Direct, indirect & solar unvented cylinder (48 pages)
Summary of Contents for joule Victorum Compact 73310033
Page 1
Victorum Pre-Plumb & Victorum Compact Exhaust Air Heat Pump Installation & Maintenance Manual REGISTER THIS PRODUCT ONLINE WITHIN 28 DAYS OF COMMISSIONING IRELAND www.joule.ie/register-a-product UNITED KINGDOM ENG-0014-7 www.jouleuk.co.uk/register-a-product Victorum Exhaust Air Heat Pump Installation Guide...
Page 2
Commissioning Company Date Address Location of Exhaust Air Heat Pump. Serial No. Contact Tel. Contact Email General Checks Has the system been installed in accordancewith manufacturer’s requirements? Type of ductwork installed Rigid Radial Rigid Flat-pack Semi Rigid www.jouleuk.co.uk | www.joule.ie...
Page 3
System Recording Air Flow Measurement - Extract Design Air Flow Measured Air Flow Measured Air Flow Design Air Flow Room Reference High Rate (l/s) High Rate (l/s) Low Rate (l/s) Low Rate (l/s) Kitchen Utility Bathroom En Suite Heating System Expansion Vessel Test Pressure Fill Pressure...
Page 4
Has an electrical isolation switch been installed? Has the correct size power cable been used for exhaust air heat pump? See Page 12 for cable requirements NO Pre Paid Meters are to be installed on a Victorum Exhaust Air Heat Pump System www.jouleuk.co.uk | www.joule.ie...
Page 5
Installation Checklist Ventilation System Total floor area of dwelling? Total installed equivalent area of background ventilators in dwelling? Does the total installed equivalent ventilator area meet the requirements given in Section 1.2 of TGD F? Have all background ventilators been left in the open position? Have the correct number and location of extract fans/terminals been installed that satisfy relevant Table of Tables 1, 2 and 3 of TGD F? Is the installation complete with no obvious defects present?
In order to prevent electric shocks, fires or injuries, always stop the unit, disable the protection switch and contact Joule’s technical support if the unit produces smoke, if the power cable is hot or damaged, or if the unit is very noisy.
• Power supply to heat pump to be terminated with with a suitable isolator located next to the unit. • Pre-moulded communication cable from Heat Pump unit to the pre-plumbed unit (Supplied by Joule) Communication Location Heat Pump Breaker Size...
The Heat Pump duct connections are Ø150mm. Flat Pack, Round or Semi Rigid duct is acceptable however, the cross sectional area must not be reduced; it must be maintained or increased to avoid noise in the duct system. www.jouleuk.co.uk | www.joule.ie...
Transport & Handling Handling Instructions • Care must be taken when transporting, storing and installing the Heat Pump. • The Victorum unit is delivered fully packaged and fixed to a wooden pallet base. Care should be taken when transporting the Heat Pump ensuring that the unit is not damaged by impact.
300mm min 500 min 150mm min Min. 10 mm (When using the top connection for incoming ventilation air) Min. 300 mm (When using the side connection for incoming ventilation air) www.jouleuk.co.uk | www.joule.ie...
Mounting the Heat Pump Wall Mounted The Victorum can only be hung on a smooth wall capable of holding a mass of 200kg/m². If the mass is lower than this, ensure the recommended wall build-up is adhered to. The Victorum should always be hung level however there is a permitted tolerance of 2°.
The build-up also incorporates a sheet of 3/4” plywood fixed directly to the stub before the plasteboard is used as the standard wall finish. Description Part No. Victorum Rubber Damper Bottom Circle TZV-MOUNT00-B Joule Victorum Vhp (Ie) HHH-0-0000-VHP Victorum Wall Bracket TZ-W-00-COMP-1 400mm Timber Noggin Concrete Floor Slab ¾”...
Page 19
Wall Build Up Detail Victorum Exhaust Air Heat Pump Installation Guide...
