多台逆变器串联通讯监控,WIFI 模块,GPRS 模块多用于单台逆变器通讯监控。 对应通讯接口及模块安装位置如下图所示。 ST40/50/60KTL-M RS485 通讯端口:...
  • Page 19: 产品并网及调试

    图 12 ST40/50/60KTL 40/50/60KTL-M RS485 通讯端口 逆变器多台监控可通过 RS485 通讯线缆以菊花链形式实现通讯连接, 系统 通讯线缆以菊花链形式实现通讯连接, 系统 图如下: 逆变器1 逆变器2 逆变器N WIFI 盒子 互 GPRS 盒子 联 网 通过通讯协议 接入其他监控系统 图 13 RS485 RS485 串行通讯监控 6.产品并网及调试 并网前,本产品应用的系统设计、配置、安装应考虑本说明书条 并网前,本产品应用的系统设计、配置、安装应考虑本说明书条 款 2.2,条款 5 所提及的内容。并按照下列指示进行并网前检查: 所提及的内容。并按照下列指示进行并网前检查: 1) 使用万用表逐一测量每一路直流 使用万用表逐一测量每一路直流支路的电压符合条款...
  • Page 20: 故障告警排查处理

    以上内容检查符合要求后, 通过扭旋转逆变器左下方的直流开关开启逆变 器并等待逆变器 LCD 屏幕点亮工作。逆变器 LCD 屏幕正常工作后,可根据本 说明书条款 2.3 的指导内容, 对 LCD 屏幕所显示的输入参数参数信息进行查看。 此时逆变器处于非并网状态,逆变器应处于告警状态,并显示电网故障。确认 所检测到的直流输入参数符合万用表所测量的电压值后,则可以通过系统的交 流配电箱合并交流开关进行并网。 逆变器并网过程包括:初始化开机——等待——自检——并网,自检过 程中相应指示灯会闪烁提示并伴随内部继电器闭合断开的声音。逆变器并网后 系统调试人员应查看逆变器的输入参数和输出参数,直流参数稳定,交流参数 稳定,变动幅度小表示并网成功,状况良好。 最后, 根据本说明书条款 2.3 的指导内容, 对逆变器的时间、 通讯地址 (默 认为 01)进行设定,完成并网调试工作。 如果并网失败或者异常,请根据本说明书的故障排查指导内容进行操作, 例如常见的电网电压过高等问题,如碰到困难或无法自行完成,请向当地经销 商进行咨询。 7.故障告警排查处理 逆变器是按并网运行的标准进行设计的,符合的安全要求和电磁兼容性要 求。在供给客户之前,逆变器经过若干道严格的测试去保证它能持久可靠地优 化运行。如果出现故障,液晶显示屏会显示报警信息。在这种情况之下,逆变 器可能会停止发电。其故障的情景和可能的原因如下表所示。 报警代码及显示信息 处理方法 直流绝缘阻抗过低告警;使用万用 表、摇表分别测量正负极对大地、...
  • Page 21 LCD 屏与控制板通信断开告警; W002 Comm_LCD_Lose_Warning LCD 屏与控制板的通讯线异常,请 联系茂硕协助处理。 低电压穿越故障告警;电网电压出 W003 LVRT_Fault_Warning 现过低电压穿越情况 风扇故障告警;风扇异常,请排查 风扇是否有异物卡死,关机清理异 W004 Fan_Fault_Warning 物后故障如不消失,请联系当地经 销商协助处理。 报警代码及显示信息 处理方法 直流主断路器断开告警;直流主断 路器开路,请排查直流线路是否存 W005 DC_AirSwitchOpenWarning 在短路情况,在排除异常前切勿尝 试重新并网 锁存的总硬件故障;设备硬件检测 到的过流、过压告警(比软件精度 W006 Fault_Feedback_Warning 高、快),请联系茂硕协助处理, 切勿尝试重新并网。 交流三相电压不平衡故障告警;观 察逆变器屏幕检测到的三相电压是 W007 AC_Volt_Unbalance_Warning 否平衡,排查交流线路是否异常或 三相负载不均匀或某相有超大负载 启动 交流锁相环故障告警;电网存在振 荡无法检测到电网相位点,请查看 W008 AC_PLL_Warning 电网电压值是否稳定,并联系茂硕...
  • Page 22 AC 端防雷故障告警; 交流防雷动作, 请 W010 AC_Thunder_Warning 排查是否存在雷击情况,联系茂硕协助 处理。 烟感告警; 请确认是否非正常烟雾情况, W011 Smoke_Detect_Warning 排查异常 降额运行告警;请确认目前逆变器散热 W012 Power_Derate_ Warning 情况, 逆变器散热异常会导致降额运行。 直流输入极性接反故障; 直流输入接反, F001 DC Inversed Failure 请立即断开直流线路并矫正接线 直流绝缘阻抗故障;多次检测到直流绝 F002 DC_Insulation_Failure 缘低于正常值,在排除直流线路绝缘问 题前禁止尝试重新并网 直流漏电流故障; 直流对地存在漏电流, F003 GFDI_Failure 请逐一排查每一串组串的对地绝缘值。 GFDI(电池一端接地)接地故障;直流 F004 GFDI_Ground_Failure 组串存在对地接地情况,在查清故障前 禁止尝试并网。...
  • Page 23 组件电压过低无法启动,请联系貌似协 助处理 报警代码及显示信息 处理方法 交流主接触器错误 (AC_MainContactor_Fault 连续出现 F011 AC_MainContactor_Failure 3 次时报错误);逆变器交流接触器连 续合并 3 次失败, 请联系茂硕协助处理。 交流辅接触器错误 (AC_SlaveContactor_ Fault 故障连 F012 AC_SlaveContactor_Failure 续出现 3 次);逆变器交流接触器连续 合并 3 次失败,请联系茂硕协助处理。 预留; 软件预留空位, 如出现该误报警, F013 Reseverd 请联系茂硕协助处理。 直流软件过流故障;软件检测到过流, 请排查直流安装容量配置, 如多次报警, F014 DC_OverCurr_Failure 请排查直流线路是否存在熔短情况,并 请联系茂硕协助处理 交流软件过流故障;软件检测到过流,...
