Service and Troubleshooting
ANX, SSX, ASX, GSX, DSX, VSX Condensing Units,
ANZ, SSZ, ASZ, GSZ, DSZ, VSZ Split System Heat Pumps
With R-410A Refrigerant Blowers, Coils, & Accessories
Pride and workmanship go into every product to provide
our customers with quality products. It is possible, however,
that during its lifetime a product may require service.
Products should be serviced only by a qualified service
technician who is familiar with the safety procedures
required in the repair and who is equipped with the proper
tools, parts, testing instruments and the appropriate service
manual. REVIEW ALL SERVICE INFORMATION IN THE
APPROPRIATE SERVICE MANUAL BEFORE
BEGINNING REPAIRS.
Only personnel that have been trained to install, adjust,
service or repair(hereinafter, "service") the equipment
specified in this manual should service the equipment. The
manufacturer will not be responsible for any injury or
property damage arising from improper service or service
procedures. If you service this unit, you assume responsi-
bility for any injury or property damage which may re-
sult. In addition, in jurisdictions that require one or more
licenses to service the equipment specified in this manual,
only licensed personnel should servise the equipment.
Improper installation, adjustment, servicing or repair of
the equipment specified in this manual, or attempting to
install, adjust, service or repair the equipment specified in
this manual without proper training may result in product
damage, property damage, personal injury or death.
PROP 65 WARNING
FOR CALIFORNIA CONSUMERS
Cancer and Reproductive Harm -
www.P65Warnings.ca.gov
Brand
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
®
WARNING
WARNING
©2020-2021 Goodman Manufacturing Company, L.P.
For service information related to the Bluetooth® Shared
Data Loader BTSDL01 referenced in this manual, please
refer to the installation instructions for the BTSDL01 at
www.coolcloudhvac.com/loaderuserguide.
IMPORTANT INFORMATION .............................................2
PRODUCT IDENTIFICATION ............................................4
PRODUCT DESIGN .........................................................53
SYSTEM OPERATION .....................................................56
SERVICING ......................................................................66
CHECKING VOLTAGE .................................................66
CHECKING WIRING ....................................................66
CHECKING THERMOSTAT AND WIRING ..................66
THERMOSTAT WIRING ...............................................66
CIRCUIT .......................................................................67
CHECKING CONTACTOR CONTACTS .......................67
CHECKING FAN RELAY CONTACTS ..........................68
(HEAT PUMP MODELS) ..............................................69
CHECKING LOW PRESSURE CONTROL ..................69
3-WIRE MODULE ........................................................70
3-WIRE MODULE .........................................................70
CHECKING CAPACITOR .............................................76
MULTI-METER .............................................................76
0140M00517-A
(PSC MOTORS) ...........................................................77
(ECM MOTORS) ..........................................................77

TABLE OF CONTENTS

RS6200006r100
February 2021

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ANX and is the answer not in the manual?

Questions and answers

Summary of Contents for Amana ANX

  • Page 1: Table Of Contents

    Service and Troubleshooting ANX, SSX, ASX, GSX, DSX, VSX Condensing Units, ANZ, SSZ, ASZ, GSZ, DSZ, VSZ Split System Heat Pumps With R-410A Refrigerant Blowers, Coils, & Accessories Pride and workmanship go into every product to provide For service information related to the Bluetooth® Shared our customers with quality products.
  • Page 2: Important Information

    IMPORTANT INFORMATION CHECKING ECM MOTOR WINDINGS ......78 IMPORTANT NOTICES FOR CONSUMERS ECM CFM ADJUSTMENTS MBE/AEPF .....78 AND SERVICERS BLOWER PERFORMANCE DATA ......83 RECOGNIZE SAFETY SYMBOLS, WORDS AND CHECKING HIGH EFFICIENCY MOTORS ....83 LABELS EEM BLOWER REPLACEMENT .........84 MBR/AR*F ELECTRONIC BLOWER TIME DELAY RELAY ................85 CHECKING COMPRESSOR ........85 WARNING...
  • Page 3 IMPORTANT INFORMATION SAFE REFRIGERANT HANDLING WARNING While these items will not cover every concievable situation, they should serve as a usefull guide. To avoid possible explosion: • Never apply flame or steam to a refrigerant cylinder. If you must heat a cylinder for faster charging, partially immerse it in warm water.
  • Page 4: Product Identification

