Download Print this page
Leviton Decora ODS10-IDx Installation Instructions

Leviton Decora ODS10-IDx Installation Instructions

Designer wall switch occupancy sensor

Advertisement

Quick Links

C O L L E C T I O N B Y L E V I T O N
Designer Wall Switch
Occupancy Sensor
S
ingle Pole (One Location)
or Multi-Location
Rated: 120/277V, 60Hz
Cat. No. ODS1Ø-IDx
Incandescent
800W - 6.67A @ 120V
Fluorescent
1200VA - 10A @ 120V
2700VA - 10A @ 277V
Supplemental
1/4hp - 5.8A @ 120V
No Minimum Load Required
Compatible with electronic and magnetic ballasts,
electronic and magnetic low-voltage ballasts,
incandescent lamps, and fans.
Installation Instructions
DI-000-ODS10-02A
LIMITED FIVE YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for
the benefit of anyone else that this product at the time of its sale
by Leviton is free of defects in materials and workmanship under
normal and proper use for five years from the purchase date.
Leviton's only obligation is to correct such defects by repair or
replacement, at its option, if within such five year period the
product is returned prepaid, with proof of purchase date, and a
description of the problem to Leviton Manufacturing Co., Inc.,
Att: Quality Assurance Department, 59-25 Little Neck
Parkway, Little Neck, New York 11362-2591. (In Canada send
to Leviton Mfg. of Canada Ltd., 165 Hymus Blvd., Point
Claire, (Quebec), Canada, H9R 1E9). This warranty excludes
and there is disclaimed liability for labor for removal of this
product or reinstallation. This warranty is void if this product is
installed improperly or in an improper environment, overloaded,
misused, opened, abused, or altered in any manner, or is not
used under normal operating conditions or not in accordance
with any labels or instructions. There are no other or implied
warranties of any kind, including merchantability and fitness for
a particular purpose, but if any implied warranty is required by
the applicable jurisdiction, the duration of any such implied
warranty, including merchantability and fitness for a particular
purpose, is limited to five years. Leviton is not liable for incidental,
indirect, special, or consequential damages, including without
limitation, damage to, or loss of use of, any equipment, lost sales
or profits or delay or failure to perform this warranty obligation.
The remedies provided herein are the exclusive remedies under
this warranty, whether based on contract, tort or otherwise.
For Technical Assistance Call:
1-800-824-3005 (U.S.A. Only)
1 800 405-5320 (Canada Only)
www.leviton.com
DI-000-ODS10-02A
• Leviton's Decora
®
style design
• Switches electronic ballasts
• Low Profile, tamper-resistant lens
• Ambient Light Override
Leviton Cat. No. ODS1Ø-IDx, Designer Wall Switch Occupancy Sensor, is designed to detect motion from a heat-emitting
source (such as a person entering a room) within its field-of-view (monitored space) and automatically switch lights ON
and OFF. The controlled lights will remain ON until no motion is detected and the scheduled time-delay has expired.
Cat. No. ODS1Ø-IDx is UL listed, CSA certified and conforms to California Title 24 requirements.
The Occupancy Sensor senses motion within its coverage area of 2400 sq. ft. (223.3 m
connected lighting. This is a self-contained device which provides sensing and light control. The Occupancy Sensor will
turn the lights ON when motion is initially detected, and keep the lights ON for as long as motion is detected.
The Occupancy Sensor uses a small semiconductor heat detector that resides behind a multi-zone optical lens. This
Fresnel lens establishes dozens of zones of detection. The sensor is sensitive to the heat emitted by the human body. In
order to trigger the sensor, the source of heat must move from one zone of detection to another. The device is most
effective in sensing motion across its field-of-view, and less effective sensing motion towards or away from its field-of-
view (refer to figures 1 and 1A). Keep this in mind when selecting the installation location (refer to figures 1 and 1A).
Note that occupancy sensors respond to rapid changes in temperature, so care should be taken not to mount the device
near a climate control source (i.e. radiators, air exchanges, and air conditioners). Hot or cold drafts will look like body
motion to the device and will trigger it if the unit is mounted too close. It is recommended to mount the Occupancy
