APPLICATION NOTES
17.2.1.
SETTINGS AND CONFIGURATION
The settings and configuration related to this function are described below:
1. Under I/O CONFIGURATION, Input#1 must be configured as 'General Input'. It will be used to monitor the
permanent presence of voltage.
2. Under LOGIC CONFIGURATION, LOGIC#1, Invert Input#1 and set the timer to the time delay to produce the Trip
Circuit Supervision Alarm, for example 15 seconds.
GEK-106273L
MIF Digital Feeder Protection
17-5