The fire control panel

Advertisement

Technical Documentation
The Fire control panel
SCP-03
Rev.02
SKALMEX Sp. z o.o.
ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39
Strona 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SCP-03 and is the answer not in the manual?

Questions and answers

Summary of Contents for Skalmex SCP-03

  • Page 1 Technical Documentation The Fire control panel SCP-03 Rev.02 SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 1...
  • Page 2 Failure to follow the instructions contained in this manual may be dangerous or cause damage to the control unit. SKALMEX Sp. z o.o. is not liable for damages resulting from operating contrary to the following instruction. The product is not suitable for further operation, should be sent to one of the points dealing with the collection of waste electrical and electronic equipment.
  • Page 3: Table Of Contents

    8.1 Fire gate or lock 8.2 Smoke exhaust flap 9. Description of control panel I / O terminals 10. Maintenance and replacement of fuses 11. Packaging, storage, transport SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 3...
  • Page 4: Introduction

    − alarm. 1.3 Protection and safety of use The smoke removal system control panel and the SCP-03 gate or airlock control are classified as protection class I devices and should only be used if additional electric shock protection is used in the form of connection to the machine's protective terminal, protective conductor (PE) or protective-neutral conductor (PEN).
  • Page 5: Delivery Range

    SKALMEX Sp. z o.o. is not responsible for the operation of equipment maintained and repaired by unauthorized companies. 1.4 Delivery range − Control panel for smoke extraction and gate or airlock control fire protection SCP-03 −...
  • Page 6: Guarantee

    2. The condition for recognizing the warranty is performance by SKALMEX Sp. z o.o. or a company authorized by the manufacturer to require periodic system maintenance with a frequency of at least once a year.
  • Page 7: Product Description

    2. Product description The smoke removal system control panel the SCP-03 gate or airlock control is designed for use in smoke removal systems and the control of the gate or airlock cutting off hazardous rooms. The Alarm state can be issued by signals from: sensors, manual smoke exhaust buttons, manual call points, external fire protection systems.
  • Page 8 (<3s) ATTENTION - All functions related to the alarm state have a higher priority than the other functions of the control unit. SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 8...
  • Page 9: Control Panel Technical Data

    3. Control panel technical data Control panel type SCP-03 Overall dimensions 260x312x125mm Total weight <7 kg IP 42 housing tightness Environmental class: 2 Operating temperature range: - 5 ° C ÷ + 50 ° C (Long-term operation) - 5 ° C ÷ + 75 ° C (Short-term operation max. 2 hours) Permissible relative humidity of operation 95% at + 40 °...
  • Page 10 -multiplied signals of the door motors of the gate x4 pcs 1 changeover contact 8A 250VAC -output electromagnetic jumper door 1 changeover contact 8A 250VAC SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 10...
  • Page 11: Configuration And Data Reading Options

    4. Configuration and data reading options In the SCP-03 control panel, access to configuration elements and enabling the control panel status reading has been divided into 3 levels. Access level 1 - includes signaling and buttons on the control panel main cover, access is not restricted.
  • Page 12: Level 2

    SW2.2-Blocking the option of external alarm reset caused by the manual smoke exhaust button. SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 12...
  • Page 13 If only the failure diode on the housing is lit and no diode indicating the type of error is lit, then the main power supply failure occurs. SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39...
  • Page 14 Battery error, voltage too low or too high. In conjunction with the blue LED on the front panel flashing, the battery is damaged or disconnected. SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 14...
  • Page 15 The test LED blinks every second during the control panel normal operation. Ad. f The D6 diode signals the processor reset with a hardware monitoring system. SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 15...
  • Page 16: Description Of Control Panel Operating States

    There is an option to try again to open the smoke damper for 30 minutes in 2-minute opening and waiting cycles. Enabling this option is possible with the configuration switch SW2.3. SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 16...
  • Page 17: Main Alarm Status

    There is an option to try again to open the smoke damper for 30 minutes in 2-minute opening and waiting cycles. Enabling this option is possible with the configuration switch SW2.3. SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 17...
  • Page 18: Supervision Status

    − Multiple switching on and off of all LEDs in the control panel for checking their operation. − After a few seconds, simulating an alarm condition for checking the correctness of the control panel response. SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 18...
  • Page 19: Failure Status

    The failure condition disappears automatically when no error occurs. The failure condition can also be caused by damage to the battery, in which case the battery LED will additionally flash. SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 19...
  • Page 20: Installation Of The Control Panel

    The device is installed using 4 wall plugs of a size not less than 6 mm. The location of the mounting holes is shown in the figure below. SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 20...
  • Page 21 (4k7), as close as possible to the smoke exhaust damper. The way of connecting the ventilation buttons and manual SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 21...
  • Page 22 (+) to the appropriate output (network, alarm or failure), connect the cathode (-) of all LEDs together and connect to the GND terminal. The supply voltage for additional LEDs is 24VDC. SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 22...
  • Page 23: Configuration And Commissioning

    After switching on the control panel, you should not: -Change settings with configuration switches -Screw and unscrew the wires -Remove and insert plugs with cables connected to the headquarters SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 23...
  • Page 24: Manual Control

    Re-opening it is possible only manually and turning off (except for the alarm condition) after the signal loss at the weather input. SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 24...
  • Page 25 Return to counting is possible again after pressing the open button. SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 25...
  • Page 26: Description Of Control Panel I / O Terminals

    5. GND BRAKE – 24V brake ground cable 6. power supply for circuit breakers 24V 7. Limit switch up - limit switch signals 8. Limit switch down - limit switch signals SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 26...
  • Page 27 To use them, solder the tin jumper next to the connector. Solution for Fire Control devices with NO contact. Set SW3 dip SW3.2 to OFF position on switch. SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 27...
  • Page 28 SMOKE DETECTOR - input for conventional sensors, e.g. smoke detectors. You can connect up to 6 smoke detectors on one line. At the end of the line, connect a 4700ohm terminating resistor. SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 28...
  • Page 29 GATE - buttons for manually opening (S3) and closing (S4) the gate. LED - signaling diode outputs: breakdown (failure, LED1), ALARM (LED2), MAINS (power supply, LED3). SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 29...
  • Page 30 BREAKDOWN - failure ALARM - alarm HOLDERS - ventilation jumper relay, switching the relay on should release the jumper catch and thus open it SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 30...
  • Page 31: Maintenance And Replacement Of Fuses

    Checking the operation of the fire gate and smoke damper, signaling devices and the correctness of signal transmission to external devices and systems. SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 31...
  • Page 32 However, the owner of the installation, in consultation with the designer and conservator, can increase the number of inspections carried out per year. SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 32...
  • Page 33: Packaging, Storage, Transport

    The units must also be protected against sudden shocks and ambient temperatures outside the range from - 20 ° C to + 50 ° C. SKALMEX Sp. z o.o. ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 33...