220mm x 90mm flat pack ducting must terminate with a double air brick. All ductwork insulation MUST be fully sealed at all joints, transitions, air bricks and/or roof cowls. www.jouleuk.co.uk | www.joule.ie...
Page 23
Connecting the Heat Pump Ventilation Connection Ductwork – Insulation Specification Provision of insulation to ducts and pipes, in accordance with the standards specified in BS 5422:2009, should adequately limit heat loss or heat gain, as appropriate. Ductwork – Unheated Spaces Any ductwork passing through an unheated space must be suitably insulated to avoid condensation and/or heat loss or heat gain.
Piping Sizing, positioning and pre-charge pressure of the heating system expansion vessel The Exhaust Air Heat Pump does not have an expansion vessel incorporated. The installer must ensure the system is protected from the effects of expansion by installing a suitably sized expansion vessel.
0.5 bar. If the difference in height increases or decreases, then an additional charge pressure will be required. Use the formula below to calculate the additional charge and add this to the pre-charge pressure: )= ( (1 0+ 0.3) www.jouleuk.co.uk | www.joule.ie...
Piping Filling & Venting Follow the steps below to Fill and Vent the system in the correct order: Ensure all system valves are open fully. Fill the system using the incorporated filling loop to the recommended pressure (min 1.0 bar – max 1.5 bar). While filling the system, air should be released via the manual or automatic air vents within the system.
Page 28
Valve C is now opened to allow for normal system operation. The fill and flush pump may now be switched off and the hoses disconnected. The blanking caps can now be replaced on Valves A & B. www.jouleuk.co.uk | www.joule.ie...
Piping Connecting the Drain Hose The Exhaust Air Heat Pump absorbs heat from the extracted indoor air. The moisture in the air condenses on the cold evaporator. The condensation water must be drained from the unit to allow the unit to function normally. That is why the Heat Pump must be connected to a drain pipe. The end of the drain hose must not protrude below the water level of the siphon.
Option 1 2 Core Flex 0.75mm Option 2 CAT 6a (SFTP), Supplied by Joule During the unit installation first make the ventilation connections, then the piping connections and then electrical connections. If unit is uninstalled disconnect the unit in the reverse order.
Check all connections and the mains voltage is correct before powering On the Heat Pump to prevent damage to the Heat Pumps electronics.’ • If the power cable is damaged, contact Joule to have it repaired before powering On the Heat Pump. •...
5 (bar) Test Pressure 10 (bar) Max. Working Temperature 90°c 1. No. Incoloy Heating Elements Immersion Heat Loss 78 W 87 W Heat up Time (mins) Energy Efficiency Class C Height (mm) 1490mm 1405mm Diameter (mm) 530mm 600mm www.jouleuk.co.uk | www.joule.ie...
Product Overview Preplumb Pipework Upon filling and commissioning, ensure all connections are completely watertight. Victorum Exhaust Air Heat Pump Installation Guide...
All exposed pipework must be insulated. The unit must be installed upright on a base capable of supporting its weight when full (please see the technical specification section for weights). 400mm Clearance www.jouleuk.co.uk | www.joule.ie...
Installing the unit Moving the PrePlumb unit Select the moving route in advance. Be sure that moving route is safe from weight of the cylinder. Moving the PrePlumb unit with a fork lift. Insert the fork into the wooden pallet at the bottom of the cylinder carefully.
The installer must ensure the system is protected from the effects of expansion by installing a suitably sized expansion vessel. Refer to section ‘Sizing, positioning and pre-charge pressure of the heating system expansion vessel’ for vessel sizing. www.jouleuk.co.uk | www.joule.ie...
12” (15mm) cold mains pipework to a larger size if the recommended minimum pressure / flow rateis not being achieved. Joule™ recommend that primary pipework used has a minimum diameter of 22mm to ensure low pressure loss.