  • Page 24 短情况,并联系茂硕协助处理。 硬件交流过流故障;请排查交流线路是 F018 Tz_Ac_OverCurr_Fault 否存在绝缘低、熔短、虚短、假短情况, 并联系茂硕协助处理。 硬件集成故障 (所有硬件故障的合成) ; 请排查输入、 输出线路是否存在绝缘低、 F019 Tz_Integ_Fault 熔短、虚短、假短情况,并联系茂硕协 助处理。 报警代码及显示信息 处理方法 直流硬件过流故障;请排查直流线路是 F020 Tz_Dc_OverCurr_Fault 否存在绝缘低、熔短、虚短、假短情况, 并联系茂硕协助处理。 直流漏电流过流故障;请排查直流线路 F021 Tz_GFDI_OC_Fault 是否存在绝缘低、熔短、虚短、假短情 况,并联系茂硕协助处理。 急停故障,按下急停按钮后报出该故障, 逆变器脱开电网并脱开直接断路器;该 F022 Tz_EmergStop_Fault 按键只能由人手按下,旋转弹起复位, 如非运维人员操作,请确认安保问题。 交流漏电流瞬间过流故障;交流存在突 F023 Tz_GFCI_OC_Fault 变漏电流,请排查交流线路、配电绝缘 情况,甚至用电负载,恢复并网。 直流绝缘阻抗故障;使用万用表、摇表 分别测量正负极对大地、支架、边框的 F024 DC_Insulation_ Fault 绝缘电阻值,低于...
  • Page 25 直流反灌故障;检测到有反向直流电, 请立即断开所有直流线路,并检查直流 F025 DC_Feedback_Fault 线路的电压、绝缘、耐压,判断是否存 在短路,禁止强行并网。 直流母线不平衡故障;逆变器正负母线 电压异常,请单独接入一组组串尝试判 F026 BusUnbalance_Fault 断是否逆变器存在内部异常,并联系茂 硕协助排查处理。 直流端绝缘隔离错误;使用万用表、摇 表分别测量正负极对大地、支架、边框 F027 DC_Insulation_Fault 的绝缘电阻值,低于 37k 为不良,逐段 排查线路,MC4 插头,组件是否有破损 隐裂。 逆变 1 直流量高故障;逆变器直流分量 F028 DCIOver_M1_Fault 异常,请联系茂硕协助处理 报警代码及显示信息 处理方法 交流负荷开关故障;逆变器继电器合并 失败,请断开交流电,万用表测量每一 F029 AC_AirSwitch_Fault 段交流线路的 L-N-PE 之间的电阻值, 如不是无限大请排除绝缘问题。 交流主接触器故障;逆变器交流接触器 AC_MainContactor_Fault F030 连续合并...
  • Page 26 异常,请联系茂硕协助处理 交流电流过高(软件报出的交流电流过 流故障,1 个工频周期来报出);交流 F033 AC_OverCurr_Fault 输出电流过高,请查看交流电压是否有 跌落,或者交流线路是否是熔短、假短 情况,并联系茂硕协助处理。 交流过载;情况类同 F033,并联系茂硕 F034 AC_Overload_Fault 协助处理。 交流端无市电错误;请检查是否有市电 F035 AC_NoUtility_Fault 接入。 交流电网相序错误;关闭直流电直到屏 F036 AC_GridPhaseSeque_Fault 灭,断开交流电压,把交流 A、B 两根 火线调换位置重新上电并网 交流三相电压不平衡故障;请查看逆变 器屏幕交流三相电压是否一致,如果电 F037 AC_Volt_Unbalance_Fault 压差异较大,侧为电网三相负载不平衡 导致,联系供电部门协调处理。 交流三相电流不平衡故障;请查看三相 F038 AC_Curr_Unbalance_Fault 交流电流是否一致、 三相电压是否一致, 并联系茂硕协助处理。 交流过流故障(软件报出的过流故障, 一个开关周期内报出);交流输出电流 F039 INT_AC_OverCurr_Fault 过高,请查看交流电压是否有跌落,或...
  • Page 27 交流 WU 线电压过低;查看三相交流电 压, 保护范围是额定交流电压的 0.8-1.2 F042 AC_WU_UnderVolt_Fault 倍,超出范围为正常保护值,需观察并 网输出功率情况,输出线路阻抗,电网 负载轻载情况,协调供电部门处理。 交流 VW 线电压过高;查看三相交流电 压, 保护范围是额定交流电压的 0.8-1.2 F043 AC_VW_OverVolt_Fault 倍,超出范围为正常保护值,需观察并 网输出功率情况,输出线路阻抗,电网 负载轻载情况,协调供电部门处理。 交流 VW 线电压过低;查看三相交流电 压, 保护范围是额定交流电压的 0.8-1.2 F044 AC_VW_UnderVolt_Fault 倍,超出范围为正常保护值,需观察并 网输出功率情况,输出线路阻抗,电网 负载轻载情况,协调供电部门处理。 交流 UV 线电压过高;查看三相交流电 压, 保护范围是额定交流电压的 0.8-1.2 F045 AC_UV_OverVolt_Fault 倍,超出范围为正常保护值,需观察并...
  • Page 28 出范围为正常保护,等待电网回复 或协调供电部门处理。 交流频率过低故障;查看三相交流 频率,保护范围是 49.5-50.2,超 F048 AC_UnderFreq_Fault 出范围为正常保护,等待电网回复 或协调供电部门处理。 U 相并网电流直流分量高;关闭逆 F049 AC_U_GridCurr_DcHigh_Fault 变器 5min 然后重启,并联系茂硕 协助处理。 V 相并网电流直流分量高;关闭逆 F050 AC_V_GridCurr_DcHigh_Fault 变器 5min 然后重启,并联系茂硕 协助处理。 W 相并网电流直流分量高; 关闭逆 F051 AC_W_GridCurr_DcHigh_Fault 变器 5min 然后重启,并联系茂硕 协助处理。 交流电感 A 相电流直流分量过高; F052 AC_A_InductCurr_DcHigh_Fault 关闭逆变器 5min 然后重启,并联 系茂硕协助处理。...
