Installation manual

Advertisement

Table of Contents
loading

Summary of Contents for SMAY WKP-P

  • Page 1 WKP-P Installation manual Rectangular fire damper https: www.smay.eu...
  • Page 2: Table Of Contents

    Installation manual WKP-P Version 6.00 SMAY reserves the right to make changes to this document. TABLE OF CONTENT INSTALLATION TECHNOLOGY ..................2 INSTALATION TECHNOLOGY – RIGID WALL ............3 INSTALLATION TECHNOLOGY – STRUCTURES THICKER THAN 125 MM ..... 7 III.
  • Page 3: Installation Technology

    Before installing the fire dampers, make sure that there are no damage, during transport or storage, that could block the baffle. Check that the baffle can be opened and closed (full opening and closing position). To open fire dampers WKP-p use the actuator key.
  • Page 4: Instalation Technology - Rigid Wall

    Rigid wall Figure 1. Dimensions of the installation opening of the WKP-P dampers in rigid wall with a horizontal and with vertical axis of rotation of the baffle. The C dimension is given in the table. N – number of blades in damper Version: 6.00...
  • Page 5 WKP-P Figure 2. Installing method of WKP-P fire dampers in rigid wall, baffle axis should be in line with wall axis Figure 3. Installing method of WKP-P fire dampers in rigid wall, baffle axis should be in line with wall axis Version: 6.00...
  • Page 6 Installation manual WKP-P Figure 4. Installing method of WKP-P fire dampers in rigid wall Version: 6.00 Page 5 z 9 Date of editing: 16.09.2022 r.
  • Page 7 Installation manual WKP-P Figure 5.Installing method of WKP-P fire dampers with PROMAT boards duct After setting the fire damper as described, and build it in wall, duct made of PROMATECT-L500 boards with 50 mm thickness must be installed. The band around the duct must be made by PROMATECT-L500, with 50 mm thickness and 60 mm width.
  • Page 8: Installation Technology - Structures Thicker Than 125 Mm

    INSTALLATION TECHNOLOGY – STRUCTURES THICKER THAN 125 mm In rigid walls, with thickness less than or equal to 125 mm, WKP-P fire dampers are installed in this way that an axis of the fire baffle matches the axis of the wall, and ensure a concentricity of fire damper and installation opening.
  • Page 9 Installation manual WKP-P Figure 7. Installation method of fire dampers WKP-P in flexible wall with 125 mm thick Figure 8. Installation method of fire dampers WKP-P in flexible wall Version: 6.00 Page 8 z 9 Date of editing: 16.09.2022 r.
  • Page 10: Installation Technology - Mkw Honeycomb Mesh Cover

    Installation manual WKP-P INSTALLATION TECHNOLOGY – MKW HONEYCOMB MESH COVER Before installing honeycomb mesh cover, it is necessary to stick 5x10 self-adhesive ceramic gasket, on inside surface of mesh cover, along the deflection, around the perimeter. Honeycomb mesh cover install to the wall with use metal pins for gas-concrete 6x32 and with use 5x40 screws.