Before beginning to fill the heating system ensure all components are installed and respect any recommended direction of flow. Ensure all connections are water tight and sound. It is recommended to check the pre-charge pressure of the heating expansion vessel before filling the system and to adjust it if necessary. www.jouleuk.co.uk | www.joule.ie...
Commissioning Filling & Venting Follow the steps below to Fill and Vent the system in the correct order: Ensure all system valves are open fully. Fill the system using the incorporated filling loop to the recommended pressure (min 1.0 bar – max 1.5 bar). While filling the system, air should be released via the manual or automatic air vents within the system.
Page 40
Valve C is now opened to allow for normal system operation. The fill and flush pump may now be switched off and the hoses disconnected. The blanking caps can now be replaced on Valves A & B. www.jouleuk.co.uk | www.joule.ie...
Temperature & Pressure Relief Valve Connect the tundish and route the discharge pipe which must be routed in accordance with Build- ing Regulations - Part G3 of schedule 1. When operating normally water will not be discharged from the temperature and pressure relief valve. Water discharge from the temperature and pressure valve will only occur under fault conditions.
Electrical Overview Victorum Compact Power Supply The table below outlines the power requirements for the Victorum Compact Pre-Plumb unit. Volts Phase Victorum PrePlumb Single Power Supply Cable Entry All electrical wiring must be carried out by a competent installer and be installed in accordance with current local Wiring Regulations.
The exterior wall material must be considered, as materials like Zinc can act as a heat sink. This can affect the sensor reading, producing higher readings. The outdoor sensor requires a two core 0.75mm2 cable and it is not polarity sensitive. The sensor is connected to ‘B1’ and ‘Gnd’ on the controller. www.jouleuk.co.uk | www.joule.ie...
Electrical Outdoor Sensor Controller Connecting the Touchscreen The entire system is controlled via the Touchscreen- heating, hot water and ventilation. The touchscreen is typically installed in the living area (zone 1), where it also acts as the temperature sensor for that zone. The recommended location for the touchscreen is 1.5m off the floor and kept away from sources of heat and/or cooling like radiators, drafts or...
Pre-Plumbed Cylinder unit. The heating signal enable is to be wired using a two core 0.75mm2 cable and it is NOT polarity sensitive. The sensor is connected to ‘DI1’ and ‘Gnd’ on the controller. www.jouleuk.co.uk | www.joule.ie...
Product Specification The Victorum Compact is a pre-plumbed and wired unit containing the Victorum Exhaust Air Heat Pump in a cased white good. On the mechanical side, the Compact unit incorporates the hot water tank, an inline heater, automatic air vent, DHW & heating zone valves, an automatic bypass valve and a 3-bar safety relief valve.
Transporting the unit Transport and Handling The Victorum Compact unit is delivered fully packaged and fixed to a wooden pallet base. Care should be taken when transporting the unit ensuring that the casing is not damaged by impact. At least two people should lift the unit to prevent injuries.
Installation space Ensure to leave the appropriate space as indicated in the drawing. Installation site should be secured with adequate ventilation so that the components of indoor unit will not be damaged from overheating. www.jouleuk.co.uk | www.joule.ie...
Assembling the Heat Pump Adjusting the feet Position the bottom section of the Victorum Com- pact on a suitable base that can take the weight of the unit. Use the product’s adjustable feet to en- sure the Heat Pump is level and stable. The adjust- ment is approx.
The two sections are fixed together using the screws provided. The screws are inserted in the underside of the top section, at the front of the unit. www.jouleuk.co.uk | www.joule.ie...
Connecting the Heat Pump Air Out (Exhaust) Terminal The air Out (Exhaust) terminal size is 150mm. Air In (Extract) Terminal The air In (Extract) terminal size is 150mm. Air In Spigots are supplied with the unit and these are needed to connect a flexible duct to the top of the unit.
The drain pipe terminates in the bottom section beside the Tundish on the left hand side. It is the installers responsibility to connect the drain pipe to a suitable location to allow sufficient drainage from the unit. www.jouleuk.co.uk | www.joule.ie...