  • Page 29 报警代码及显示信息 处理方法 交流反灌故障;请停止并网,排查直 流、交流绝缘情况,只有在直流线路 F057 AC_BackFeed_Fault 在发电情况下出现短路才会造成交流 反灌情况。或交流电压峰值大于直流 电压峰值,请联系茂硕协同处理 交流电网 U 电流过流故障;请确认是 并网瞬间报过流,还是并网运行一段 时间后报过流,查看逆变器输出交流 F058 AC_U_GridCurr_High_Fault 的电压电流参数,看报故障时电压电 流变化是否有突变。根据突变的相线 排查线路绝缘问题,并联系茂硕协助 处理。 交流电网 V 电流过流故障;请确认是 并网瞬间报过流,还是并网运行一段 时间后报过流,查看逆变器输出交流 F059 AC_V_GridCurr_High_Fault 的电压电流参数,看报故障时电压电 流变化是否有突变。根据突变的相线 排查线路绝缘问题,并联系茂硕协助 处理。 交流电网 W 电流过流故障; 请确认是 并网瞬间报过流,还是并网运行一段 时间后报过流,查看逆变器输出交流 F060 AC_W_GridCurr_High_Fault 的电压电流参数,看报故障时电压电 流变化是否有突变。根据突变的相线...
  • Page 30 时间后报过流,查看逆变器输出交流 的电压电流参数,看报故障时电压电 流变化是否有突变。根据突变的相线 排查线路绝缘问题,并联系茂硕协助 处理。 电抗器 B 相电流过流故障;请确认是 并网瞬间报过流,还是并网运行一段 时间后报过流,查看逆变器输出交流 F062 AC_B_InductCurr_High_Fault 的电压电流参数,看报故障时电压电 流变化是否有突变。根据突变的相线 排查线路绝缘问题,并联系茂硕协助 处理。 报警代码及显示信息 处理方法 电抗器 C 相电流过流故障;请确认 是并网瞬间报过流, 还是并网运行一 段时间后报过流, 查看逆变器输出交 F063 AC_C_InductCurr_High_Fault 流的电压电流参数, 看报故障时电压 电流变化是否有突变。 根据突变的相 线排查线路绝缘问题, 并联系茂硕协 助处理。 IGBT 散热器温度过低故障;真冷, F064 Heatsink_LowTemp_Fault 散热器都冻僵了。 逆变模块 1 IGBT 散热器过温故障; 请查看平面上检测到的温度,...
  • Page 31 预留;软件预留空位,如出现该误报 F067 Reseverd 警,请联系茂硕协助处理。 预留;软件预留空位,如出现该误报 F068 Reseverd 警,请联系茂硕协助处理。 电抗器过温故障; 请查看平面上检测 F069 Inductor_OverTemp_Fault 到的温度,确保风扇正常工作、风道 通畅,并联系茂硕处理。 电抗器低温故障; 请查看平面上检测 F070 Inductor_LowTemp_Fault 到的温度,确保风扇正常工作、风道 通畅,并联系茂硕处理。 主隔离变压器过温故障; 请查看平面 F071 Transformer_OverTemp_Fault 上检测到的温度,确保风扇正常工 作、风道通畅,并联系茂硕处理。 主隔离变压器低温故障; 请查看平面 F072 Transformer_LowTemp_Fault 上检测到的温度,确保风扇正常工 作、风道通畅,并联系茂硕处理。 报警代码及显示信息 处理方法 GFCI(RCD)交流漏电流故障;交流存 在漏电流,请尝试使用万用表串接在 N F073 GFCI_Fault 线上,查看并网时漏电流大小,并逐一 去除直流输入组串,排查漏电来源。...
  • Page 32 压穿越情况 DC 端防雷发生故障;直流防雷动作,请 F077 DC_Thunder_Fault 排查是否存在雷击情况,联系茂硕协助 处理。 AC 端防雷发生故障;交流流防雷动作, F078 AC_Thunder_Fault 请排查是否存在雷击情况,联系茂硕协 助处理。 F079 ENV_OverTemp_Fault 环境温度高;太热了 F080 ENV_UnderTemp_Fault 环境温度低;太冷了 交流 U 相电压过高; 查看三相交流电压, 保护范围是额定交流电压的 0.8-1.2 倍, F081 AC_U_OverVolt_Fault 超出范围为正常保护值,需观察并网输 出功率情况,输出线路阻抗,电网负载 轻载情况,协调供电部门处理。 交流 U 相电压过低; 查看三相交流电压, 保护范围是额定交流电压的 0.8-1.2 倍, F082 AC_U_UnderVolt_Fault 超出范围为正常保护值,需观察并网输...
  • Page 33 出功率情况,输出线路阻抗,电网负载 轻载情况,协调供电部门处理。 交流 W 相电压过高; 查看三相交流电压, 保护范围是额定交流电压的 0.8-1.2 倍, F085 AC_W_OverVolt_Fault 超出范围为正常保护值,需观察并网输 出功率情况,输出线路阻抗,电网负载 轻载情况,协调供电部门处理。 交流 W 相电压过低; 查看三相交流电压, 保护范围是额定交流电压的 0.8-1.2 倍, F086 AC_W_UnderVolt_Fault 超出范围为正常保护值,需观察并网输 出功率情况,输出线路阻抗,电网负载 轻载情况,协调供电部门处理。 A 路直流电压高;请立即断开直流线路 并用万用表测量直流输入电压,确保电 压输入值低于 900V,考虑地域气温问 F087 PVA_VoltHigh_Fault 题,正常的开路电压设计上不应大于 850V。设计不合理需更正,禁止强行并 网。 B 路直流电压高; 请立即断开直流线路并 用万用表测量直流输入电压,确保电压 F088 PVB_VoltHigh_Fault 输入值低于...
