1MRK 511 403-UEN Rev. L
Step No.
6-b
6-c
* - CT ratios of the phase currents (1000/1 A) and unbalance currents (10/1 A). The values of IB1 and IB2 are
considered as 1000 A and 10 A, respectively. The current inputs I
inputs and I
To calculate IREFUNBL1 in
IREFUNBL1
IECEQUATION19378 V1 EN-US
To calculate IUNBCLCL1 in
IUNBCLCL1 IUNBL1 IREFUNBL1
IECEQUATION19377 V1 EN-US
Testing with 3 Unbalance Curr option
1.
Set the following parameters:
2.
The logical signals and service values for SCUCPTOC function are available on the local HMI
under: Main menu/Tests/Function status/Unbalance protection /
CapBankCurrentUnbalance(60N, Iub>)/SCUCPTOC(60N, Iub>):x/outputs , where x =
instance number.
3.
To store the unbalance current values, perform these steps:
Bay control REC670
Commissioning manual
Changes after step 5
Change I
= 0.45∠0° A
UNBL1
Change I
= 0.55∠0° A
UNBL1
refers to the unbalance current inputs.
UNBL1
Step
5-c, use the following equation:
IL1
=
´
IMEMUNBL1
IMEML1
Step
6, use the following equation:
=
-
The measured unbalance current is referred with respect to its reference current.
Refer Technical manual for more information about unbalance current calculation.
Operation = ON
SCBConf = 3 unbalance curr
tDefTrip = 5.00 s; tDefAlm = 5.00 s; tDefWrn = 5.00 s
IUnbal> = 30% IB2
IUnbalAlm> = 20% IB2
IUnbalWrn> = 10% IB2
IMin = 10% IB1
© 2017 - 2022 Hitachi Energy. All rights reserved
Expected output
ALARM and ALML1 signals should become HIGH after
the set time delay
IUNBL1 = 4.5 A
IUNBCLCL1 = 2.5 A which is equivalent to 25% of
IBase2
START and TRIP TEST
START and STL1 signals should become HIGH
TRIP and TRL1 signals should become HIGH
after the set time delay, if BlockTrip is set to Trip
enabled
IUNBL1 = 5.5 A
IUNBCLCL1 = 3.5 A which is equivalent to 35%
of IBase2
, I
, and I
L1
L2
Section 11
Testing functionality by secondary injection
refer to the phase current
L3
(Equation 26)
(Equation 27)
GUID-C028CACA-D487-4DD1-B7CA-92219F3A41F0 v1
133

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec670

Table of Contents