Piping Heating System Pipe Connections The heating zone valves are pre-installed along with the expansion vessel (8L), pressure relief valve (3 bar), filling loop and backup heater (3kW). Connect the flow pipe from the applicable zone to the corresponding zone valve. The zone valves are labelled in the image below.
Consideration should be given to upgrading existing 12” (15mm) cold mains pipework to a larger size if the recommended minimum pressure / flow rate is not being achieved. Joule™ recommend that primary pipework used has a minimum diameter of 22mm to ensure low pressure loss.
Piping Potable Expansion Vessel The expansion vessel receives the increased Potable Expansion Vessel water volume when expansion takes place as the system heats up and it maintains a positive Hot Water Outlet pressure in the system. The expansion vessel contains a flexible diaphragm, which is initially charged on one side with nitrogen, but can be topped up with air when required.
Valve C is turned to the closed position (90° to the pipe direction). Open valves A and B and switch on the fill & flush pump. Water is circulated through the system for a minimum of 45 minutes. www.jouleuk.co.uk | www.joule.ie...
Page 59
Commissioning In this time, the individual circuits can be flushed seperatly (DHW, Zone 1, Zone 2, etc). To flush a circuit, first the zone valve for the circuit must be manually opened. This allows circulation of water through the open circuit. While flushing a circuit, it is essential to flush each emitter separately.
0.8m 1.4m 1.0m 1.4m 1.7m 1.4m 1.7m 2.3m the discahrge pipe Sizing of copper discharge pipe (D2) for a temp, relief valve with a G1/2 outlet size (as supplied) www.jouleuk.co.uk | www.joule.ie...
Page 61
Temperature & Pressure Relief Valve Examples of Discharge Arrangements Left Side Pipe Exit Front View Side View Right Side Pipe Exit Front View Side View Victorum Exhaust Air Heat Pump Installation Guide...
Electrical DC Power G*** Temp Sensor Description Description H1 Immersion Joule Electrical Enclosure PrePlumb Unit H2 Back up Heater Heat Pump V1 DHW Valve Outdoor Sensor V2 Heating Zone valve 2 2nd Zone Sensor V3 Heating zone valve 1 Touchscreen RJ45 BOSS system connection www.jouleuk.co.uk | www.joule.ie...
Electrical Overview Victorum Compact Power Supply The table below outlines the power requirements for the Victorum Compact Pre-Plumb unit. Zones Volts Phase HXVC-PP-011 Single HXVC-PP-012 Single Power Supply Cable Entry All electrical wiring must be carried out by a competent installer and be installed in accordance with current local Wiring Regulations.
The exterior wall material must be considered, as materials like Zinc can act as a heat sink. This can affect the senor reading, producing higher readings. The outdoor sensor requires a two core 0.75mm2 cable and it is not polarity sensitive. The sensor is connected to ‘B1’ and ‘Gnd’ on the controller. www.jouleuk.co.uk | www.joule.ie...
Electrical Outdoor Sensor Controller Connecting the Touchscreen The entire system is controlled via the Touchscreen- heating, hot water and ventilation. The touchscreen is typically installed in the living area (zone 1), where it also acts as the temperature sensor for that zone. The recommended location for the touchscreen is 1.5m off the floor and kept away from sources of heat and/or cooling like radiators, drafts or...
Pre-Plumbed Cylinder unit. The heating signal enable is to be wired using a two core 0.75mm2 cable and it is NOT polarity sensitive. The sensor is connected to ‘DI1’ and ‘Gnd’ on the controller. www.jouleuk.co.uk | www.joule.ie...
Gravity Cold Outlet - Cold Water Tank Heating Circuit Safety Relief Valve Mains/ Boosted Supply Inlet Balanced Cold Outlet Expansion vessel Tundish Common Heating Zones Return C Primary Return Heating Zone 2 Flow Heating Zone 1 Flow Hot Water Outlet Primary Flow www.jouleuk.co.uk | www.joule.ie...