  • Page 34 D 路直流电压高;请立即断开直流线路 并用万用表测量直流输入电压,确保电 压输入值低于 900V,考虑地域气温问 F080 PVD_VoltHigh_Fault 题,正常的开路电压设计上不应大于 850V。设计不合理需更正,禁止强行并 网。 E 路直流电压高; 请立即断开直流线路并 用万用表测量直流输入电压,确保电压 F091 PVE_VoltHigh_Fault 输入值低于 900V,考虑地域气温问题, 正常的开路电压设计上不应大于 850V。 设计不合理需更正,禁止强行并网。 并联直流电压不一致;直流输入存在并 联情况,工作模式不正确,请联系茂硕 F092 PV_Different 协助处理,并禁止使用非光伏组件以外 的输入源进行并网。 逆变 1 电流有效值高;输出过流,重启 F093 INVOCP_M1_Fault_Rms 逆变器恢复并网,如不成功请联系茂硕 协助处理。 逆变 2 电流有效值高;输出过流,重启 F094 INVOCP_M2_Fault_Rms 逆变器恢复并网,如不成功请联系茂硕 协助处理。...
  • Page 35 报警代码及显示信息 处理方法 直流 B 路绝缘阻抗故障;使用万用表、 摇表分别测量正负极对大地、支架、边 F098 PVB_ISO_Fault 框的绝缘电阻值,低于 37k 为不良,逐 段排查线路,MC4 插头,组件是否有破 损隐裂。 直流 C 路绝缘阻抗故障;使用万用表、 摇表分别测量正负极对大地、支架、边 F099 PVC_ISO_Fault 框的绝缘电阻值,低于 37k 为不良,逐 段排查线路,MC4 插头,组件是否有破 损隐裂。 直流 D 路绝缘阻抗故障;使用万用表、 摇表分别测量正负极对大地、支架、边 F100 PVD_ISO_Fault 框的绝缘电阻值,低于 37k 为不良,逐 段排查线路,MC4 插头,组件是否有破 损隐裂。 直流 E 路绝缘阻抗故障;使用万用表、 摇表分别测量正负极对大地、支架、边...
  • Page 36 排查直流线路是否存在熔短情况,并请 联系茂硕协助处理 直流 C 路过流;软件检测到过流,请排 查直流安装容量配置,如多次报警,请 F105 PVC_CurrHigh_Fault 排查直流线路是否存在熔短情况,并请 联系茂硕协助处理 报警代码及显示信息 处理方法 直流 D 路过流;软件检测到过流,请排 查直流安装容量配置,如多次报警,请 F106 PVD_CurrHigh_Fault 排查直流线路是否存在熔短情况,并请 联系茂硕协助处理 直流 E 路过流;软件检测到过流,请排 查直流安装容量配置,如多次报警,请 F107 PVE_CurrHigh_Fault 排查直流线路是否存在熔短情况,并请 联系茂硕协助处理 直流 A 路极性反接;直流输入接反,请 F108 PVAShort_Fault 立即断开直流线路并矫正接线 直流 B 路极性反接;直流输入接反,请 F109 PVBShort_Fault 立即断开直流线路并矫正接线 直流...
  • Page 37 通风情况,或者更换安装地点,避免阳 光直晒 负母线有效值高;直流存在细微反放电 F115 BusOverN_Fault 情况,请联系茂硕协助处理。 负母线有效值低;直流存在细微反放电 F116 BusLowN_Fault 情况,请联系茂硕协助处理。 正母线有效值高;直流存在细微反放电 F117 BusOverP_Fault 情况,请联系茂硕协助处理。 正母线有效值低;直流存在细微反放电 F118 BusLowP_Fault 情况,请联系茂硕协助处理。 报警代码及显示信息 处理方法 母线电压瞬时高;直流存在细微反放电 F119 BusOverFault_ISR 情况,请联系茂硕协助处理。 母线电压瞬时低;直流存在细微反放电 F120 BusUnderFault_ISR 情况,请联系茂硕协助处理。 逆变 1 一级过流;请确认是并网瞬间报 过流,还是并网运行一段时间后报过流, 查看逆变器输出交流的电压电流参数, F129 INV1_OCP_Failure 看报故障时电压电流变化是否有突变。 根据突变的相线排查线路绝缘问题,并 联系茂硕协助处理。 逆变 2 一级过流;请确认是并网瞬间报 过流,还是并网运行一段时间后报过流,...
  • Page 38 过流,还是并网运行一段时间后报过流, 查看逆变器输出交流的电压电流参数, 看报故障时电压电流变化是否有突变。 根据突变的相线排查线路绝缘问题,并 联系茂硕协助处理。 逆变 2 二级过流;请确认是并网瞬间报 过流,还是并网运行一段时间后报过流, 查看逆变器输出交流的电压电流参数, F132 INV2ABC_OCP_Failure 看报故障时电压电流变化是否有突变。 根据突变的相线排查线路绝缘问题,并 联系茂硕协助处理。 正母线硬件过压;直流存在细微反放电 F135 PBUS_Failure 情况,请联系茂硕协助处理。 负母线硬件过压;直流存在细微反放电 F136 NBUS_Failure 情况,请联系茂硕协助处理。 报警代码及显示信息 处理方法 直流 A 路硬件过流;软件检测到过流, 请排查直流安装容量配置,如多次报警, F137 BTA_OCP_Failure_Trip 请排查直流线路是否存在熔短情况,并 请联系茂硕协助处理 直流 B 路硬件过流;软件检测到过流, 请排查直流安装容量配置,如多次报警, F138 BTB_OCP_Failure_Trip 请排查直流线路是否存在熔短情况,并 请联系茂硕协助处理...