    NOMENCLATURE PRODUCT IDENTIFICATION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information.
  • Page 5 PRODUCT IDENTIFICATION...
  • Page 6 PRODUCT IDENTIFICATION...
  • Page 7 PRODUCT IDENTIFICATION...
  • Page 8 PRODUCT IDENTIFICATION...
  • Page 9 PRODUCT IDENTIFICATION...
  • Page 10 PRODUCT IDENTIFICATION All Airhandlers use DIRECT DRIVE MOTORS. Power supply is AC 208-240v, 60 hz, 1 phase.
  • Page 11 G S X 11 090 1 6,7,8 10,11 Brand Engineering G - Goodman brand Major/Minor Revisions A - Amana brand Type Voltage Split System 1 - 208/230V Single-Phase 60 Hz 2 - 220/240V Single-Phase 50 Hz Type 3 - 208/230V Three-Phase 60 Hz...
  • Page 12 PRODUCT IDENTIFICATION GSX11 LIGHT COMMERCIAL GOODMAN® BRAND SPLIT X-R410A CONDENSERS 11 SEER Model/Rev Description GSX11090*AA Introduction of Goodman Light Commercial 11 SEER, R-410A Condensers. GSX11120*AA GSX111203AB GSX110903AB 208-230V and 460V 3 Phase condensing units with new ball valve/brackets, suction GSX111204AB tube/assembly and panel w/offset.
  • Page 13 AMANA® BRAND SPLIT Z-R410A HEAT PUMP 13 SEER Model/Rev Description ASZ130**1AA Initial release of Amana® Brand 13 SEER Heat Pump R410A. ASZ130**1AB Introduces new revisions with improved circuiting for effective defrost. ASZ130[18, 36-60]1AB Introduces models containing crankcase heater, CCH switch and upgraded defrost ASZ130[24-30]1AC control.
  • Page 14 ASZ14 AMANA® BRAND SPLIT Z-R410A HEAT PUMP 14 SEER Model/Rev Description Initial release of Amana® Brand 14 SEER Heat Pump R410A with sound blankets and ASZ140**1AA Coresense control. ASZ140**1AB Screw locations moved in the top panel, base pans, louvers, and control box covers.
  • Page 15 Initial release of Amana® Brand 16 SEER Heat Pump models with 9.6+ HSPF ASZ160601LA Initial release of Amana® Brand 5 Ton 16 SEER, 13 eer Heat Pump models. ASZ160[24,30]1LB Motor change on 3 & 3.5T 14 SEER & 2 & 2.5T 16 SEER. Increase blade gap.
  • Page 16 AMANA® BRAND SPLIT SYSTEM N-BASE Z-R410A HEAT PUMP 13 SEER Model/Rev Description ANZ130[18-60]1AA Initial release of Amana® Brand Split System Base Heat Pump, 13 Seer R-410A units. ANZ130[18/24/30]1AB Reversing valve change from Dunan to new SanHua reversing valve ANZ130481AB Ranco 0151M00020 reversing valve changed to new SanHua 0151R00070 reversing valve ANZ130241AC Create new Motor &...
  • Page 17 PRODUCT IDENTIFICATION DSZ16 DELUXE SPLIT Z-R410A HEAT PUMP 16 SEER Model/Rev Description DSZ160**1AA Initial release of Deluxe Goodman 2-stage 16 SEER heat pumps with R-410A. DSZ160241AC Sanhua (RANCO) reversing valves. DSZ16036, 48, 60]1AB DSZ18 DELUXE SPLIT Z-R410A HEAT PUMP 18 SEER Model/Rev Description DSZ180**1AA...
  • Page 18 PRODUCT IDENTIFICATION VSZ13 VALUE SPLIT Z-R410A HEAT PUMP 13 SEER Model/Rev Description VSZ13**1AA Initial release of Value Line 13 SEER heat pumps with R-410A. VSZ130[24 & 30]1AB Improved circuiting for effective defrost. VSZ130[24 & 36]1BA Initial release of models with 5mm Smart Coil™. VSZ130[18, 42, 48]1AB VSZ130241BB Models containing crankcase heater, CCH switch and upgraded defrost control.
  • Page 19 PRODUCT IDENTIFICATION VSZ14 VALUE SPLIT Z-R410A HEAT PUMP 14 SEER Model/Rev Description VSZ14[018-060]1AA Introduction of ready 15, 14 SEER heat pumps to meet the 2015 efficiency requirement. VSZ140(18-30)1AB Energy guide update. PCBDM160 with new software. VSZ140421AB Motor change on 3 & 3.5T 14 SEER & 2 & 2.5T 16 SEER. Increase blade gap. VSZ140491AB VSZ140[18,30]1AC Refrigerant charge reduction.
  • Page 20 PRODUCT IDENTIFICATION GSZ13 GOODMAN SPLIT Z-R410A HEAT PUMP 13 SEER Model/Rev Description GSZ13**1AA Initial release with Regal Beloit motor. GSZ13**1AB GSZ13**3AA Initial release with Broad Ocean motor. GSZ13**4AA GSZ130[24 & 30]1AC Release of minor revision with improved circuiting for effective defrost. GSZ130[24 &...
  • Page 21 PRODUCT IDENTIFICATION GSZ13 GOODMAN SPLIT Z-R410A HEAT PUMP 13 SEER Model/Rev Description GSZ130[19,31]1AD GSZ130241BE Create new Motor & Replace 0131M00294 with 0131M00800 GSZ130251AC GSZ130601AE Create new Motor 0131M00807 & Replace 0131M00061 with 0131M00807 GSZ130181AH Replaced motor 0131M000266 with 0131M00811 GSZ130301AJ GSZ130361BF GSZ130371AD Replaced motor 0131M00018P with 0131M00813...
  • Page 22 PRODUCT IDENTIFICATION GSZ16 GOODMAN SPLIT Z-R410A HEAT PUMP 16 SEER Model/Rev Description GSZ160[18-48]1BA Initial release of Goodman 16 SEER, 13 EER Heat Pumps with 9.0+ HSPF GSZ1160601BA Initial release of Goodman 5 Ton 16 SEER, 13 EER Heat Pumps GSZ160241BB Motor change on 3 &...
  • Page 23 PRODUCT IDENTIFICATION SSZ14 SPECIAL HIGH FEATURE SPLIT Z-R410A HEAT PUMP 14 SEER Model/Rev Description SSZ140**1AA Initial release of Goodman 14 SEER Heat Pump R410A. SSZ140**1AB Screw locations moved in the top panel, base pans, louvers, and control box covers. SSZ140**1AC Broad Ocean Motors.
  • Page 24 PRODUCT IDENTIFICATION SSZ16 SPECIAL HIGH FEATURE SPLIT Z-R410A HEAT PUMP 16 SEER Model/Rev Description SSZ160**1AA Initial release of Goodman 16 SEER Heat Pump R410A. SSZ160**1AB Screw locations moved in the top panel, base pans, louvers, and control box covers. Broad Ocean Motor. Updated muffler and standardized TXV. Compensator using ASZ18 SSZ160**1AC SEER weldment to the SSZ160601AC.
  • Page 25 PRODUCT IDENTIFICATION GSX13 GOODMAN BRAND SPLIT X-R410A CONDENSERS 13 SEER Model/Rev Description GSX130**1AA Initial release of Goodman 13 SEER R-410A Condensers with Regal Beloit motors Introduction of Goodman 13 SEER R-410A Condensers that supplement our current 5 ton GSX13061[1/3/4]AA models. GSX130363AB GSX130484AB Changed from the current four piece louver assembly, to a two piece louver plus a corner...
  • Page 26 (OLP). c t i 13 SEER 2_5T Condenser Rechi Conversion - Switch from Copeland compressor to Rechi GSX130301LA compressor in 13 SEER 2.5 ton condensers (GSX, VSX, ANX) GSX130361EF GSX130[42,48]1BG Replaced motor 0131M00018P with 0131M00813...
  • Page 27 PRODUCT IDENTIFICATION GSX14 G OODMAN BRAND S PLIT X- R410A C ONDENSERS 14 SEER t n I . s l GSX140[18-19]1KA GSX140[24-25]1KA Goodman Split X 14 Seer Condensing units. Introducing the Goodman 14 SEER standard GSX140[30-31]1KA condenser 5mm architecture with updated scroll compressors. GSX140[36-37]1KA GSX140[42, 48, 60]1KA GSX140241KB...
  • Page 28 PRODUCT IDENTIFICATION GSX16 GOODMAN BRAND SPLIT X-R410A CONDENSERS 15 AND 16 SEER Model/Rev Description GSX160**1FA Initial release of the Goodman 16 SEER R410A Condensers. GSX160611FA New high capacity 5 ton model that will supplement the current GSX160601 models. GSX160[18-61]1FB Minor revision for GSX16s to include ball valves 0151R00045 and 0151R00046. GSX160601GA 7mm coils.
  • Page 29 PRODUCT IDENTIFICATION SSX14 SPECIAL HIGH FEATURE SPLIT X-R410A CONDENSERS 14 SEER Model/Rev Description SSX140**1AA Initial release of Goodman 14 SEER AC 410A. Revisions have screw locations moved in the top panel, base pans, louvers, and control SSX140**1AB box covers. SSX14018, 241AC Revised condenser coils by removing [1] haripin.
  • Page 30 PRODUCT IDENTIFICATION SSX16 SPECIAL HIGH FEATURE SPLIT X-R410A CONDENSER 16 SEER Model/Rev Description SSX160**1AA Introduces Goodman 16 SEER AC 410A New revisions have screw locations moved in the top panel, base pans, louvers, and SSX160**1AB control box covers. SSX160**1AB New revisions have screw locations moved in the top panel, base pans, louvers, and SSX160591AA control box covers.
  • Page 31 PRODUCT IDENTIFICATION VSX13 VALUE SPLIT X-R410A CONDENSER 13 SEER Model/Rev Description VSX130[18-48]1AA Introduces Value Line 13 SEER condensing units with R-410A. VSX130611AA Supplements the 5 ton model GSX130611 to enhance performance. VSX130301AB Replaced fan motor to -294 and fan blade to -18 on the VSX130301AA. VSX130301AC Changed from current four piece louver assembly to a two piece louver assembly plus a VSX130[42-48]1AC...
