Output Lead Set Ratings; Metering - T&R PCU2 mk5 Operating And Maintenance Manual

Primary current injection system
Table of Contents

Advertisement

1.2.3

Output Lead Set Ratings

The optional 3000AL, 4000AL, 5000AL, 6000AL lead sets supplied for use with the PCU2 are
made up from a number of 70mm
ratings. The rating is also affected by the arrangement of the individual 70mm
up the high current cable. The leads are supplied with the cables strapped together, but to
achieve their maximum rating the straps must be cut and the cores laid out side by side whilst
testing.
Lead set type
3000AL
4000AL
5000AL
6000AL
8000AL
CAUTION
The cables and terminals will become hot in use. Ensure adequate cooling time is allowed
before touching cables or connectors after tests.
Note:
The output leads should not be rested against any sharp edges whilst testing. The insulation
on the cables softens as it heats up, and it is possible for sharp edges to damage the
insulation on the cable under these circumstances. Eddy current heating may occur in ferrous
metals that the pair of cable rests against, and this could heat the cable insulation further.
1.2.4

Metering

The output current is metered by a digital memory ammeter with an LED display. The current
reading is continuously updated when the output is energised, and the value held when the
output is de-energised.
In timing modes where the contact inputs are used to signify the end of a test, the last valid
current measurement before the contacts changed state is held. This also occurs when using
the current operated timer mode.
The ammeter's minimum response time is 200ms to capture a reading. If the duration of the
current is less than 200ms the ammeter's display will display "Err".
2
cores and have different continuous and intermittent
Continuous rating
Cores strapped
Cores laid out
together
1200A
1400A
1600A
1800A
1800A
11
5 minute on/ 15
minute off rating
Cores strapped
flat
together
3000A
1500A
4000A
2000A
5000A
2500A
6000A
3000A
6000A
3000A
2
cables making
1 sec on/ 1
minute off
rating
Cores strapped
together
6000A
8000A
10000A
12000A
12000A