Transporting the unit Transport and Handling The Victorum Combi unit is delivered fully packaged and fixed to a wooden pallet base. Care should be taken when transporting the cylinder unit ensuring that the casing is not damaged by impact. At least two people should lift the cylinder to prevent injuries.
Installation space Ensure to leave the appropriate space as indicated in the drawing. Installation site should be secured with adequate ventilation so that the components of indoor unit will not be damaged from overheating. www.jouleuk.co.uk | www.joule.ie...
Piping Piping The Preplumbed Combi unit consists of a 220 litre cold-water storage cistern and a 180 litre pressurised hot water storage tank. The Combi unit is designed to be installed alongside a booster pump so the hot and cold services within the dwelling are pressurised.
The water supply should be checked to ensure it can meet these requirements. If necessary, consult the booster pump’s datasheet regarding the likely pressure and flow rate available. Joule™ recommend that the pipe connection sizes on all components are respected and not reduced. This will ensure low pressure loss.
Piping Balanced Cold Outlet The Balanced Cold outlet connection is incorporated into the inlet control group. The connection is designed to supply all cold outlets within the dwelling, and it ensures that all cold and hot water pressures and flows are balanced. This is critical for mixing showers and taps to provide accurate mixing of the supplies, otherwise mixing can be difficult to achieve.
The PrePlumb unit does not have an expansion vessel incorporated. The installer must ensure the system is protected from the effects of expansion by installing a suitably sized expansion vessel. Refer to section ‘Sizing, positioning and pre-charge pressure of the heating system expansion vessel’ for vessel sizing. www.jouleuk.co.uk | www.joule.ie...
Commissioning Filling the Cold-Water Storage Cistern Before beginning to fill the cold-water storage cistern check all the connections for water tightness including any factory-made connections such as the ball cock and drain valve. The orientation of the ball cock and float should be checked as misalignment will result in the valve not closing correctly and water being expelled from the overflow connection.
Valve C is turned to the closed position (90° to the pipe direction). Open valves A and B and switch on the fill & flush pump. Water is circulated through the system for a minimum of 45 minutes. www.jouleuk.co.uk | www.joule.ie...
Page 77
Commissioning In this time, the individual circuits can be flushed seperatly (DHW, Zone 1, Zone 2, etc). To flush a circuit, first the zone valve for the circuit must be manually opened. This allows circulation of water through the open circuit. While flushing a circuit, it is essential to flush each emitter separately.
0.8m 1.4m 1.0m 1.4m 1.7m 1.4m 1.7m 2.3m discharge pipe Sizing of copper discharge pipe (D2) for a temp, relief valve with a G1/2 outlet size (as supplied) Image below shows the position of the tundish outlet. www.jouleuk.co.uk | www.joule.ie...
Electrical Pre Installed by Joule Installer to connect Only required for local Outdoor sensor Only required for 2 heating zone systems G*** * * * Required if BOSS system installed Description Item Codes Description Item Codes H1 Immersion Joule Electrical Enclosure...
Connect the ‘Protective Earth’ line with the Earth terminal inside the electrical enclosure. The rear casing of the electrical enclosure is the termination point for all Protective Earth Connections. Please use the earth termination points provided. www.jouleuk.co.uk | www.joule.ie...
Electrical Overview Connecting the Outdoor Sensor The Outdoor Sensor monitors the outside air temperature and is installed on the exterior of Outdoor Sensor Controller the dwelling on a north facing wall, if possible. Otherwise, the sensor must be kept away from direct sunlight.
Zone 2 room sensor- installation height, avoiding heat sources, etc. The second zone sensor requires a two core 0.75mm2 cable and it is not polarity sensitive. The sensor is connected to ‘B4’ and ‘Gnd’ on the controller. www.jouleuk.co.uk | www.joule.ie...
