ADDRESSING THE FANS USING
EC CONTROL SOFTWARE
This documents implements the following settings:
Indoor Fans
Outdoor Fans
* For Indoor Fans, 2590-011 / 2590-014 / 2590-019 may be used, check actual motor installed.
• 2590-011 fans uses 2591-011-XXX.
• both 2590-014 and 2590-019 fans uses 2591-014-XXX .
Copyright © 2016
All rights reserve. This manual is a controlled document which contains confidential and proprietary information. No part or contents of this book maybe
reproduced or transmitted in any form or by any means without the written permission of Actron Engineering Pty. Ltd.
Fan Number
1
2
3
4
Fan Number
1
2
3
4
HERCULES UNIT
PKV1400 / PKV2000
2591-xxx-101*
2591-xxx-201*
2591-xxx-301*
2591-xxx-401*
PKV1400 / PKV2000
2506-138-101
2506-138-201
2506-138-301
2506-138-401
REVISION 5.0
220201

Advertisement

loading
Need help?

Need help?

Do you have a question about the HERCULES PKV1400 and is the answer not in the manual?

Questions and answers

Summary of Contents for actionair HERCULES PKV1400

  • Page 1 HERCULES UNIT ADDRESSING THE FANS USING EC CONTROL SOFTWARE REVISION 5.0 220201 This documents implements the following settings: Fan Number PKV1400 / PKV2000 2591-xxx-101* Indoor Fans 2591-xxx-201* 2591-xxx-301* 2591-xxx-401* Fan Number PKV1400 / PKV2000 2506-138-101 Outdoor Fans 2506-138-201 2506-138-301 2506-138-401 * For Indoor Fans, 2590-011 / 2590-014 / 2590-019 may be used, check actual motor installed.
  • Page 2: Table Of Contents

    ADDRESSING THE FANS USING EC CONTROL SOFTWARE TABLE OF CONTENTS 1.0 Safety Precautions ................4 2.0 Background ..................4 3.0 Tools and Accessories ..............4 4.0 EBM EC-Control Software .............. 4 5.0 Indoor Fans Addresses ..............22 6.0 Outdoor Fans Addresses .............. 22 ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
  • Page 3: Safety Precautions

    ADDRESSING THE FANS USING EC CONTROL SOFTWARE 1.0 SAFETY PRECAUTIONS • Only licensed HVAC technicians* should install and service this air conditioning equipment. Improper service or alteration by an unqualified technician could result in significant and major damage to the product or property which may render your warranty null and void.
  • Page 4: Background

