Toshiba GR200 Series Instruction Manual page 932

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

INF
Semantics
Reception of the
signal#1
27
Auxiliary input1
generated at an
Aux. contact
Reception of the
signal#2
28
Auxiliary input2
generated at an
Aux. contact
Reception of the
signal#3
29
Auxiliary input3
generated at an
Aux. contact
Reception of the
signal#4
30
Auxiliary input4
generated at an
Aux. contact
Supervision of the
Measurand
current of the
32
supervision I
zero-sequence and
the CT error
Supervision of the
Measurand
33
voltage of the
supervision V
zero-sequence
Supervision of the
Phase sequence
35
voltage of the
supervision
negative-sequence
Trip
circuit
Supervision of a
36
supervision
trip circuit
Status on the OC
I>>
back-up
37
relay being in DT
operation
mode
38
VT fuse failure
VTF
Tele-protection
Communication
39
disturbed
fail
46
Group warning
minor error
47
Group alarm
serious error
Earth
48
Earth Fault L1
phase-A
Earth
49
Earth Fault L2
phase-B
Earth
50
Earth Fault L3
phase-C
Earth
Fault
Earth fault in the
51
Fwd, i.e. line
forward direction
Type
Contents
GI
ID
OK
1
OK
1
OK
1
OK
1
OK
1
OK
1
OK
1
OK
1
OK
1
OK
1
OK
1
OK
1
OK
1
fault
in
OK
1
fault
in
OK
1
fault
in
OK
1
OK
1
- 918 -
COT
Function_ID
11
12
Issued by the general commands described later.
1, 9
1, 9
1, 9
1, 9
0x2218C1
1, 9
(CHK_CT_CBP)
0x221BC1
1, 9
(CHK_VZ_CBP)
0x221AC1
1, 9
(CHK_V2_CBP)
1, 9
1, 9
1, 9
Not supported in GRB200 IED
1, 9
Not supported in GRB200 IED
0x220001
1,9
(MNT_LOGIC)
0x220001
1, 9
(MNT_LOGIC)
1, 9
Not supported in GRB200 IED
1, 9
Not supported in GRB200 IED
1, 9
Not supported in GRB200 IED
1, 9
Not supported in GRB200 IED
6F2S1931 (0.20)
GRB200
Data_ID
; DPI Off: On=1: 2
No default setting.
No default setting.
No default setting.
No default setting.
2218C1 32100011B0
(CTTFRES)
; DPI Off: On=1: 2
221BC1 32100011B0
(CVZRES)
; DPI Off: On=1: 2
221AC1 32100011B0
(CV2RES)
; DPI Off: On=1: 2
No default setting.
No default setting.
220001 3110121001
(MINR_ERR)
; DPI Off: On=1: 2
220001 3110111001
(SERI_ERR)
; DPI Off: On=1: 2
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grb200

Table of Contents