Flow monitoring immersion sensor without integrated processor

Advertisement

Quick Links

Flow monitoring
Immersion sensor without integrated processor
FCS-GL1/2A4-NAEX0
Type code
Ident no.
Mounting conditions
Water Operating Range
Oil Operating Range
Stand-by time
Switch-on time
Switch-off time
Temperature jump, response time
Temperature gradient
Medium temperature
Device designation
ignition protection category
PowerP
i
Internal inductances/capacitances
Ex approval acc. to conformity certificate
Protection class
Housing material
Sensor material
Max. tightening torque housing nut
Connection
Cable length
Cable cross section
Pressure resistance
Process connection
1 / 2
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com
FCS-GL1/2A4-NAEX0
6870469
insertion style sensor
1...100cm/s
3...200 cm/s
typ. 8 s (2...15 s)
typ. 2 s (1...13 s)
typ. 2 s (1...15 s)
max. 12 s
ð 250 K/min
-20...60 °C
É II 1/2 G EEx ia IIC T6
Ex ia IIC
ð 0.69 W
negligibly small
TÜV 99 ATEX 1517X
IP67
Stainless steel, V4A (1.4571)
stainless steel, AISI 316Ti
30 Nm
PUR cable
2 m
4 x 0.25 mm
2
60 bar
G ½" long
ATEX category II 1/2 G, Ex zone 0
Intrinsically safe flow sensor for liquid
media
Calorimetric principle
Adjustment via potentiometer at Ex sig-
nal processor
Status indicated via LED chain on sig-
nal processor
Intrinsically safe EEx ia IIC T6, for use
in zone 0
Cable device
4-wire connection to an Ex0 processor
Wiring Diagram
Functional principle
Our insertion - flow sensors operate on the
principle of thermodynamics. The measur-
ing probe is heated by several °C as against
the flow medium. When fluid moves along the
probe, the heat generated in the probe is dis-
sipated. The resulting temperature is mea-
sured and compared to the medium tempera-
ture. The flow status of every medium can be
derived from the evaluated temperature differ-
ence. Thus TURCK's wear-free flow sensors
reliably monitor the flow of gaseous and liquid
media.

Advertisement

loading

Summary of Contents for turck FCS-GL1/2A4-NAEX0

  • Page 1 4 x 0.25 mm Pressure resistance 60 bar Process connection G ½" long 1 / 2 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com...
  • Page 2 Repairs are not possible. The approval expires if the device is repaired or modified by a person other than the manufacturer. The most important data from the approval are listed. 2 / 2 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com...