Electrical Communication Cable – Heat Pump to Pre-Plumbed Cylinder unit The communication cable between the Heat Pump to Pre-Plumbed Cylinder unit is supplied in the kit with the Cylinder unit. It is a pre-molded Controller Heatpump Ethernet cable and does not require and alteration.
C – Flow to UFH manifold 3 – Flow temperature sensor D – Return from UFH manifold When the valve is installed, the spindle position must be set to match the installation orientation. Spindle Identifier Clockwise Counter Clockwise www.jouleuk.co.uk | www.joule.ie...
Page 85
Victorum EAHP UFH ESBE electronic mixing valve Mount the controller using the fixings provided. Victorum Exhaust Air Heat Pump Installation Guide...
Page 86
Victorum EAHP UFH ESBE electronic mixing valve NOTE: Orientation of the valve body and controller actuator must be respected. Fix the Flow temperature sensor to a metal pipe upstream of the UFH circulating pump. Use the aluminium tape provided. www.jouleuk.co.uk | www.joule.ie...
Victorum EAHP UFH ESBE electronic mixing valve Setup Set the working direction of the controller by pressing the joystick to right for clockwise opening or left for counter clockwise opening (A). Keep the joystick in the desired direction and connect power (B). Wait 2 seconds until joystick is released (C), the correct working direction is now set 230V —...
Set the pump control mode (A), using the operation button (B). The speed setting is indicated by the LED (C). Check the Delta T across the Heat Pump is 5 (CH-flow - CH-return = 5). Temperature Air-in 20.0 Air-Out Evaporator CH-flow 35.4 CH-return 30.4 www.jouleuk.co.uk | www.joule.ie...
Victorum EAHP UFH ESBE electronic mixing valve Setting the differential by-pass valve Setting the differential by-pass valve is essential in ensuring the Heat Pumps internal circulating pump has a clear circuit and does not dead head. This would lead the Heat Pump to overheat and damage the pump.
Replace Fileter In Used Today 365 days 0,00 kWh Time 11 30 Settings Boost Timer Sensor Fault Time Boost On Error Code: 51 Call your Installer Time Heatpump On Replace lter in 06 30 365 days Purge Purge? www.jouleuk.co.uk | www.joule.ie...
Page 91
Victorum EAHP Menu Overview Login Temperature Temperature Settings Fault History Air-in Error Air-out Error Evaporator Error CH- ow Error CH-return Error Status Fault history Trickle Rate Adjust air Valves? Error on Air ow 08-01-200 05.56 120 m /hour Error VHP/Boost rate 150m /hour Error Code...
10, using the plus and minus buttons. Trickle Rate Once the airflow has been selected, you will be prompted to save the changes. Pless Yes to 120 m hour save and No to cancel. www.jouleuk.co.uk | www.joule.ie...
Victorum Setup – Installer Functions Setting the Boost air flow rate Settings To set the Boost air flow rate, press the Settings icon on the second Settings tile and scroll to the right to the VHP/Boost Rate setting. VHP/ Boost rate Here the Boost Rate for the dwelling is set.
NOTE: the process takes 2 minutes to complete. The first minute is used to measure and set the Trickle fan speed. The second minutes is used to measure and set the Boost fan speed. www.jouleuk.co.uk | www.joule.ie...
Victorum Setup – Date & Time Setting the correct date and time is important for the correct operation of the unit. To access the Date and Time settings, navigate to the spanner icon on the home screen. Next, scroll to the right to the Time tile and press Time the icon.
Blocking No Temp diff across Evaporator Check fan operation or a possible Heat Pump Reset Itself. Please wait blockage in the duct system *Temporary blocking of the Heat Pump. The Heat Pump automatically restarts after 1 hour www.jouleuk.co.uk | www.joule.ie...
Error Codes & Troubleshooting The second type of warning icon looks like this. This icon means that the Victorum EAHP is locked and out of operation. Only an installer can manually override this lock. Warning Screen Error Code Error Meaning Possible Solution Compressor locked Remove error 80...