  • Page 39 请联系茂硕协助处理 直流 D 路硬件过流;软件检测到过流, 请排查直流安装容量配置,如多次报警, F140 BTD_OCP_Failure_Trip 请排查直流线路是否存在熔短情况,并 请联系茂硕协助处理 直流 E 路硬件过流;软件检测到过流, 请排查直流安装容量配置,如多次报警, F141 BTE_OCP_Failure_Trip 请排查直流线路是否存在熔短情况,并 请联系茂硕协助处理 8.产品规格 产品型号 ST40KTL-M ST50KTL-M ST60KTL-M 最大直流功率 48000W 60000W 72000W 最大输入电压 1100V 1100V 1100V 启动电压 160V 160V 160V MPPT 电压范围/额定电压 200~950V/620V 200~950V/620V 200~950V/620V 最大输入电流...
  • Page 40 最大输出电流 可调节功率因数范围 0.8 超前...0.8 滞后 0.8 超前...0.8 滞后 0.8 超前...0.8 滞后 总电流谐波失真 <2% <2% <2% 直流分量 <0.5% <0.5% <0.5% 最大效率 98.4% 98.60% 98.80% 欧洲效率 98.2% 98.30% 98.50% MPPT 效率 99.90% 99.90% 99.90% 夜间自耗电 <0.1W <0.1W <0.1W 输入反接保护,输出短路保护,输出过流保护,输出过压保护,绝缘阻抗监测,漏电流 电气保护 监测,交直流浪涌保护,防孤岛保护,过温保护,端子连接性监测,标配直流输入开关 电网连接 无变压器...
  • Page 41 保修产品仅限于以下产品: ST40KTL-M /ST50KTL-M /ST60KTL-M · 产品质保(有限责任) (适用于正常应用、安装、使用及维护的机器)。 茂硕电源承诺上述型号的产品在质保期内没有任何影响使用的缺 陷,且承诺在质保期内为上述型号的产品提供相应的质保服务,质保期 自产品出厂日期开始计算,标准为 5 年免费质保。 关于茂硕电源系列逆变器,如果您有任何疑问,请致电服务热线:+ 400-756-5188。 请保留以下信息来更好地为您服务。(请注意,为更好地为您服务, 在致电前请提供以下信息): a. 逆变器型号。 b.逆变器的序列号。 c.通讯方式。 d.光伏组件的信息。 e. 经销商。 10.联系方式...
  • Page 42 茂硕电源科技股份有限公司 地址: 中国广东省深圳市南山区西丽镇松白路 1061 号茂硕科技园 营销服务中心 电话: 400-756-5188 传真: (86-755) 2765-7908 网站: www.mosopower.com 邮箱: sales.solar@mosopower.com 售后服务中心 电话: 400-756-5188 传真: (86-755) 2765-7908 邮箱: service.solar@mosopower.com...
  • Page 43 Solar Grid -tied Inverter ST40KTL-M/ ST50KTL M/ ST50KTL-M/ ST60KTL-M User Manual User Manual User Manual User Manual Version 2.0 (EN) Version 2.0 (EN)
  • Page 44 All rights to the content of this manual are owned by MOSO Power Supply Technology Co., Ltd (hereinafter “MOSO”). No part of this document can be modified, distributed, reproduced or published in any form or by any means without prior written permission from MOSO...
  • Page 45 ONTENT 1.PRODUCT INTRODUCTION..................... 1 1.1Overview ..........................1 1.2Packing list ..........................2 ........................3 AFETY INSTRUCTIONS 2.1Safety symbols and certification marks ................ 3 2.2TERMS and conditions ....................... 4 ........................5 PERATION INTERFACE 3.1operation interface diagram .................... 5 3.2Operation button and status indicator ................. 6 3.3 LCD DISPLAY INTERFACE ....................
  • Page 46 5.3eLECTRICAL CONNECTION .................... 11 5.3.2ac CONNECTION ......................13 5.3.3mONITORING DEVICE INSTALLATION ..............14 ..................... 15 ONNECT TO THE GRID AND DEBUG 7.FAULT AND ALARM TROUBLESHOOTING .............. 16 ......................40 DUCT SPECIFICATION ....................41 V INVERTER WARRANTY MANUAL...
  • Page 47: Product Introduction

