3. Wiring
WIRING
PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING
PRECAUTIONS
• When drilling screw holes or wiring, make sure cutting or wire debris does
not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent any
damage to the machinery or accidents due to abnormal data written to the
PLC under the influence of noise:
1) Do not bundle the power line or shield of the analog input/output cable
together with or lay it close to the main circuit, high-voltage line, or load
line.
Otherwise, noise disturbance and/or surge induction are likely to take
place. As a guideline, lay the control line at least 100mm (3.94") or more
away from the main circuit ,high-voltage line, or load line.
2) Ground the shield of the analog input/output cable at one point on the
signal receiving side. However, do not use common grounding with heavy
electrical systems.
• Make sure to properly wire to the terminal block (European type) in
accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit,
wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions
described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires
of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected
parts are directly stressed.
• Make sure to properly wire the terminal block in accordance with the
following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit,
wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions
described in the manual of the PLC main unit.
- Tightening torque should follow the specifications in the manual of the
PLC main unit.
3.1 Applicable Cable and Terminal Tightening Torque
3.1.1
Terminal block (European type)
1) Wire size
Wiring to analog device should use 20-22 AWG wire.
2) Applicable cable
Type
Wire size
Single-wire
2
2
0.3 mm
to 0.5 mm
(AWG22 to 20)
2-wire
2 pieces of 0.3 mm
2
(AWG22)
3) Termination of cable end
Strip the coating of strand wire and twist the cable core before connecting it,
or strip the coating of single wire before connecting it.
An alternative connection is to use a ferrule with insulating sleeve.
<Reference>
Manufacturer
Model
Caulking tool
CRIMPFOX 6
Phoenix Contact Co., Ltd.
AI 0.5-8WH
(or CRIMPFOX 6T-F
*1 Old model name: CRIMPFOX ZA 3
*2 Old model name: CRIMPFOX UD 6
- Stick terminal with insulating sleeve
- Strand wire/single wire
Contact area
Insulation sleeve
(Crimp area)
9mm
(0.35")
2.6mm(0.1")
14mm(0.55")
When using a stick terminal with insulating sleeve, choose a wire with proper
cable sheath referring to the above outside dimensions, or otherwise, the wire
cannot be inserted easily.
The tightening torque must be 0.22 to 0.25 N
m. Do not tighten terminal
screws with a torque outside the above-mentioned range. Failure to do so may
cause equipment failures or malfunctions.
3.2 Power Supply Wiring
For the power supply wiring, refer to the following manual.
→ FX
FX
FX
/FX
/FX
Series User's Manual - Analog Control Edition
3S/
3G/
3GC
3U
3UC
3.3 Wiring of Analog Input
→ For the terminal configuration, refer to Section 1.2
Using current
4AD-ADP
Terminal
input
block
*1
V +
*2
250Ω
I +
COM
Using voltage input
*1
V +
250Ω
I +
COM
External power
supply wiring
24+
24 V DC
24-
*3
Grounding
(Ground resistance: 100 Ω or less)
V +, I +, ch
:
represents the channel number.
*1 Use 2-core shielded twisted pair cable for the analog input lines, and separate
the analog input lines from other power lines or inductive lines.
*2 Make sure to short-circuit the 'V +' and 'I +' terminals when current is input.
( : input channel number)
*3 24 V DC service power supply of the FX
/FX
3S
3G
used.
3.4 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100 Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" of the
following figure.
For details, refer to the respective PLC User's manual Hardware Edition.
Other
Other
PLC
PLC
equipment
equipment
Independent grounding
Shared grounding
Best condition
Good condition
• The grounding wire size should be AWG 22-20 (0.3-0.5 mm
• The grounding point should be close to the PLC, and all grounding wire should be
as short as possible.
4. Specifications
STARTUP AND
MAINTENANCE
PRECAUTIONS