    ADDRESSING THE FANS USING EC CONTROL SOFTWARE 2.0 BACKGROUND: As situation dictates, you will be required to assign correct address to EBM EC Indoor and Outdoor Fans. The procedures described in this manual will assist you in this situation. Please read this manual thoroughly and follow the procedures to correctly address the fans using the EBM EC Control software.
  • Page 5 ADDRESSING THE FANS USING EC CONTROL SOFTWARE 4.03 Disconnect the unit’s J9 FBus 1 Terminal from CM100 Controller. Disconnect J9 FBus 1 Terminal CM100 J9 FBus 1 Receptacle CM100 4.04 Connect the other ends of the EBM Bus Cable between the disconnected J9 FBus 1 Terminal and the CM100 J9 FBus 1 Receptacle.
  • Page 6 ADDRESSING THE FANS USING EC CONTROL SOFTWARE 4.05 Open the EC Control Application on the desktop. (If not on desktop, the application can be found at the location you specified during the software installation process). The following screen will be displayed: 4.06 Make sure the Fab Name is “Customer”, User name is “Administrator”...
  • Page 7 ADDRESSING THE FANS USING EC CONTROL SOFTWARE 4.07 Enter the password as “topsecret” and click on “Login”. NOTE: The password is case sensitive. The following screen will be displayed: ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Hercules Units w/ CM100- Addressing the Fans Using EC Control Software Copyright ©...
  • Page 8 ADDRESSING THE FANS USING EC CONTROL SOFTWARE 4.08 Note:- Make sure the COM port is detected correctly without any error, when in error the colour of the port setting goes red with an error message. In case of failure of communication with the interface following screen will be displayed.
  • Page 9 ADDRESSING THE FANS USING EC CONTROL SOFTWARE 4.09 Turn ON the circuit breaker for the fan you wish to program, keeping all the others OFF. 4.10 Click on “File”. 4.11 Click on “Configuration Assistant”. ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Hercules Units w/ CM100- Addressing the Fans Using EC Control Software Copyright ©...
  • Page 10 ADDRESSING THE FANS USING EC CONTROL SOFTWARE 4.12 Click on “Small Size Fab”. 4.13 Click on “I have connected single Fan” and then click “Continue”. ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Hercules Units w/ CM100- Addressing the Fans Using EC Control Software Copyright ©...
  • Page 11 ADDRESSING THE FANS USING EC CONTROL SOFTWARE 4.14 Click on “Start Search”. 4.15 When the search is complete, the fan you wish to program will be displayed. Check whether the type is displayed as “MODBUS-ebm papst”. Then click on “Continue”. ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
  • Page 12 ADDRESSING THE FANS USING EC CONTROL SOFTWARE 4.16 The following screen will be displayed. Click on “Save”. 4.17 The following screen will be displayed. Click on “Finish”. ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Hercules Units w/ CM100- Addressing the Fans Using EC Control Software Copyright ©...
  • Page 13 ADDRESSING THE FANS USING EC CONTROL SOFTWARE The following screen will be displayed and the configuration data will start loading: 4.18 After the config data is loaded the following screen is displayed with “My Fab” in green. Click on the dropdown “ ”...
  • Page 14 ADDRESSING THE FANS USING EC CONTROL SOFTWARE 4.19 The following screen will be displayed. Right click on the fan showing “MODBUS1_1”. The following screen will be displayed: ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Hercules Units w/ CM100- Addressing the Fans Using EC Control Software Copyright ©...
  • Page 15 ADDRESSING THE FANS USING EC CONTROL SOFTWARE 4.20 Click on “Set up fan parameters”. 4.21 Following screen will be displayed. Make sure the status shows “Fan OK”. Change “Source of set value” from “Ain1” to “RS485/Bus”. ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Hercules Units w/ CM100- Addressing the Fans Using EC Control Software Copyright ©...
  • Page 16 ADDRESSING THE FANS USING EC CONTROL SOFTWARE 4.22 Click on “Parameter set 1”. 4.23 Select “Source of Parameter set switch” as “RS485/Bus” ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Hercules Units w/ CM100- Addressing the Fans Using EC Control Software Copyright ©...
  • Page 17 ADDRESSING THE FANS USING EC CONTROL SOFTWARE The following screen will be displayed: 4.24 Select “Control Mode” as “Closed Loop Speed Control”. ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Hercules Units w/ CM100- Addressing the Fans Using EC Control Software Copyright ©...
  • Page 18 ADDRESSING THE FANS USING EC CONTROL SOFTWARE 4.25 Then click on “Set” The following screen will be displayed: ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Hercules Units w/ CM100- Addressing the Fans Using EC Control Software Copyright ©...
  • Page 19 ADDRESSING THE FANS USING EC CONTROL SOFTWARE 4.26 Click on “Communication Parameters”. 4.27 Click on the number of the “Device Address”. ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Hercules Units w/ CM100- Addressing the Fans Using EC Control Software Copyright ©...
  • Page 20 ADDRESSING THE FANS USING EC CONTROL SOFTWARE 4.28 Change the address to “2”. Refer to Fans addressing chart (see page 22) and then click on “Set” to lock the fan address. The following screen will be displayed: ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Hercules Units w/ CM100- Addressing the Fans Using EC Control Software Copyright ©...
  • Page 21 ADDRESSING THE FANS USING EC CONTROL SOFTWARE 4.29 Close the window. 4.30 Switch ON the next Fan. 4.31 Follow procedures 4.10 to 4.29. 4.32 When searched for the next fan is completed, the next screen will be displayed: Note that every new fan will have an initial address as 1. 4.33 When the first two fans are configured the following screen will be displayed.
  • Page 22: Outdoor Fans Addresses

    ADDRESSING THE FANS USING EC CONTROL SOFTWARE 5.0 INDOOR FANS ADDRESSES Indoor Fans Number and Address (Front View) Fan Number Fan # 2 Fan # 1 MODBUS1_3 MODBUS1_2 Address Fan # 3 Fan # 4 MODBUS1_4 MODBUS1_5 Bottom of the Unit 6.0 OUTDOOR FANS ADDRESSES Outdoor Fans Number and Address (Top View) Fan Number...
  • Page 23 THIS PAGE IS INTENTIONALLY LEFT BLANK...