01234567 Serial no: 1234567 On the type plate you will find the serial number. Manufacturer: Joule IE Unit 407 Northwest Business Park This is a unique number to the machine you are installing. This number will be required during the...
Maintenance & Servicing Planning And Organising Your Project The design and operation of an exhaust air heat pump system has a direct link to its output and efficiency. Consideration should be given to heating and ventilation at an early stage in any project as the system requires to be integrated with construction and building project process.
Ensuring control parameters are still set correctly and that there are no heat pump errors. Air Distribution System - 2 Years • Inspection of duct work where possible. • Check air flow rate on all ceiling extract valves. www.jouleuk.co.uk | www.joule.ie...
Filter Replacing the Filter For the unit to continue to operate at its optimum it is required to maintain and change the filter periodically. There is a reminder on the Victorum controller to change the filter once every year.. 1. Remove the Victorum cover. 2.
There are no warranties, which extend beyond the face of this document. No agent or representative of Joule has any authority to extend or modify this warranty unless such extension or modification is made in writing by a corporate officer.
Page 104
2-year warranty •It has not been misused, tampered with or from the date of purchase of the Joule product subjected to neglect; which includes one year’s parts and labour and •The system is fed from the public mains water...
Page 105
Please note that invoices for servicing may be requested to prove that the unit has been serviced annually. Joule fully endorse the Benchmark scheme and the code of practice can be obtained from www.centralheating.co.uk Warning To The User •Do not remove or adjust any part of this un-...
Page 120
PRODUCT FICHE (ENERGY LABELLING OF PACKAGE OF COMBINATION HEATER) Supplier's name or trademark Joule Supplier's model identifier Victorum HW 7784292 / µPC3 / Joule 200L H.G Cyclone Variant models Compact 62210022, Compact 62210018 Preferential heater Seasonal space heating energy efficiency class (Average) Seasonal space heating energy efficiency (Average) 148.5...
Page 121
Joule Ireland, Unit 407 North West Business Park, Cappagh Road, Dublin 11, Ireland. D11 HD36 Contact details (*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh , and the rated output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj) .
Page 122
Joule Ireland, Unit 407 North West Business Park, Cappagh Road, Dublin 11, Ireland. D11 HD36 Contact details (*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh , and the rated output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj) .
Page 123
Standby cylinder heat loss 2.064 Joule Ireland, Unit 407 North West Business Park, Cappagh Road, Dublin 11, Ireland. D11 HD36 Contact details (*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh , and the rated output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj) .
Page 124
Standby cylinder heat loss 2.064 Joule Ireland, Unit 407 North West Business Park, Cappagh Road, Dublin 11, Ireland. D11 HD36 Contact details (*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh , and the rated output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj) .
Page 125
Heat Pump Water Heater Product Reference: Victorum 73310033 & Joule 200L Cyclone to which this declaration relates is in conformity with the essential requirements and other relevant requirements of Directive 2009/125/EC on the Ecodesign of energy related products. The product is...
Page 126
Water heating energy efficiency (Warmer) Annual electricity consumption (Colder) Annual electricity consumption (Warmer) Precautions as described in the installation/user manual must be taken when assembling, installing and maintaining this product Applicable date: 07/09/2020 Revision: Document Control No. COM0037 www.jouleuk.co.uk | www.joule.ie...
Page 127
ERP Information COMMISSION REGULATION (EU) No. 812/2013 Technical Documentation - Heat Pump Water Heater Contact details: Joule Ireland, Unit 407 North West Business Park, Cappagh Road, Dublin 11, Ireland. D11 HD36 Model: Victorum 73310033 Harmonised Standards: Commission Delegated Regulation (EU) No 813/2013...
Need help?
Do you have a question about the Victorum Compact 73310033 and is the answer not in the manual?
Questions and answers