  • Page 32 (OLP). VSX130181EJ Switching compressor from 50N382XV-5AKM to 50N382YV-5AKM 13 SEER 2_5T Condenser Rechi Conversion - Switch from Copeland compressor to Rechi VSX130301LA compressor in 13 SEER 2.5 ton condensers (GSX, VSX, ANX) VSX130361EF VSX130[42,48]1AG Replaced motor 0131M00018P with 0131M00813 VSX130601BF...
  • Page 33 PRODUCT IDENTIFICATION VSX14 V ALUE S PLIT X- R410A CONDENSER 13 SEER VSX140[18-19]1AA VSX140[24-25]1AA Introducing the 14 SEER standard condenser 5mm architecture with updated scroll VSX140[30-31]1AA compressors. VSX140[36-37]1AA VSX140[42, 48, 60]1AA VSX140241AB Replaced 1/12hp fan motor with 1/8hp fan motor. Changed compressor from K5 to K6, Changed coil slab from 25"...
  • Page 34 (grommets, bolts, wires, associated tubing, etc.) will replace the current compressor and associated parts. 13 SEER 2_5T Condenser Rechi Conversion - Switch from Copeland compressor to Rechi ANX130301BA compressor in 13 SEER 2.5 ton condensers (GSX, VSX, ANX) ANX130181AC Replaced motor 0131M000266 with 0131M00811 ANX130181BB...
  • Page 35 PRODUCT IDENTIFICATION ANX14 AMANA® BRAND SPLIT SYSTEM N-BASE X-R410A CONDENSERS 14 SEER Model/Rev Description ® Introducing the Amana Brand 14 SEER standard condenser 5mm architecture with ANX140[18-60]1AA updated scroll compressors. ANX140241AB Replaces 1/12hp fan motor with 1/8hp fan motor. ANX140431AA Introduction of ready 15, 12.2 EER air conditioning units.
  • Page 36 Description ® ASX130**1AA Initial release new models of Amana Brand Deluxe 13 SEER AC R410A conditioners. Initial release of new models of Amana® Brand Deluxe 13 SEER AC R410A conditioners; ASX130611AA replaced ASX130601* models. ® Introduction of Amana brand 13 SEER R-410A Condensers that supplement our current ASX130611AA 5 ton models.
  • Page 37 PRODUCT IDENTIFICATION ASX14 AMANA® BRAND SPLIT X-CONDENSERS 14 SEER Model/Rev Description ® ASX140**1AA Initial release of models of Amana Brand Deluxe 14 SEER AC R410A conditioners. ASX140**1AB Screw locations moved in the top panel, base pans, louvers, and control box covers.
  • Page 38 PRODUCT IDENTIFICATION ASX14 AMANA® BRAND SPLIT X-CONDENSERS 14 SEER Model/Rev Description Remove HS Kit from Control Panels of condenser units with updated ASX140191KB ZP14K6E scroll compressors. ASX140241LA Change compressor from K6 to K5 on ASX140241 and DX14SA0241 ASX 140[30,43]1KB Change from copper wound motor to aluminum wound motor.
  • Page 39 PRODUCT IDENTIFICATION ASX16 AMANA® BRAND SPLIT X-CONDENSERS 16 SEER Model/Rev Description ASX160**1AB Screw locations moved in the top panel, base pans, louvers, and control box covers. ASX160**1AC Horizontal style louvers. ASX160**1FA Single speed outdoor fan. ASX160611FA High capacity 5 ton models that supplement the current ASX160601 models.
  • Page 40 PRODUCT IDENTIFICATION ACNF A-SINGLE PIECE AIR HANDLER CEILING MOUNT N-UNCASED FLOWATER Model/Rev Description ACNF****1AA Release of all models of 13 SEER Dayton uncased air handlers. Release of all models of 13 SEER Dayton uncased air handlers suitable for use with R-22 ACNF****16AA &...
  • Page 41 PRODUCT IDENTIFICATION AEPF A-SINGLE PIECE E-MULTI-POSITION VARIABLE SPEED PAINTED FLOWATER Model/Rev Description AEPF****16AA Introducation of new 13 SEER Air Handler Models suitable for use with R-22 and R-410A. AEPF****16BA Introduction of new models adding lower kW hit kits on the S&R plate. Replacement of the current spot welded blower housing with the same cinched or crimped AEPF****16BB design used on the 80% furnace line.
  • Page 42 PRODUCT IDENTIFICATION ARUF A-SINGLE PIECE AIR HANDLER R-MULTI-POSITION PSC MOTOR UNPAINTED FLOWRATOR Model/Rev Description Introduction of new Air Handler Models with all aluminum evaporator coils. Conversion ARUF172916AA includes coils, manifold, hairpin, flowrators, 3/8" return bend to 5/16" aluminum return A24-00-2RCA bends.
  • Page 43 PRODUCT IDENTIFICATION ARPT - R410A ONLY A-SINGLE PIECE AIR HANDLER R-MULTI-POSITION PSC MOTOR PAINTED FLOWRATER TXV Model/Rev Description ARPT***14AA Initial release of the new air handlers. ARPT***14AB Initial release of the air handlers manufactured at the Houston furnace facility. ARPT[18-36]B14AC Serial plate changes.
  • Page 44 PRODUCT IDENTIFICATION ASPT A-SINGLE PIECE AIR HANDLER S-MULTI-POSITION EEM MOTOR PAINTED TXV Model/Rev Description ASPT[24/36/48/60]*14 Introduction of new generation ASPT air handlers. ASPT36C 14AB ASPT[48/60]D14AB 9mm return bend coil changes to new generation of ASPT air handlers. ASPT48D 14AC ASPT24B 14AC Programmed Broad Ocean Motor.
  • Page 45 PRODUCT IDENTIFICATION MODULAR BLOWER AIR HANDLER R-MULTI-POSITION PSC MOTOR Model/Rev Description MBR****AA-1AA Initial release of a module blower with PSC blower motor. MBR****AA-1AB A quality improvement to use 0.75" Quiet Flex Insulation. MBR****AA-1AC Release of MBR/MBVC Models(Minor Revisions) for 11th St Plant. Dayton to Houston Add permanent sealing/condensation-control upgrades to all MB units and remove high- MBR****AA-1AD voltage knockouts...
  • Page 46 PRODUCT IDENTIFICATION AWUF A SINGLE PIECE AIR HANDLER WALL MOUNT PSC MOTOR UNPAINTED FLOWRATOR Model/Rev Description AWUF****1AA Initial release of 13 SEER Dayton wall mount air handlers. Initial release 13 SEER Dayton wall mount air handlers suitable for use with R-22 and R- AWUF****16AA 410A refrigerant.
  • Page 47 PRODUCT IDENTIFICATION AWUF A SINGLE PIECE AIR HANDLER WALL MOUNT PSC MOTOR UNPAINTED FLOWRATOR Model/Rev Description AWUF180[316,516,816]BC AWUF190[316,516,816]AB AWUF240[316,516,816]BC AWUF241016BC AWUF250[316,516,816]AB AWUF251016AB Release gasket and caps to seal leak. With this modification we will be able to meet 2% at AWUF300[516,816]BD 1 inch static leak and 1.4% leak rate at 0.5 inch static.
  • Page 48 PRODUCT IDENTIFICATION CAPF C-INDOOR COIL A-UPFLOW/DOWNFLOW PAINTED FLOWRATOR Model/Rev Description CAPF*****6AA Initial release of CAPF Dayton Upflow/Downflow coils. CAPF*****6BA Burr Oak Louvered Fin released in place of the Wavy Fin. CAPF36***CA Redesigned for performance improvement from 2 row to 3 row. CAPF*****6DA Replaced existing copper coils and other associated parts with aluminum components.
  • Page 49 PRODUCT IDENTIFICATION CAPF C-INDOOR COIL A-UPFLOW/DOWNFLOW PAINTED FLOWRATOR Model/Rev Description CAPFA1714A6AA CAPFA1714B6AA Initial release of 7mm AL CAPFA Upflow/Downflow Coils. CAPFA1818C6BA CAPFA2318A6AA CAPFA2318B6AA CAPFA2318C6AA Initial release of 7mm AL CAPFA Upflow/Downflow Coils. CAPFA2422A6AA CAPFA3022A6AA CAPFA2922A6AA CAPFA2922B6AA Initial release of 7mm AL CAPFA Upflow/Downflow Coils. CAPFA2922C6AA CAPFA4226B6AA CAPFA4226C6AA...
  • Page 50 PRODUCT IDENTIFICATION CAPT C-INDOOR OIL A-UPFLOW/DOWNFLOW PAINTED CASED FLOWRATOR W/TXV Model/Rev Description CAPT3131B4BA Initial release of coils with factory-installed, non-adjustable TXV. Single stage AHRI ratings CAPT3131C4BA for CAPT3131 NTC combinations. CAPT3743C4AA Initial release of single stage AHRI ratings for CAPT3743 NTC combinations. CAPT3743D4AA CAPT4961C4AA Initial release of single stage AHRI ratings for CAPT4961C4 NTC combinations.
  • Page 51 PRODUCT IDENTIFICATION CAUF/A C-INDOOR COIL A-UPFLOW/DOWNFLOW UNCASED FLOWRATOR Model/Rev Description CAUF*****6AA Initial release of CAUF Dayton Upflow/Downflow coils. CAUF*****6BA Burr Oak Louvered Fin released in place of the Wavy Fin. CAUF****6*DA Replaced existing copper coils and other associated parts with aluminum components. CAUF*****6DB Drain pan material changed.
  • Page 52 PRODUCT IDENTIFICATION CSCF C-INDOOR COIL S-HORIZONTAL SLAB COIL UNPAINTED FLOWRATOR Model/Rev Description CSCF*****6AA Release 13 SEER CSCF slab horizontal coil. Burr Oak Louvered Fin released in place of the Wavy Fin. The rows change by one, (i.e. CSCF*****6BA 4 row to 3 row; 3 row to 2 row) where applicable. CSCF1824N6BB CSCF3036N6BB Drain pan material change.
  • Page 53: Product Design