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric representative.
• Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
*1
• Please contact a certified electronic waste disposal company for the
*2
)
environmentally safe recycling and disposal of your device.
TRANSPORTATION AND
STORAGE PRECAUTIONS
• The product is a precision instrument. During transportation, avoid impacts larger
than those specified in the general specifications by using dedicated packaging
boxes and shock-absorbing palettes. Failure to do so may cause failures in the
product. After transportation, verify operation of the product and check for damage
8mm
of the mounting part, etc.
(0.31")
4.1 Applicable PLC
Model name
FX
3S
Series PLC
Ver. 1.00 or later (from first production)
FX
Series PLC
Ver. 1.00 or later (from first production)
3G
FX
Series PLC Ver. 1.40 or later (from first production)
3GC
FX
3U
Series PLC
Ver. 2.20 or later (from first production)
147kΩ
ch
Ver. 1.20 or later (from the production manufactured in May,
FX
Series PLC
3UC
47kΩ
2004 with SER No. 45****)
The version number can be checked by monitoring D8001/D8101 as the last three
digits indicate it.
147kΩ
ch
4.2 General Specifications
Items other than the following are equivalent to the those of the PLC main unit.
47kΩ
For general specifications, refer to the respective PLC User's manual Hardware
Edition.
+15V
Item
Dielectric withstand
500 V AC for one minute
voltage
5 MΩ or higher by 500 V DC
Insulation resistance
insulation resistance tester
4.3 Power Supply Specifications
Item
A/D conversion
24 V DC +20 %/-15 %, 40 mA for 24 V DC
circuit driving power
Connect a 24 V DC power supply to the terminal block.
/FX
Series PLC can also be
3U
5 V DC, 15 mA
Interface driving
5 V DC power is supplied from the internal power supply of
power
main unit.
4.4 Performance Specifications
Item
Voltage input
Analog input
0 to 10 V DC
range
(Input resistance: 194 kΩ)
Other
PLC
equipment
Maximum
-0.5 V, +15 V
absolute input
Digital output
12 bits, binary
Common grounding
Not allowed
Resolution
2.5 mV (10 V/4000)
2
).
• ±0.5 % (±50 mV) for full scale
of 10 V (when ambient
temperature is 25 °C±5 °C)
Total accuracy
• ±1.0 % (±100 mV) for full
scale of 10 V (when ambient
temperature is 0 °C to 55 °C)
• FX
/FX
3U
(The data will be updated at every scan time of the PLC.)
A/D conversion
time
• FX
/FX
3S
(The data will be updated at every scan time of the PLC.)
4080
4000
Input
characteristics
0
Analog input
• The photocoupler is adopted to insulate the analog input area
from the PLC.
Insulation
• The DC/DC converter is adopted to insulate the power supply
method
line from the analog input area.
• Channels are not insulated from each other.
Occupied
0 point (This number is not related to the maximum number of
points
input/output points of the PLC.)
「电器电子产品有害物质限制使用标识要求」的表示方式
Applicability
含有有害6物质的名称, 含有量, 含有部品
  本产品中所含有的有害6 物质的名称, 含有量, 含有部品如下表
所示。
部件名称
可编程
Specification
控制器
Between all terminals and
本表格依据SJ/T 11364的规定编制。
ground terminal of PLC
main unit
○ :表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572
规定的限量要求以下。
×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T
26572规定的限量要求。
Specification
基于中国标准法的参考规格:GB/T15969.2
Description
Current input
4 to 20 mA DC
(Input resistance: 250 Ω)
-2 mA, +30 mA
11 bits, binary
10 µA (16 mA/1600)
• ±0.5 % (±80 µA) for full scale
of 16 mA (when ambient
temperature is 25 °C±5 °C)
• ±1.0 % (±160 µA) for full scale
of 16 mA (when ambient
temperature is 0 °C to 55 °C)
Series PLC: 200 µs
3UC
/FX
Series PLC: 250 µs
3G
3GC
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
1640
occur as a result of using the contents noted in this manual.
1600
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
0
4mA
20mA
20.4
10V
10.2V
mA
(3) Special damages and secondary damages whether foreseeable or not, compensation for
Analog input
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Note: This symbol mark is for China only.
产品中有害物质的名称及含量
有害物质
多溴
六价铬
多溴联苯
二苯醚
(Pb)
(Hg)
(Cd)
(Cr(VI))
(PBB)
(PBDE)
外壳
印刷基板
×
For safe use

Advertisement

loading

This manual is also suitable for:

Melsec-f fx3u series