Advanced Setpoints; Network Settings - Greenheck PGD1000W00 Reference Manual

Microprocessor controller for make-up air
Table of Contents

Advertisement

Control Variables
Advanced

Advanced Setpoints

Control Variables
Advanced

Network Settings

®
Menu
o
e
h
Verride
lecTric
eaT
When This screen only appears if the unit is equipped with electric post heat.
Electric heater percentage is directly proportional to the 0 – 10 VDC output signal.
o
h
Verride
eaTing
When the heating control is in the manual mode, use the arrow buttons to vary the
heating output.
o
e
c
Verride
conomizer
When the heating control is in the manual mode, use the arrow buttons to vary the
output of the economizer ramp. This value may have an effect on the modulating
outside air damper position.
The Advanced Setpoints Menus allows the user to view and modify network
settings. The service password (1000) is required to make changes.
u
u
o
noccupied
niT
peraTion
Possible unoccupied unit operation methods include:
• Unit Off
• Night Setback Cycle
• Recirculation with Unoccupied Setpoints
• Normal Operation with Unoccupied Setpoints
m
w
u
orning
arm
p and
This screen will appear when the unit has a recirculating air damper installed. The
user can enable morning warm up, morning cool down, and set the duration for
the sequence.
The Network Settings Menus allows the user to view and modify network
settings. The service password (1000) is required to make changes.
.
co b
a
c
p
oard
ddress
This screen will appear with or without a network protocol provided with the unit.
This screen allows the user to configure the IP setting for BMS and/or when
the Web User Interface will be utilized. The controller may have a DHCP server-
assigned address or a manually-assigned static IP address. Factory settings are
shown in the screen to the left.
bac
ip c
neT
onFig
This screen will appear if the unit is set for BACnet IP and allows the user to set
the device and port settings.
m
Tcp s
odbus
laVe
This screen will appear if the unit is set for Modbus TCP and allows the user to set
device ID number.
onTrol
c
d
ool
own
Microprocessor Controller for MUA