Sensor at least 6 ft. away from then climate control source. The device can be mounted in a single gang wallbox.
In addition, it is also recommended NOT to mount the Occupancy Sensor directly under a large light source. Large
wattage bulbs (greater than 100W incandescent) give off a lot of heat and switching the bulb causes a temperature
change that can be detected by the device. Mount the Occupancy Sensor at least 6 ft. away from large bulbs. If it
necessary to mount the device closer, lower the wattage of the bulb directly overhead.
FCC COMPLIANCE STATEMENT
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device
must not cause harmful interference, and (2) This device must accept any interference received, including interference
that may cause undesired operation.
INSTALLATION INSTRUCTIONS
WARNING:
TO BE INSTALLED AND/OR USED IN ACCORDANCE WITH APPROPRIATE ELECTRICAL CODES AND
REGULATIONS.
WARNING:
IF YOU ARE NOT SURE ABOUT ANY PART OF THESE INSTRUCTIONS, CONSULT A QUALIFIED
ELECTRICIAN.
WARNING:
CONTROLLING A LOAD IN EXCESS OF THE SPECIFIED RATINGS WILL DAMAGE THE UNIT AND
POSE RISK OF FIRE, ELECTRIC SHOCK, PERSONAL INJURY OR DEATH. CHECK YOUR LOAD RATINGS TO
DETERMINE SUITABILITY FOR YOUR APPLICATION.
WARNING:
DO NOT INSTALL THIS UNIT TO CONTROL A RECEPTACLE.
OTHER CAUTIONS AND NOTES:
1. DISCONNECT POWER WHEN SERVICING FIXTURE OR CHANGING BULBS.
2. USE THIS DEVICE WITH COPPER OR COPPER CLAD WIRE ONLY. WITH ALUMINUM WIRE, USE
DEVICES MARKED CO/ALR OR CU/AL ONLY.
3. DO NOT TOUCH THE SURFACE OF THE LENS. CLEAN OUTER SURFACE WITH A DAMP CLOTH ONLY.
4. THE CAT. NO. ODS1Ø-IDx OCCUPANCY SENSOR IS INTENDED TO REPLACE A STANDARD LIGHT SWITCH.
TO INSTALL:
NOTE: Cat. No. ODS1Ø-IDx requires a ground connection in order to operate. Use the ground wire in the electrical box
for ground connection. If there is no ground wire, make sure the electrical box is grounded and attach the ground wire to
the box with a screw.
1.
WARNING:
TO AVOID FIRE, SHOCK, OR DEATH: TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST
THAT THE POWER IS OFF BEFORE WIRING.
2. Connect wires per appropriate WIRING DIAGRAM as follows (refer to wiring diagrams 1 & 2): BLACK lead to LINE.
BLUE lead to LOAD. GREEN lead to GROUND. Twist strands of each lead tightly and, with circuit conductors, push
firmly into the appropriate wire connector. Screw connector on clockwise making sure that no bare wire shows below
the connector. Secure each wire connector with electrical tape.
3. Carefully position the wires into the wallbox, then mount the Sensor Unit into the wallbox.
4. Secure device using long mounting screws provided.
5. Restore power at circuit breaker or fuse.
Allow approximately thirty (30) seconds after power is supplied for warm-up. After this, the device will
NOTE:
turn the lights ON and the LED will blink.
FEATURES
INTRODUCTION
DESCRIPTION
2
) maximum and controls the
Figure 1: Field-of-View (Horizontal)
60 ft. (18.3 m)
30 ft. (9.1 m)
Figure 1A: Side (Vertical) Field-of-View
Sensor Unit
0
8.3
27 ft.
(8.2 m)
38 ft.
(11.7 m)
Figure 2: Sensor Features
Mounting Yoke
Lens
Blinders
Control Panel
Cover
Push Button
LED
Window
Bottom
Figure 2A: Control Features
Blinder
Adjustment
Levers
1
2
4
7
4
7
3
10
10
Time
Range
Light
Slash Mark
1
0

Advertisement

loading
Need help?

Need help?

Do you have a question about the Decora ODS10-IDx and is the answer not in the manual?

Questions and answers

Summary of Contents for Leviton Decora ODS10-IDx

  • Page 1 Occupancy Sensor ingle Pole (One Location) Leviton Cat. No. ODS1Ø-IDx, Designer Wall Switch Occupancy Sensor, is designed to detect motion from a heat-emitting or Multi-Location source (such as a person entering a room) within its field-of-view (monitored space) and automatically switch lights ON and OFF.
  • Page 2 TO OPERATE PUSH-BUTTON: Cat. No. ODS10-IDx has a push-button switch that will toggle the lights (refer to figure 2). If the lights are OFF, the lights will turn ON when the button is pressed, and remain ON in the presence of motion. In the absence of motion, the Sensor Unit will time-out and turn the lights OFF.
  • Page 3 Cat. No. 8.5¨ Front Panel Cat. No. Front Panel Front Panel Cat. No. Fold Line Panel Line Cat. No. LEVITON INSTRUCTION SHEET/MANUAL SPECIFICATIONS DI-000-ODS10-02A Black Helvetica 50 Lb. offset Paper size: 11.5" x 8.5" Overall size: 2.875" x 4.25" Final fold size:...