TECHNICAL & SERVICE MANUAL SA– 79G SA– 99G FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-79G-A 1 851 005 18 General (50Hz) & Europe SA-99G-A 1 851 005 19 SA– 79G SA– 99G 700402 REFERENCE NO.
Page 2
IMPORTANT! When Installing Place of Installation Please Read Before Starting • If possible, install the unit in a shady location. If the site This air conditioner meets strict safety and operating is exposed to the sun, you should provide a sun screen standards.
Page 3
This manual is designed to help service personnel to understand basic functions, operation and possible troubles and their remedies on SANYO window type air conditioners. You can use this manual both as a reference to find specific information about the capacity, construction of the unit, and as a source of information to help you set up and maintain the air conditioner.
2. SPECIFICATIONS 2-1. Unit Specifications Model SA– 79G Power Source 220–240V Single phase 50Hz Voltage rating 220 / 230 / 240 V Performance Cooling Capacity 2.10 2.10 2.10 BTU/h 7,200 7,200 7,200 Air circulation (High) Moisture removal (High) Liters/h Electrical Rating Cooling Available voltage range 198 ~ 264...
Page 7
Model SA– 99G Power Source 220–240V Single phase 50Hz Voltage rating 220 / 230 / 240 V Performance Cooling Capacity 2.55 2.55 2.60 BTU/h 8,700 8,700 8,900 Air circulation (High) Moisture removal (High) Liters/h Electrical Rating Cooling Available voltage range 198 ~ 264 Running amperes Power input...
2-3. Other Component Specifications Model SA – 79G SA – 99G Auto Deflector Motor MA062299 Rating AC 200/240V, 50/60Hz, 20mA, 4W, 5.0/6.0 rpm Coil resistance kΩ (at 20°C) 9.92...
3. DIMENSIONAL DATA Model SA – 79G SA – 99G Slits for ventilation Side view (L) Front view Side view (R) Power code Power code outlet outlet Unit : mm NOTE Dimension with " " mark indicates the maximum allowable wall thickness required for ventilating the unit.
6. ELECTRICAL DATA 6-1. Electrical Characteristics Model SA– 79G Fan Motor Compressor Complete Unit Performance at 220 / 240 V Single phase 50Hz Rating Conditions Running Amps. 0.38 / 0.40 3.22 / 3.00 Power Input kW 0.086 / 0.099 0.684 / 0.701 0.77 / 0.80 Full Load Conditions Running Amps.
6-2. Electrical Wiring Diagrams Model SA-79G To avoid electrical shock hazard, be sure to SA-99G disconnect power before checking, servicing WARNING and/or cleaning any electrical parts. DATA SUBJECT TO CHANGE WITHOUT NOTICE.
7. TROUBLESHOOTING 7-1. Check before and after troubleshooting WARNING Hazardous voltage can cause ELECTRIC SHOCK or DEATH. Disconnect power or turn off circuit breaker before you start checking or servicing. 7-1-1. Check power supply. Check that voltage is in specified range (±10% of the rating). Check that power is being supplied.
7-2. Air conditioner does not operate. 7-2-1. Circuit breaker trips (or fuse blows). A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.) There is a possibility of ground fault. Check insulation resistance. If resistance value is 2MΩ...
Page 19
B. Circuit breaker trips in several minutes after turning the air conditioner on. There is a possibility of short circuit. • Check capacity of circuit breaker. Replace with suitable one (larger capacity). Capacity of circuit breaker is suitable. Measure resistance of fan motor •...
7-3. Some part of air conditioner does not operate. 7-3-1. Only fan does not run. • Check fan casing Remove foreign foreign matter on matter or repair. Fan cannot inside. be turned. • Check fan rotation. Turn fan gently once or twice by hand.