Page 1
Ducted R410A Models Model No. Indoor Units Indoor Type Units Type 4-Way Cassette S-36PU1E5A S-45PU1E5A S-50PU1E5A S-60PU1E5A S-71PU1E5A S-100PU1E5A S-125PU1E5A S-140PU1E5A Ceiling S-36PT2E5A S-45PT2E5A S-50PT2E5A S-60PT2E5A S-71PT2E5A S-100PT2E5A S-125PT2E5A S-140PT2E5A Wall Mounted S-36PK1E5A S-45PK1E5A S-50PK1E5A S-60PK1E5A S-71PK1E5A S-100PK1E5A – –...
Page 2
Check of Density Limit The standards for minimum room volume are as follows. (1) No partition (shaded portion) The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set limit. The refrigerant (R410A), which is used in the air conditioner, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to protect the ozone layer.
Page 3
IMPORTANT INFORMATION REGARDING THE REFRIGERANT USED This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere. Refrigerant type: R410A value: 1975 GWP = global warming potential Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Please contact your local dealer for more information.
Page 49
1-2. Dimensional Data (B) Outdoor Unit: U-50PE1E5 U-60PEY1E5 / U-71PEY1E5 (97) Drain port Air intake Air intake Drain port Air discharge (161) Refrigerant tubing joint (liquid tube) Unit: mm (157) Flare connection ø6.35 mm (50) ø9.52 mm (60, 71) Refrigerant tubing joint (gas tube) Flare connection ø12.7 mm (50) ø15.88 mm (60, 71) 1-199...
Page 50
1-2. Dimensional Data (B) Outdoor Units: U-60PE1E5A / U-71PE1E5A/ U-100PEY1E5/ U-125PEY1E5 U-71PE1E8A / U-100PEY1E8/ U-125PEY1E8 Unit:mm or more or more 2-U shaped hole Air intake Space for piping,wiring and maintenance Air intake Air discharge 2-18x13 Anchor hole 68.5 Hole (Bottom) Air discharge Air intake Handle...
Page 51
1-2. Dimensional Data (B) Outdoor Units: U-100PE1E5A / U-125PE1E5A / U-140PE1E5A U-100PE1E8A / U-125PE1E8A / U-140PE1E8A / U-140PEY1E8 or more or more 2-U shaped hole Air intake Space for piping,wiring and maintenance Air intake Air discharge 2-18x13 Anchor hole 68.5 Hole (Bottom) Air intake...
Page 55
1-4. Operationg Range Type PE1 Temperature Indoor air intake temp. Outdoor air intake temp. Maximum 32°C DB / 25°C WB 46°C DB Cooling Minimum 18°C DB / 14°C WB -15°C DB Maximum 30°C DB / − WB 24°C DB/18°C WB Heating Minimum 16°C DB / −...
1-6. Noise Criterion Curves (A) Indoor Units High Low Silhouette Ducted Type : S-36PF1E5A : S-45PF1E5A MODEL MODEL : High 33 dB(A) : High 33 dB(A) SOUND LEVEL SOUND LEVEL 25 dB(A) 25 dB(A) : Under the unit 1.5m CONDITION CONDITION : Under the unit 1.5m SOURCE...
Page 68
1-6. Noise Criterion Curves (A) Indoor Units High Low Silhouette Ducted Type : S-100PF1E5A : S-125PF1E5A MODEL MODEL : High 38 dB(A) : High 39 dB(A) SOUND LEVEL SOUND LEVEL 31 dB(A) 32 dB(A) : Under the unit 1.5m CONDITION CONDITION : Under the unit 1.5m SOURCE...
Page 69
1-6. Noise Criterion Curves (A) Indoor Units High Ducted Type MODEL : S-36PN1E5A MODEL : S-45PN1E5A S-50PN1E5A SOUND LEVEL SOUND LEVEL : HIGH 40 dB(A) : HIGH 41 dB(A) 35 dB(A) 35 dB(A) CONDITION CONDITION : Under the unit 1.5m : Under the unit 1.5m SOURCE SOURCE...
Page 70
1-6. Noise Criterion Curves (B) Outdoor Unit : U-50PE1E5 : U-50PE1E5 MODEL MODEL SOUND LEVEL : Cooling 46 dB(A) SOUND LEVEL : Heating 50 dB(A) : 1 m in front at height of 1.5 m : 1 m in front at height of 1.5 m CONDITION CONDITION : 220-230-240V, 1 phase, 50Hz...
Page 71
1-6. Noise Criterion Curves (B) Outdoor Unit : U-60PE1E5A : U-60PE1E5A MODEL MODEL SOUND LEVEL : Cooling 48 dB(A) SOUND LEVEL : Heating 50 dB(A) : 1 m in front at height of 1.5 m : 1 m in front at height of 1.5 m CONDITION CONDITION : 220-230-240V, 1 phase, 50Hz...
Page 72
1-6. Noise Criterion Curves (B) Outdoor Unit : U-100PE1E5A, U-100PE1E8A : U-100PE1E5A, U-100PE1E8A MODEL MODEL SOUND LEVEL : Cooling 52 dB(A) SOUND LEVEL : Heating 52 dB(A) : 1 m in front at height of 1.5 m : 1 m in front at height of 1.5 m CONDITION CONDITION 1 phase model...