    The CAUF, CAPF and CAPT coils are designed for upflow and counterflow applications. The CACF and CHPF coils are designed for horizontal applications. GSX, GSZ, ANX, ANZ, ASX, ASZ, SSX, SSZ, DSX, DSZ, VSX, and VSZ models are available in 1 1/2 through 5 ton AR*F, ASPF, ASUF, ASPT sizes and use R-410A refrigerant.
  • Page 54 PRODUCT DESIGN The ASX [16 & 18], ASZ [16 & 18], DSX[16 & 18] and As this motion occurs, the pockets between the two forms DSZ [16 & 18] series split system units use a two-stage are slowly pushed to the center of the two scrolls while scroll compressor.
  • Page 55 PRODUCT DESIGN Molded Plug w/ Rectifier Line Run Capacitor Line Internal Unloader Coil 24 Vac FIGURE B 1. It is expected that the majority of run hours will be in the low capacity, unloaded mode. 2. It allows a simple two-stage thermostat to control capacity through the second stage in both cooling and possibly heating if desired.
  • Page 56: System Operation

    SYSTEM OPERATION Cooling Cycle For heat pumps, during cooling cycle the reversing valve is For legacy room thermostat: When the room thermostat energized as the room thermostat closes “O” terminal to R calls for cool, the contacts of the room thermostat close and the microprocessor on the UC board responds to such making terminals R to Y1 &...
  • Page 57 SYSTEM OPERATION This draws in the normally open contact CC, starting the Heating Cycle Reversing Valve compressor condenser fan motors. At the same time, The reversing valve on the GSZ, SSZ, ANZ, ASZ and DSZ (Energized) contacts RFC close, starting the indoor fan motor. models is energized in the cooling cycle through the “O”...
  • Page 58 Expansion Valve/Check Valve Assembly In Heating Operation Operation Most expansion valves used in current Amana Heat Pump products use an internally checked expansion valve. This type of expansion valve does not require an external check valve as shown above. Restrictor Orifice Assy in Cooling Operation...
  • Page 59 SYSTEM OPERATION NOTE: If more than two heater elements are on 4.1 On a demand for first stage heat with heat pump units, the heater assembly, it will contain a second heat the room thermostat energizes “G” and “Y” and 24Vac is sequencer, HR2,which will control the 3rd and 4th supplied to “Y”...
  • Page 60 5.2 The defrost control in the heat pump unit checks to seeif a defrost is needed every 30, 60 or 90 minutes of MBE/AEPF With Single Stage GSX, ANX, ASX, SSX, heat pump operation depending on the selectable setting And VSX Condensers...
  • Page 61 SYSTEM OPERATION NOTE: If more than two heater elements are on 3.2 The heat pump is turned on in the cooling mode. the heater assembly, it will contain a second heat sequencer, HR2, which will control the 3rd and 4th 3.3 When the cooling demand is satisfied, the room heater elements if available.
  • Page 62 SYSTEM OPERATION NOTE: If more than two heater elements are on 5.4 When a defrost cycle is initiated, the contacts of the the heater assembly, it will contain a second heat HVDR relay on the defrost board open and turns off the sequencer, HR2, which will control the 3rd and 4th outdoor fan.
  • Page 63 SYSTEM OPERATION NOTE: If more than two heater elements are on 1.1 On a demand for cooling, the room thermostat the heater assembly, it will contain a second heat energizes “G” and “Y1” and 24Vac is supplied to “G” and “Ylow/Y1”...
  • Page 64 SYSTEM OPERATION 4.2 If a thermostat that provides a “Y2” demand in heating 3.1 On a demand for cooling, the room thermostat is used and first stage heating cannot satisfy the demand, energizes “G” and “Y1” and 24Vac is supplied to “G” and the room thermostat will energize “Y2”...
  • Page 65 SYSTEM OPERATION 5.4a For models with defrost control PCBDM133 or 4.5 As the temperature indoors increase, it will reach a PCBDM160, a 30 second compressor delay at defrost point where the “W2/W3” demand is satisfied. When initiation/termination is optional. As shipped from the this happens, the room thermostat will remove the 24Vac factory, the control is set for the delay (“DLY”), which will from “E/W1”...
  • Page 66: Servicing

