All examples and diagrams are intended to aid understanding, and do not guarantee operation. Unitronics accepts no responsibility for actual use of this product based on these examples. Please dispose of this product according to local and national standards and regulations.
4. Tighten the bracket’s screws against the panel. Hold the bracket securely against the unit while tightening the screw. 5. When properly mounted, the controller is squarely situated in the panel cut-out as shown in the accompanying figures. V130/V130J/V350/V350J/V350S/V350JS Unitronics...
Page 4
DIN-rail Mounting (V130/V130J/V350/V350J/V350S/V350JS ) 1. Snap the controller onto the DIN rail as shown in the figure to the right. 2. When properly mounted, the controller is squarely situated on the DIN-rail as shown in the figure to the right. Unitronics...
- If input 0 is set as a high-speed counter (without reset), input 1 can function as a normal digital input. Inputs 7-8 and 9-10 can function as digital, thermocouple, or PT100 inputs; Input 11 can also serve as the CM signal for PT100. Unitronics...
Page 6
Analog Output 0: Set to Voltage/Current Digital* Set to JP13 Voltage Voltage* Current Current Input 6: Set Type - Digital or Analog #2 Set to Analog Output 1: Set to Voltage/Current Digital* Set to JP14 Voltage Voltage* Current Current *Default settings Unitronics...
Page 8
PT100 (Sensor 0): use Input 9 and 10, related to CM signal. PT100 (Sensor 1): use Input 7 and 8, related to CM signal. 4 wire PT100 can be used by leaving one of the sensor leads unconnected Unitronics...
To maximize system performance, avoid electromagnetic interference by: Mounting the controller on a metal panel. Connect each common and ground connection directly to the earth ground of your system. For ground wiring uses the shortest and thickest possible wire. Unitronics...
Page 10
To do so, remove the RS485 connector (pins 1 & 6) from the PLC and connect a standard RS232 programming cable. Note that this is possible only if DTR and DSR signals of RS232 are not used (which is the standard case). Unitronics...
Page 11
** Causes the unit to function as an end unit in an RS485 network USB Port The USB port is not isolated. Caution Make sure that the PC and the controller are grounded to same potential. The USB port may be used for programming, OS download, and PC access. Unitronics...
Note that you must replace the back cover securely before powering up the controller. The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market.