Circuit breakers with communication capability - profibus (286 pages)
Summary of Contents for Siemens SIMATIC PN
Page 1
___________________ PN/PN coupler Preface ___________________ Description ___________________ Assembling SIMATIC ___________________ Connecting Bus links Configuring and ___________________ PN/PN coupler commissioning ___________________ Functions Installation and Operating Manual ___________________ Operating ___________________ Diagnostics ___________________ Technical data Order numbers and ___________________ accessories ___________________ Dimensional drawings 06/2010 A5E00717043-04...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
STEP 7 ● Knowledge of working with . This is gained from the Programming with STEP 7 V5.4 (http://support.automation.siemens.com/WW/view/en/18652056) manual. Scope of manual The manual applies to the PN/PN coupler V3.0 with order number 6ES7158-3AD01-0XA0. This manual contains a description of the components which were valid at the time the manual was published.
Page 4
Additional support If you have questions regarding use of the products described in these operating instructions, and do not find the answers in this document, contact your local Siemens representative. Your contact persons are listed in the Internet (http://www.siemens.com/automation/partner).
Page 5
SIMATIC S7 automation system. Please contact your regional training center or the central training center in D -90327, Nuremberg, Germany. You will find more information in the Internet (http://www.siemens.com/sitrain). Service & Support on the Internet In addition to our documentation, we offer a comprehensive knowledge base on the Internet (http://www.siemens.com/automation/service&support).
Description Application and function Application The PN/PN coupler is used to link two Ethernet subnets with one another and to exchange data. That way use data about input or output address areas or datasets can be used. The maximum size of the transferable input and output data is 1024 bytes. The division into input and output data is preferable, so that e.g.
Page 10
Description 1.1 Application and function Application examples for cyclic I/O data exchange between IO Controllers via a PN/PN coupler Figure 1-2 Cyclic data exchange between two I/O Controllers via IWLAN Figure 1-3 Cyclic data exchange between two I/O Controllers via a redundant ring Configuring You either configure the PN/PN coupler using STEP 7 or a configuring tool which uses a GSD file to integrate the PN/PN coupler.
Page 11
Description 1.1 Application and function Example The following example shows that both networks of independent of one another. They issue a unique device name for each PROFINET IO network. In the following picture this is called device names "subnet 1 and "subnet 2". Figure 1-4 Main FC of the PN/PN coupler (example) PN/PN coupler...
Description 1.2 View View Display elements and interfaces The following picture shows the PN/PN coupler and its display elements and interfaces: ① ⑥ PROFINET IO interfaces for subnet 1 (X1) Status LEDs for PROFINET IO subnet 1 (X1) ② ⑦ PROFINET IO interfaces for subnet 2 (X2) Status LEDs for PROFINET IO subnet 2 (X2) ③...
Description 1.3 Properties Properties Properties The PN/PN coupler has the following properties: ● Dataset transfer from an IO controller of one side to an IO controler of the other side. ● Data exchange of maximum 1024 bytes input data / output data with preferable division. ●...
Assembling Assembly rules Mounting position You can mount the PN/PN coupler in any position. Please note that the maximum ambient temperature for horizontal mounting positions is 60 °C while that for all other positions is 40 °C. You will find more information on operating conditions in Appendix Technical data (Page 79). Open component The PN/PN coupler is an open component.
Assembling 2.3 Disassembling the PN/PN coupler Assembling PN/PN coupler on DIN rail 1. Assemble the DIN rail such that there is enough space to assemble and heat the modules (at least 40 mm above and below the modules). If you want to swap the SIMATIC Micro Memory Card once the PN/PN coupler is assembled, you will have to leave additional space for this.
Assembling 2.4 Assembling-color plates Assembling-color plates Introduction The color-coding plates allow you to individually color code the PROFINET IO interfaces in accordance with company and national regulations. The color-coding plates are available in white, red, yellow, yellow-green, brown, blue and turquoise. You can provide every PROFINET IO interface on the PN/PN coupler with a color-coding plate.
Connecting Electrical isolation and grounding 3.1.1 Introduction Redundant 24 V DC power supply You can connect the PN/PN coupler to two independent 24 V DC power supplies. Only one 24 V DC power supply is ever active at any one time. If one power supply fails, the other automatically becomes active.
Connecting 3.1 Electrical isolation and grounding 3.1.2 General operating rules and regulations Introduction If they are part of plants or systems the modules described require adherence to specific rules and regulations depending on the application. The most important rules, which you must observe for safe integration into a plant or system, are listed below.
Need help?
Do you have a question about the SIMATIC PN and is the answer not in the manual?
Questions and answers