    SERVICING Checking Voltage Checking Wiring 1. Remove outer case, control panel cover, etc., from unit WARNING being tested. High Voltage! With power ON: Disconnect all power before servicing or installing. Multiple power sources WARNING may be present. Failure to do so may cause property damage, personal injury or death.
  • Page 67: Checking Transformer And Control Circuit

    SERVICING Resistance Heaters Checking Contactor And/Or Relays 1. Set room thermostat to a higher setting than room WARNING temperature so both stages call for heat. 2. With voltmeter, check for 24 volts at each heater relay. High Voltage! 3. No voltage indicates the trouble is in the thermostat or Disconnect all power before servicing wiring.
  • Page 68: Checking Fan Relay Contacts

    SERVICING 1. Disconnect wire leads from terminals 2 and 4 of Fan Relay Cooling and 2 and 4, 5 and 6 of Fan Relay Heating. 2. Using an ohmmeter, test between 2 and 4 - should read open. Test between 5 and 6 - should read continuous. 3.
  • Page 69: Checking Loss Of Charge Protector (Heat Pump Models)

    SERVICING 5. Apply power to unit and set thermostat to cool and set for all for cool. WARNING 6. High pressure switch should open at 610 PSIG +/- 10 PSIG and close at 420 PSIG +/- 25 PSIG Line voltage now present 7.
  • Page 70: Copeland Comfort Alert™ Diagnostics - 3-Wire Module

    SERVICING 5. Apply power to unit and set thermostat to cool and set for a call for cool. Bold line shows field installed wiring 6. Low pressure switch should open at 21 PSIG, and auto Dashed line shows thermostat demand wiring in system without reset (close) at approximately 50 PSIG.
  • Page 71 SERVICING Once attached, CoreSense™ provides around-the-clock Diagnostics - 2-Wire Module monitoring for common electrical problems, compressor Applies to ASX130[18-60]CA, ASX140[18-36]1CA, defects and broad system faults. If a glitch is detected, an ASX140421DA, And ASX140[48-60]1BA Units LED indicator flashes the proper alert codes to help you WARNING quickly pinpoint the problem.
  • Page 72 SERVICING Diagnostics Table: 2-Wire Comfort Alert™ Module Status LED Status LED Description Status LED Troubleshooting Information Green “POWER” Module has power Supply voltage is present at module terminals Red “TRIP” Thermostat demand signal 1. Compressor protector is open Y1 is present, but the 2.
  • Page 73 SERVICING Diagnostics Table: Coresense™ Module Flash code number corresponds to the number of LED flashes, followed by a pause and then repeated. TRIP and ALERT LEDs flashing at the same time mean control circuit voltage is too low for operation. Status Description Troubleshooting Information...
  • Page 74 SERVICING Diagnostics Table: Coresense™ Module Flash code number corresponds to the number of LED flashes, followed by a pause and then repeated. TRIP and ALERT LEDs flashing at the same time mean control circuit voltage is too low for operation. Status Description Troubleshooting Information...
  • Page 75 SERVICING Table 1 - Quick Reference Table Alert Code Alert Condition Lock Level Lock Indication Normal Run Normal operation, no trip Solid Yellow Code1 Long run time. Compressor is on running for more than 18 Yellow Flash 1 hours. (Code1 is disabled in Heat Pump mode.) Compressor (pressure) trip.
  • Page 76: Checking Capacitor