    DC current from solar module to AC current, and output to the utility grid. DC current from solar module to AC current, and output to the utility grid. Models are as follows: ST40KTL-M, ST50KTL-M, ST60KTL-M Figure14 ST40KTL- -M, ST50KTL-M, ST60KTL-M...
  • Page 48: Packing List

    1. PRODUCT INTRODUCTION PRODUCT INTRODUCTION 1.2PACKING LIST The packing list of corresponding inverters are as below, when receiving inverters, please check if the The packing list of corresponding inverters are as below, when receiving inverters, please check if the accessories are complete. 1.PRODUCT INTRODUCTION PRODUCT INTRODUCTION ST40-60KTL-M packing list:...
  • Page 49: Safety Instructions

    Pair Pair OT terminal 2.SAFETY INSTRUCTIONS SAFETY INSTRUCTIONS Please read this manual carefully before use. Improper use may result in electric shock or burn hazard. Please read this manual carefully before use. Improper use may result in electric shock or burn hazard. You must follow the instructions in this manual during installation and maintenance.
  • Page 50: Terms And Conditions

    disconnected. Open the front cover of the inverter at least 5 minutes after disconnecting. TUV certificate CQC certificate 认证 CE certificate SAA certificate 表示产品已通过 CE 认证 表示产品已通过 SAA 认证 2.SAFETY INSTRUCTIONS SAFETY INSTRUCTIONS 2.2TERMS AND CONDITIONS The inverters meet the national safety standards national safety standards, ensure personal safety during use.
  • Page 51: Operation Interface

    it must be properly dissipated and beware of high-temperature burns. 14) The behavior related to this inverter requires professionals to complete. 15) When the crystal silicon module is selected, the input and output lines of the inverter don’t need to be grounded. Inverter input line needs to be grounded according to module requirements when using thin film modules.
  • Page 52: Operation Button And Status Indicator

    3.2OPERATION BUTTON AND STATUS INDICATOR There are four operation buttons on the front panel of the inverter, and three status indicators. The green indicator on the left shows the DC input status of the inverter, the middle green indicator shows the power generation status of the inverter, and the red indicator on the right shows the alarm status of the inverter.
  • Page 53 OPERATION INTERFACE Figure16Operation procedure...
  • Page 54: Product Storage

    4.PRODUCT STORAGE The inverter needs to be stored under specific environmental conditions: The inverter needs to be repackaged in the original box.  The box needs to be sealed with tape.  The inverter needs to be stored in a clean and dry place and protected from dust and moisture. ...
  • Page 55: Inverter Installation

    During the operation of the inverter, there will be some noise from the inductors and the fans. The  installation place cannot be close to the rest place of the residents. 5.PRODUCT INSTALLATION 5.2INVERTER INSTALLATION When installing multiple inverters at the same time, there should be enough spacing between the inverters to facilitate heat dissipation, wiring and maintenance.
  • Page 56 Figure 18 Multiple cross Multiple cross-type installation 5.PRODUCT INSTALLATION PRODUCT INSTALLATION The inverter will be mounted on the wall or metal bracket through the backing plate in the mounted on the wall or metal bracket through the backing plate in the accessory.
  • Page 57: Electrical Connection

