Figure 10-18 External Pso Receiver; Figure 10-19 Pso Codes - Siemens GCP5000 Instruction & Installation Manual

Grade crossing predictor for electrified territory (gce)
Table of Contents

Advertisement

MENU MAPS
_________________________________________________________________________________________________________
When the PSO 1 RX1 Wrap Used is set to Yes, the PSO 1 RX1 Wrap is available in the System
Inputs and can be assigned to a vital input or set via internal logic. The Wrap Pickup Delay
described in Section 5 will be applied to the input.
An external track circuit can be used in place of the internal PSO by setting RX1 Used to
External as shown in Figure 10-18.
10.1.3.4 PSO 'N' Rx1 and 2 Codes
Figure 10-19 PSO Codes shows the PSO Receiver Code menu for Receiver 1 (Receiver 2 is
similar). This is used to select which code the receiver can accept. This menu is only available
when the internal PSO receiver is used.
Rx1 Code A Valid: range Yes, No, default Yes
RX1 Code A Drop Delay: range 0 – 99 sec, default 0 sec
Rx1 Code C Valid: range Yes, No, default No
RX1 Code C Drop Delay: range 0 – 99 sec, default 0 sec
Rx1 Code D Valid: range Yes, No, default No
RX1 Code D Drop Delay: range 0 – 99 sec, default 0 sec
Rx1 Code E Valid: range Yes, No, default No
RX1 Code E Drop Delay: range 0 – 99 sec, default 0 sec
Rx1 Code F Valid: range Yes, No, default No
RX1 Code F Drop Delay: range 0 – 99 sec, default 0 sec
SIG-00-22-02
Version: B.1

Figure 10-18 External PSO Receiver

10-22
JUNE 2022 (Revised September 2022)