    Only hard start kits approved by Amana® brand or Copeland should be used. “Kick Start” and/or “Super Boost” kits are not approved start assist devices.
  • Page 77: Testing A Run Capacitor Under Load

    SERVICING Checking Fan and Blower Motor (ECM Motors) To prevent the compressor from short cycling, a Time Delay Relay (Cycle Protector) has been added to the low voltabe An ECM is an Electronically Commutated Motor which circuit. offers many significant advantages over PSC motors. The ECM has near zero rotor loss, synchronous machine Testing a Run Capacitor Under Load operation, variable speed, low noise, and programmable...
  • Page 78: Checking Ecm Motor Windings

    SERVICING 4. Using an ohmmeter, check the motor windings for continuity to ground (pins to motor shell). If the ohmmeter indicates continuity to ground, the motor is defective and Lines 1 and 2 will be connected must be replaced. for 12OVAC Power Connector applications only 5.
  • Page 79 SERVICING Dipswitch Functions Cooling/Heat Pump Operation The MBE / AEPF air handler motors have an electronic Model Switch 5 Switch 6 control that contains an eight (8) position dip switch. The 1,200 function of these dipswitches are shown in Table 1. 1,000 MBE1200 Dipswitch Functions...
  • Page 80 SERVICING CFM Delivery Tables 10-Electric Heat and 11-Cooling/Heat Pump show the CFM output for dipswitch combinations 1-2, and 5-6. Emergecny Heat Pump Switch Switch Model (Electric) w/Backup Heat Heat 1100 1210 AEPF1830 2050 2150 1750 1835 AEPF3036 AEPF3137 OFF 1600 1680 1200 1260...
  • Page 81 SERVICING...
  • Page 82 SERVICING...
  • Page 83: Blower Performance Data

    SERVICING Blower Performance Data MBR800**-* MBR1200**-* MBR1600**-* MBR2000**-* SPEED STATIC SCFM SCFM SCFM SCFM 1,240 1,500 1,800 2,160 1,170 1,460 1,740 2,080 1,120 1,360 1,680 1,990 HIGH 1,060 1,280 1,610 1,890 1,200 1,520 1,790 1,110 1,430 1,690 1,380 1,540 1,730 1,320 1,490 1,670...
  • Page 84: Eem Blower Replacement

    SERVICING EEM Blower Replacement For AWUF19-25, AWUF31-32, and AWUF37 Air Handlers. 1. Disconnect power at main electrical panel. 2. Remove front access panel. 3. Remove the two screws on each side holding the lower control box and move out of the way to give access to the blower assembly 5.
  • Page 85: Mbr/Ar*F Electronic Blower Time Delay Relay

    SERVICING During an electric heat only demand, “W1” is energized but “G” is not. The blower motor is connected to the normally closed contacts of the relay on the EBTDR board. The other side of this set of contacts is connected to the heat sequencer on the heater assembly that provides power to the first heater element.
  • Page 86: Resistance Test

    SERVICING Ignition cannot occur at the venting terminal without the presence of contaminant air, and cannot occur externally from the venting terminal without the presence of an external ignition source. Therefore, proper evacuation of a hermetic system is essential at the time of manufacture and during servicing. To reduce the possibility of external ignition, all open flame, electrical power, and other heat sources should be extinguished or turned off prior to servicing a system.
  • Page 87: Unloader Test Procedure

    SERVICING 2. If step one does not give the expected results, shut unit 6. If ground is indicated, replace the compressor. The off. Apply 18 to 28 volt ac to the unloader molded plug resistance reading should be infinity. If there is any leads and listen for a click as the solenoid pulls in.
  • Page 88: Checking 3-Phase Scroll Compressor Rotation

    SERVICING A crankcase heater will not prevent compressor damage WARNING due to a floodback or over charge condition. Line voltage now present WARNING • If the compressor starts and continues to run, the cause Disconnect ALL power before servicing. for failure is somewhere else in the system. •...
  • Page 89: Testing Defrost Control

    SERVICING Trouble Shooting Mechanical Failures on a Reversing 6. Using VOM check for voltage across fan terminals DF1 Valve by Temperature and DF2 on the board. You should read line voltage (208- 1. When operating properly the valve contains refrigerant 230 VAC) indicating the relay is open in the defrost mode.
  • Page 90: Checking Heater Elements

    SERVICING 1. Remove the wiring from the control terminals. If other than a 240V power supply is used, refer to the BTUH CAPACITY CORRECTION FACTOR chart below. 2. Using an ohmmeter test for continuity across the normally closed contacts. No reading indicates the control is open - replace if necessary.
  • Page 91: Checking Heater Limit Control(S)

    SERVICING NOTE: The link is designed to open at approximately FORMULAS: 333°F. DO NOT WIRE AROUND - determine reason for Heating Output = KW x 3413 x Corr. Factor failure. Actual CFM = CFM (from table) x Corr. Factor Checking Heater Elements BTUH = KW x 3413 WARNING BTUH = CFM x 1.08 x Temperature Rise (T)
  • Page 92: Leak Testing (Nitrogen Or Nitrogen-Traced)

    SERVICING Brazing Materials Evacuation IMPORTANT NOTE: Torch heat required to braze tubes of various sizes is proportional to the size of the tube. Tubes of smaller size require less heat to bring WARNING the tube to brazing temperature before adding brazing alloy.
  • Page 93: Charging

    SERVICING 4. If the pressure rises to 1000 microns or less and remains steady the system is considered leak free; proceed to CAUTION startup. Damage to the unit caused by operating the 5. If pressure rises above 1000 microns but holds steady compressor with the suction valve closed is below 2000 microns, moisture and/or non-condensibles not covered under the warranty and may cause...
  • Page 94: Checking Compressor Efficiency