    Figure20 ST40/50/60KT 50/60KTL-M Backing plate diagram 5.PRODUCT INSTALLATION PRODUCT INSTALLATION 5.3ELECTRICAL CONNECTION The inverter is designed with a quick connection terminal interface and does not require opening designed with a quick connection terminal interface and does not require opening the upper cover for electrical connection. The identification of the bottom of the corresponding inverter the upper cover for electrical connection.
  • Page 58 L3(T) Positive pole ositive pole wiring port Neutral line Neutral line wiring port Grounding wiring port Grounding wiring port 5.3.1 DC terminal connection 1) The plug and core of MC4plug must be in one in one-to-one correspondence, as shown in the figure below.
  • Page 59: 2Ac Connection

    Figure Make MC4 DC terminal 5.PRODUCT INSTALLATION 5.3.2 AC CONNECTION ST40/50/60KTL-M AC connection diagram: After the AC cable is crimped to the copper terminal, it is directly locked to the internal PCB of the inverter through screws. The grounding position of the chassis is located on the lower right side of the inverter.
  • Page 60: 3Monitoring Device Installation

    Figure23 ST40/50/60KTL 40/50/60KTL-M AC connection diagram Copper wire Copper wire diameter comparison Model ZRC-YJV-3* three phase+PE ST40/50/60KTL-M ZRC-YJV-3*25mm2+16mm2; Note: The neutral wire of inverter AC side doesn’need to be connected need to be connected. The conventional ground wire is half of the positive wire diameter. The neutral wire is the same as the wire diameter.
  • Page 61: Connect To The Grid And Debug

    Multiple inverter monitoring can realize daisy-chain communication connection through RS485 communication cable. The system diagram is as follows: Inverter1 Inverter Inverter WIFI module GPRS module Other monitoring system Figure25RS485 Serial communication monitoring 6.CONNECT TO THE GRID AND DEBUG Before connecting to the grid connection, the system design, configuration and installation of this product application should consider the contents mentioned in Clause 2.2 and Clause 5 of this manual.
  • Page 62: Fault And Alarm Troubleshooting

