PROFINET IO
4.1
Parameters/address space
4.1.1
Parameters
The table below shows the parameters for the I/O device
DIQ 16x24VDC/0.5A/2A M12-L 8xM12.
Table 4- 1
Configurable parameters and their defaults (GSD file)
Parameters
Diagnostics: Undervoltage 1L+
Diagnostics: Missing 2L+
Diagnostics: Short-circuit
Diagnostics: Wire break detection and
alarm
Input delay
Hardware interrupt on rising edge
Hardware interrupt on falling edge
Digital inputs/outputs DIQ 16x24VDC/0.5A/2A M12-L 8xM12 (6ES7143-6BH00-0BB0)
Equipment Manual, 02/2022, A5E46571210-AC
Value range
•
Disable
•
Enable
•
Disable
•
Enable
•
Disable
•
Enable
•
Disable
•
Enable
•
0.05 ms
•
0.1 ms
•
0.4 ms
•
0.8 ms
•
1.6 ms
•
3.2 ms
•
12.8 ms
•
20 ms
•
Disable
•
Enable
•
Disable
•
Enable
Default
Scope with configuration soft-
ware, e.g. STEP 7 (TIA Portal)
Disable
Channel
Disable
Channels 4...7, 12...15
Disable
Channel
Disable
Channel
(Digital inputs)
3.2 ms
Channel
(Digital inputs)
Disable
Channel
(Digital inputs)
Disable
Channel
(Digital inputs)
4