    SERVICING After the refrigerant charge has bled into the system, 8. Disconnect manifold set, installation is complete. open the liquid service valve. The service valve cap is the secondary seal for the valve and must be properly SUBCOOLING FORMULA = SATURATED LIQUID TEMP. - tightened to prevent leaks.
  • Page 95: Underfeeding

    .065 .065 G/VSZ140601 .065 .065 Superheat on Fixed Orifice or TXV Amana 14 SEER Heat Pumps 1. Purge gauge lines. Connect service gauge manifold to base-valve service ports. Run system at least 10 minutes Model Cur. Rev Piston Prev. Rev Piston to allow pressure to stabilize.
  • Page 96: Subcooling On Expansion Valve System

    SERVICING 5. Capture the charge, replace the valve and drier, evacuate NOTE: An optional method is to locate the and recharge. thermometer at the suction line service valve. Ensure the thermometer makes adequate contact and is insulated for best possible readings. Checking Restricted Liquid Line When the system is operating, the liquid line is warm to the 3.
  • Page 97 SERVICING Pressure vs. Temperature Chart R-410A PSIG °F PSIG °F PSIG °F PSIG °F PSIG °F PSIG °F -37.7 114.0 37.8 216.0 74.3 318.0 100.2 420.0 120.7 522.0 137.6 -34.7 38.7 74.9 100.7 121.0 137.9 116.0 218.0 320.0 422.0 524.0 -32.0 118.0 39.5...
  • Page 98 SERVICING REQUIRED LIQUID LINE TEMPERATURE LIQUID PRESSURE REQUIRED SUBCOOLING TEMPERATURE (°F) AT SERVICE VALVE (PSIG)
  • Page 99: Non-Condensables

    If the pressure indicates a higher temperature than that of the coil temperature, non-condensables are present. NOTE: The Flushing Method using R-11 refrigerant is no longer approved by Amana® Brand Heating- Non-condensables are removed from the system by first Cooling.
  • Page 100: Refrigerant Piping

    SERVICING Refrigerant Piping The piping of a refrigeration system is very important in relation to system capacity, proper oil return to compressor, pumping rate of compressor and cooling performance of the evaporator. POE oils maintain a consistent viscosity over a large temperature range which aids in the oil return to the compressor;...
  • Page 101: Furnace External Static Pressure

    SERVICING Static Pressure Drop Periodic Maintenance Motors Indoor and Outdoor motors are permanently lubricated and Furnace External Static Pressure do not need additional oiling. To determine proper airflow, proceed as follows: 1. With clean filters in the furnace, using a Inclined Manometer Cleaning Outdoor Coil or Magnehelic gauge measure the static pressure of the 1.
  • Page 102 SERVICING Cleaning Aluminum Coils Evaporator coils and air handlers are equipped with an aluminum tube evaporator coil. The safest way to clean the evaporator coil is to simply flush the coil with water. This cleaning practice remains as the recommended cleaning method for both copper tube and aluminum tube residential cooling coils.
  • Page 103: Wiring Diagrams