    Inverter grid-connecting process includes: power on-wait--self test--connected to grid; the corresponding indicator light flashes during the self-test and the internal relay will make a sound at the same at the same time. After the inverter connecting to the grid, the system operator should check the input parameters and output parameters of the inverter.
  • Page 63 The grid voltage had “Low voltage ride through” W003 LVRT_Fault_Warning ever. The fan is abnormal, check whether the fan is stuck with foreign objects. If the fault does not disappear W004 Fan_Fault_Warning after clear the foreign objects, please contact your supplier for help.
  • Page 64 Alarm code and display information Solution AC lightning protection action, please check whether W010 AC_Thunder_Warning there is lightning strike, contact supplier for help. W011 Smoke_Detect_Warning Please confirm if there is abnormal smoke around. Please confirm the current heat dissipation of the W012 Power_Derate_ Warning inverter, and the abnormal heat dissipation of the...
  • Page 65 The Contactorof the ground leakage current F008 GFDI_Relay_Failure detection system has failed, please contact supplier for help. DC input overvoltage causes IGBT damage, please F009 IGBT_Failure contact supplier for help. DC input overvoltage causes damage to the auxiliary power , or the DC voltage is too low to start. F010 AuxPowerBoard_Failure The auxiliary power.
  • Page 66 There is leakage current on AC side. Please use multimeter to connect to the wire A in series, check F016 GFCI_Failure the leakage current when the grid is connected, and remove the DC input string one by one to check the leakage source.
  • Page 67 insulation,false short circuit, unstable connection and contact supplier for help. Emergency stop fault.Fault occurs when press the emergency stop button, inverter will disconnect from grid and turn off DC circuit breaker; the button can F022 Tz_EmergStop_Fault only be pressed manually, androtate and bounce to rese.
  • Page 68 whether the PV module is damaged or cracked. The DC component of the inverter is abnormal. F028 DCIOver_M1_Fault Please contact supplier for help. 7.FAULT AND ALARM TROUBLESHOOTING Alarm code and display information Solution The inverter relay fails to switch on, please disconnect the AC connection.
  • Page 69 Turn off the DC power until the LCD is off, disconnect the AC connection, exchange the AC F036 AC_GridPhaseSeque_Fault wire of phase A and phase B, then restart the inverter. Please check whether the AC three-phase voltage of the inverter is consistent via LCD. If the voltage F037 AC_Volt_Unbalance_Fault difference is large, that means the three-phase load...
  • Page 70 exceed normal protection value, please check the AC output power, the output AC wire impedance, the load and underloading, contact Grid Company to handle this. Check the three-phase AC voltage, the protection range is 0.8-1.2 times of the rated AC voltage, if exceed normal protection value, please check the F042 AC_WU_UnderVolt_Fault...
  • Page 71 7.FAULT AND ALARM TROUBLESHOOTING Alarm code and display information Solution Check the three-phase AC voltage, the protection range is 0.8-1.2 times of the rated AC voltage, if exceed normal protection value, please check the F046 AC_UV_UnderVolt_Fault AC output power, the output AC wire impedance, the load and underloading, contact Grid Company to handle this.
  • Page 72 restart.Contact supplier for help. Turn off the inverter for 5min and then F054 AC_C_InductCurr_DcHigh_Fault restart.Contact supplier for help. Please disconnect the DC input immediately and measure the DC input voltage with a multimeter to ensure that the DC voltage is lower than 1000V. Considering the regional temperature problem, the F055 DC_VoltHigh_Fault...
  • Page 73 Please confirm it occurs at the moment inverter connects to the grid orafter running for a period of time. Check the voltage and current parameters of F059 AC_V_GridCurr_High_Fault the inverter AC output, and see if there is a suddenvoltage and current change when the fault occurs.
  • Page 74 Alarm code and display information Solution Please confirm it occurs at the moment inverter connects to the grid orafter running for a period of time. Check the voltage and current parameters of F063 AC_C_InductCurr_High_Fault the inverter AC output, and see if there is a suddenvoltage and current change when the fault occurs.
  • Page 75 unobstructed, and contact supplier for help. Check the temperature displayed on LCD, ensure F072 Transformer_LowTemp_Fault that the fan is working properly, the air duct is unobstructed, and contact supplier for help. 7.FAULT AND ALARM TROUBLESHOOTING Alarm code and display information Solution There is leakage current on AC side.
  • Page 76 ever. DC lightning protection action, please check F077 DC_Thunder_Fault whether there is lightning strike, contact supplier for help. AC lightning protection action, please check whether F078 AC_Thunder_Fault there is lightning strike, contact supplier for help. F079 ENV_OverTemp_Fault Ambient temperature too high. F080 ENV_UnderTemp_Fault Ambient temperature too low.
  • Page 77 Check the three-phase AC voltage, the protection range is 0.8-1.2 times of the rated AC voltage, if exceed normal protection value, please check the F083 AC_V_OverVolt_Fault AC output power, the output AC wire impedance, the load and underloading, contact Grid Company to handle this.
  • Page 78 Please disconnect the DC input immediately and measure the DC input voltage of input B with a multimeter to ensure that the DC voltage is lower than 1000V. Considering the regional temperature F088 PVB_VoltHigh_Fault problem, the normal open circuit voltage should not be designed to be greater than 920V.
  • Page 79 ensure that the DC voltage of input E is lower than 1000V. Considering the regional temperature problem, the normal open circuit voltage should not be designed to be greater than 920V. The design is unreasonable and needs to be corrected. It is forbidden to force to connect to the grid.
  • Page 80 Use multimeter and tramegger to measure the insulation resistance value( input B) of the positive and negative poles to the earth, bracket and frame F098 PVB_ISO_Fault respectively. If it is under 37k, which means abnormal, check the wire connection, MC4 plug, whether the PV module is damaged or cracked.
  • Page 81 DC PV module capacity configuration. If there are multiple alarms, please check if there is a short circuit on the DC input A, and contact supplier for help. Software detects overcurrent. Please check the DC PV module capacity configuration. If there are F104 PVB_CurrHigh_Fault multiple alarms, please check if there is a short...
  • Page 82 multiple alarms, please check if there is a short circuit on the DC input D, and contact supplier for help. Software detects overcurrent. Please check the DC PV module capacity configuration. If there are F107 PVE_CurrHigh_Fault multiple alarms, please check if there is a short circuit on the DC input E, and contact supplier for help.
  • Page 83 avoid direct sunlight. There is a slight back discharge in DC, please F115 BusOverN_Fault contact supplier for help. There is a slight back discharge in DC, please F116 BusLowN_Fault contact supplier for help. There is a slight back discharge in DC, please F117 BusOverP_Fault contact supplier for help.
  • Page 84 Please confirm it occurs at the moment inverter connects to the grid orafter running for a period of time. Check the voltage and current parameters of F130 INV2_OCP_Failure the inverter AC output, and see if there is a suddenvoltage and current change when the fault occurs.
  • Page 85 Software detects overcurrent. Please check the DC PV module capacity configuration. If there are F137 BTA_OCP_Failure_Trip multiple alarms, please check if there is a short circuit on the DC input A, and contact supplier for help. Software detects overcurrent. Please check the DC PV module capacity configuration.
  • Page 86: Product Specification

    8.PRODUCT SPECIFICATION Model ST40KTL-M ST50KTL-M ST60KTL-M Max input power 48KW 50KW 60KW Max input voltage 1100V 1100V 1100V Start up voltage 160V 160V 160V MPPT voltage range /Rated 200~950V/620V 200~950V/620V 200~950V/620V voltage Max input current 36A+36A 36A+36A+36A 36A+36A+36A Number of MPPT...
  • Page 87: Inverter Warranty Manual

    LCD display,RS485(Standard 2pin plug and play terminal),WiFi/GPRS(Optional) communication 9.SOLAR INVERTER WARRANTY MANUAL MOSO offers 5-year warranty starting from the inverters delivering from the manufacturer’s warehouse. Warranty certificate represents a five year warranty service for mentioned products since the date of purchase.
  • Page 88 Below information is asked when claiming for warranty. a. Inverter’s Model. b. Inverter’s Serial No. c. Communication Method. d. PV Modules’ Model.