Page 73
1-6. Noise Criterion Curves (B) Outdoor Unit : U-140PE1E5A, U-140PE1E8A : U-140PE1E5A, U-140PE1E8A MODEL MODEL SOUND LEVEL : Cooling 54 dB(A) SOUND LEVEL : Heating 55 dB(A) : 1 m in front at height of 1.5 m : 1 m in front at height of 1.5 m CONDITION CONDITION 1 phase model...
Page 74
1-6. Noise Criterion Curves (B) Outdoor Unit MODEL : U-60PEY1E5 MODEL : U-60PEY1E5 : Cooling 46 dB(A) : Heating 50 dB(A) SOUND LEVEL SOUND LEVEL : 1 m in front at height of 1.5 m : 1 m in front at height of 1.5 m CONDITION CONDITION SOURCE...
Page 75
1-6. Noise Criterion Curves (B) Outdoor Unit : U-100PEY1E5, U-100PEY1E8 : U-100PEY1E5, U-100PEY1E8 MODEL MODEL SOUND LEVEL : Cooling 54 dB(A) SOUND LEVEL : Heating 54 dB(A) : 1 m in front at height of 1.5 m : 1 m in front at height of 1.5 m CONDITION CONDITION 1 phase model...
Page 76
1-6. Noise Criterion Curves (B) Outdoor Unit : U-140PEY1E8 MODEL : U-140PEY1E8 MODEL : Cooling 54 dB(A) SOUND LEVEL SOUND LEVEL : Heating 53 dB(A) CONDITION : 1 m in front at height of 1.5 m : 1 m in front at height of 1.5 m CONDITION SOURCE : 380-400-415V, 3 phase, 50Hz...
1-9. Fresh Air Intake 1-9-1. Precautions Regarding External Air Intake (1) Ventilation Load Ensure that the design of the air-conditioner takes air-conditioning loads into consideration when external air intake is involved. (2) Restrictions on External Air Intake Ensure that the design conforms to the restrictions on air intake volume stipulated in accordance with the model of the indoor unit and the intake method.
Page 78
1-9-2. External Air Intake Volume & Resistance Within Unit / Operation Noise Characteristics (continued) Low Silhouette Ducted (F2 Type) 1-9-2-4. In a Case of External Air Intake to Unit Directly (Using external air intake cylindrical flange) Operation noise Resistance within the unit (External air intake only) (High speed wind) External air intake cylindrical flange...
1-10. Electrical Wiring General Precautions on Wiring Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. Provide a power outlet to be used exclusively for each unit and a circuit breaker for overcurrent protection should be provided in the exclusive line.
Page 80
Wiring System Diagrams * 3-phase model connections Indoor unit (No. 1) Power supply Outdoor unit (3-phase) 220/230/240V ~50Hz INV unit Power supply Ground Remote 380/400/415V, 3 N~, 50Hz controller Ground Ground Ground Indoor unit * Single-phase model connections (No. 2) Power supply Ground Outdoor unit (single-phase)
CAUTION (1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.) For a system without link (no wiring connection between outdoor units), do not remove the short plug. (2) Do not install the inter-unit control wiring in a way that forms a loop.
Page 82
How to connect wiring to the terminal For stranded wiring Cut the wire end with cutting pliers, Stranded wire Special Screw then strip the insulation to expose washer the stranded wiring about 10 mm and Ring Ring pressure Screw and tightly twist the wire ends.
Page 83
Wiring samples K1 type T2 type Remote control wiring and inter-unit control wiring inlet port Functional ground screw (External Electronic * Insert the remote control wiring and inter- Expansion Valve Kit and Schedule Timer)* unit control wiring into the electrical Protective ground screw component box from the inlet port as Fixture screw for resin cover...
:Cooling Capacity 1-13. Capacity Table SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C...
Page 85
:Cooling Capacity 1-13. Capacity Table SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C...
Page 86
:Cooling Capacity 1-13. Capacity Table SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C...
Page 87
:Cooling Capacity 1-13. Capacity Table SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C...
Page 88
:Cooling Capacity 1-13. Capacity Table SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C...
Page 89
:Cooling Capacity 1-13. Capacity Table SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C...
Page 90
:Cooling Capacity 1-13. Capacity Table SHC :Sensible Heat Capacity 1. Cooling Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 25°C 30°C 35°C 40°C...
1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Low Sihouette Ducted Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 1.87 1.92...
Page 92
1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 220V 2.88...
Page 93
1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Single Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 1.80 1.83...
Page 94
1-13. Capacity Table :Cooling Capacity 2. Heating Capacity Performance Data IPT :Cooling Power Consumption • Combination of Multiple Unit Low Silhouette Ducted Type unit : kW Outdoor air intake temp(°C W.B.) Ambient Power Model Return -5°C 0°C 6°C 10°C 15°C Source 1.86 1.95...
Page 95
3. ELECTRICAL DATA 3-1. Indoor Units (Electric Wiring Diagram Schematic Diagram) ........3-2 4-Way Cassette Type ..........................3-2 4-Way Cassette 60 × 60 Type ......................... 3-3 Ceiling Type ............................3-4 Wall Mounted Type ..........................3-7 Low Silhouette Ducted Type ........................3-8 Ducted Type ............................