    WIRING DIAGRAMS 10kw and Below, One Stage Electric Heat From Air Handler BLUE WHITE BROWN BLACK THERMOSTAT EMERGENCY HEAT RELAY OT/EHR18-60 From Outdoor Unit 15kw and Above, Two Stage Electric Heat From Air Handler SEE NOTE BLUE WHITE BROWN BLACK THERMOSTAT EMERGENCY HEAT...
  • Page 104 WIRING DIAGRAMS 15kw and Above with Two OT/EHR18-60's, Two Stage Electric Heat and Two Stage Thermostat From Air Handler OT/EHR18-60 #1 BLUE WHITE BROWN BLACK THERMOSTAT EMERGENCY HEAT RELAY OT/EHR18-60 #2 BLUE WHITE BROWN BLACK THERMOSTAT EMERGENCY HEAT RELAY From Outdoor Unit Typical Wiring Schematics for OT/EHR18-60 (Outdoor Thermostat &...
  • Page 105 WIRING DIAGRAMS 3-Phase Heat Kit 25kW Heat Kit Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 106 WIRING DIAGRAMS ADPF, ARPF, ARUF, ATUF SEE N OTE S 2 & 6 TERMINA L BLOC K SHOW N EQ UIPMENT GROUND FOR 50HZ MODELS ONLY USE COPPE R W IRE RD GR GRND 208/240 VOLTS NOT E 4 SEE NOTE 5 SEE NOTE 1 EBTDR EBTDR...
  • Page 107 WIRING DIAGRAMS AEPF HTR1 HTR2 HTR1 HTR1 TL HTR2 HTR1 TL HTR2 HTR3 HTR3 TL HTR4 ONE (1) ELEMENT ROWS TWO (2) ELEMENT ROWS THREE (3) ELEMENT ROWS FOUR (4) ELEMENT ROWS AFTER INSTALLING OPTIONAL HEAT KIT, MARK AN "X" IN THE PROVIDED ABOVE.
  • Page 108 WIRING DIAGRAMS AEPF******CA HTR 1 HTR 1 HTR 1 HTR 1 HTR 2 PL 1 HTR 2 HTR 2 PL 1 PL 1 HTR 3 PL 1 HTR 3 HTR 4 ONE (1) ELEMENT ROWS TWO (2) ELEMENT ROWS L1 L2 THREE (3) ELEMENT ROWS FOUR (4) ELEMENT ROWS L1 L2...
  • Page 109 WIRING DIAGRAMS AR[090-120]4 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 110 WIRING DIAGRAMS ARPT**14**/ARUF**14** Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 111 WIRING DIAGRAMS ASPF******BA Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 112 WIRING DIAGRAMS ASPF******C* Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 113 WIRING DIAGRAMS ASPT**14**/ASUF**14** Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 114 WIRING DIAGRAMS ASPT**14**/ASUF**14** 3-PHASE HEAT KIT Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 115 WIRING DIAGRAMS AWUF310516AE, AWUF310816AD, AWUF321016AD Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 116 WIRING DIAGRAMS AWUF180[316,516,816]BD, AWUF240[316,516,816]BD, AWUF241016BD,AWUF300[516,816]BE, AWUF301016BE, AWUF360[516,816]BE, AWUF361016BE, AWUT24[05,08,10]14AA Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 117 WIRING DIAGRAMS AWUF190[316,516,816]AC, AWUF250[316,516,816]AC Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 118 WIRING DIAGRAMS AWUF370[516,816]BD, AWUF371016BE Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 119 WIRING DIAGRAMS AWUF31[05/08]16AB, AWUF321016AB, AWUF[19,25]** Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 120 WIRING DIAGRAMS AWUF18[03/05/08]16BB, AWUF24[03/05/08/10]16BB, AWUF30[05/08/10]16BC, AWUF36[05/08/10]16BC Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 121 WIRING DIAGRAMS AWUF37[05/08/10]16BB Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 122 WIRING DIAGRAMS 208/240 HTR2 HTR3 HTR4 EBTDR XFMR-R XFMR-C SPEEDUP W BR EQUIPMENT GROUND USE COPPER OR ALUMINUM WIRE USE COPPER WIRE Typical Wiring Schematic MBR Blower with Electric Heat. This wiring diagram is for reference only. Not all wiring is as shown above. Refer to the appropriate wiring diagram for the unit being serviced.
  • Page 123 WIRING DIAGRAMS Blower Section Typical Wiring Schematic MBE Blower with Electric Heat. This wiring diagram is for reference only. Not all wiring is as shown above. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 124 WIRING DIAGRAMS ANX130[18-24]1A* Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 125 WIRING DIAGRAMS ANX130[30-61]1A* ANX140[18-60]1A* Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 126 WIRING DIAGRAMS ANZ130[18-60]1A* LVDR 0-RV C-RV HVDR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 127 WIRING DIAGRAMS ASX130[18-48]1C[A/B]/ASX130601CA Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 128 WIRING DIAGRAMS ASX130181D*/ASX130[24,30,48]1CC-CE ASX130361[CC,CD]/D* Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 129 WIRING DIAGRAMS ASX140[18-36/48]1C[A/B] ASX140421D[A/B] / ASX140[48-60]1[BA/B] Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 130 WIRING DIAGRAMS ASX140[24-36]1CD/ASX140421DD/ASX140481CC/ ASX140601BD/ ASX1401801DB/ ASX140241KB Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 131 WIRING DIAGRAMS ASX140[18-60]1KA Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 132 WIRING DIAGRAMS ASZ130[18-60]1* LVDR 0-RV C-RV HVDR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 133 WIRING DIAGRAMS ASZ140381A*; ASZ140[18,30]1*K; ASZ140241*L; ASZ140301*K; ASZ140421*J; ASZ140[18-30]1B* LVDR 0-RV C-RV HVDR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 134 WIRING DIAGRAMS ASZ160[18-48]1L* LVDR 0-RV C-RV HVDR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 135 WIRING DIAGRAMS ASZ160601-L* LVDR 0-RV C-RV HVDR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 136 WIRING DIAGRAMS *SX160[24-60]1** Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 137 WIRING DIAGRAMS *SX180[36-60]1A* Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 138 WIRING DIAGRAMS *SZ160[24-60]1A* Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 139 WIRING DIAGRAMS *SZ180[36-60]1A* Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 140 WIRING DIAGRAMS GSX11[090-120]*A* Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 141 WIRING DIAGRAMS GSX130[36-61][3,4]A*/3-Phase Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 142 WIRING DIAGRAMS GSX140[18-60]1K*, GSX160[18-48,611]1F* Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 143 WIRING DIAGRAMS GSX160601F* Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 144 WIRING DIAGRAMS GSX160611F* Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 145 WIRING DIAGRAMS GSZ11[090-120]3A* LVDR 0-RV C-RV HVDR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 146 WIRING DIAGRAMS GSZ130181A[D/F/G], GSZ130241[B*/C*], GSZ130421A[G/H], GSZ130301A[E/F/G/H], GSZ130361B*, GSZ140[18-30/48-60]1AA, GSZ140[36-42]1AB, GSZ130181AC, GSZ130241BB, GSZ130301AD GSZ130361B*, GSZ130421A*, GSZ130481AC, GSZ130601AC LVDR 0-RV C-RV HVDR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 147 WIRING DIAGRAMS GSZ130[36-60][3,4]A* Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 148 WIRING DIAGRAMS GSZ160[18-48]1B* LVDR 0-RV C-RV HVDR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 149 WIRING DIAGRAMS GSZ160601B* LVDR 0-RV C-RV HVDR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 150 WIRING DIAGRAMS SSX140[18-60]1A*/B*/C* Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 151 WIRING DIAGRAMS SSX160[24-48]1A*/B*;SSX160591AA Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 152 WIRING DIAGRAMS SSX160601A*/BA Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 153 WIRING DIAGRAMS SSZ140381AA, SSZ140[18,30,42-60]1A*, 241A*, 361A*, SSZ140[18-36]1B*, SSZ140[19-37]1A*, SSZ140[18,30,42-60]1A*, 241A*, 361A*, SSZ140361B* LVDR 0-RV C-RV HVDR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 154 WIRING DIAGRAMS SSZ160[24]1AG, SSZ160[36-48]1AE, SSZ160[24]1AA-AF, SSZ160[36-48]1AA-AD LVDR 0-RV C-RV HVDR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 155 WIRING DIAGRAMS SSZ160[60]1BA, SSZ160[60]1AB/AC/AD/AE LVDR 0-RV C-RV HVDR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 156 WIRING DIAGRAMS VSX130[18-48/61]1A* / VSX130{24/36/42-60]1B*/1D*, VSX130[30]1D*/VSX130[36]1E*/ VSX140[18-60]1A*/VSX130[18-48/61]1A* VSX130[24/36/42-60]1B*/1D*/VSX130[30]1D*/ VSX130[36]1E* Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 157 WIRING DIAGRAMS VSX130181B*/D* Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 158 WIRING DIAGRAMS VSX130[18-24]1E* Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 159 WIRING DIAGRAMS VSZ130181A[C/D/E/F], VSZ130241B[B/C/D], VSZ130301A[D/E/F/G], VSZ130361B[B/C/D], VSZ130421A[C/D/E/F/G], VSZ130481A[C/D], VSZ130601AC LVDR 0- RV C-RV HVDR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 160 Please fill out the feedback form on one of the following links: Goodman Brand Products: (http://www.goodmanmfg.com/about/contact-us). ® Amana Brand Products: (http://www.amana-hac.com/about-us/contact-us). ® You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page. GOODMAN BRAND ®...