Summary of Contents for Siemens SINAMICS V50

  • Page 1 SIEMENS...
  • Page 2 Ensure that the prospective short-circuit current at the line terminal of the inverter does not exceed the breaking capacity (SCCR or Icc) of the protective device used. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 3 Ensure compliance with the limit values specified in the technical data during transport, storage and operation. Do not use any damaged devices. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 4 The digits and letters of the drive model number on the nameplate indicate information such as the product series, power supply class, power ratings and software/hardware versions.6SL3620-2YE36-0UB0 means this model can be used as 37kW heavy duty 45kW normal duty. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 5 37 kW to 250 kW (50 to 400 hp) SINAMICS V50 infrastructure drives for HVAC/Water/Wastewater Selection and ordering data SINAMICS V50 drives Degree of protection IP20/UL Open Type 380 ... 480 V 3 AC Configuration with line-side components (see right page) SINAMICS V50...
  • Page 6 If there is switch type reactive-power compensation capacitor or load with silicon control at the same power line, there will be high peak current flowing into drive power input circuit, causing the damage of the rectifier components. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 7 3.4. Motor Wiring It is forbidden to short circuit or ground the drive output terminals; otherwise the internal components of the drive will be damaged. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 8 The wire connecting the drive and the motor shall be as short as possible. The motor cable adopts 4-core cable, among which the grounding wire shall be one end grounded at the drive side, the other end connected to the motor enclosure. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 9 PE of the drive, and the signal cable shall be no longer than 50m. The wiring of TA/TB/TC shall be separated from wiring of other main circuit terminals. It is forbidden to short circuit the shielding layer and other signal cables or equipment. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 10 (1): Mounting direction and space installation diagram When installing multiple drives vertically upside and downside, the air deflector is required as figure above (2). SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 11 ‘P’ direction. Take off along the opposite direction. SINAMICS V50 Metal-sheet enclosure type A. The АС-in and AC-out of some drivers are at two sides of driver. Dismantling covert: dismantle the screw 1/2, open covert along ‘O’ direction, and take off it along ‘P’...
  • Page 12 Installation 4.4 Terminal description SINAMICS V50 - 6SL3620-2YE36-0UB0 ~ 6SL3620-2YE46-0UB0 Terminal diagram of main circuit Terminal Symbol Terminal description Grounding terminal PE R, S Single-phase AC input terminals R, S, T Three-phase AC input terminals (+), PB Terminals reserved for braking resistor...
  • Page 13 Installation 4.5 Control Terminal Wiring of SINAMICS V50 SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 14 Installation 4.6 SINAMICS V50 Standard configuration of control circuit terminals Type Termin Terminal function Technical specification Digital Optical-isolator input Frequency Multi-functional input range: 0 - 200Hz input terminals 1 -3 Voltage range: 0 - 24V Multi-functional input: same as X1 -...
  • Page 15 Max. parallel 127 No.s; 485 differential 485- SW3 select adapted resistor; negatives Max. Length 500m. (twisted shielding cable) 486 shielding Internal isolated with COM grounding Terminal strips with wiring example SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 16 Installation SINAMICS V50 Control Circuit Connection Wiring mode of analog input terminal T568B standard Pin No. Color Write/Orange Orange Greer/White Blue Blue/ While Green Brown/White Brown SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 17 4.7 Control board schematic drawing Control board schematic drawing Z: DIP switches CN3: Terminals 1 for options PCBA CN5: Terminal for drive PCBA Earthing: Earthing point of control PCBA SINAMICS V50 Control circuit periphery accessories selection Terminal Tightening Wire Terminal codes Type of Wire...
  • Page 18 Installation SINAMICS V50 DIP switch setting instruction Terminal Function Default I for current input(0/4-20mA); 0 - 10 V V for voltage input (0- 10V) I for current output(0/4-20mA); 0 - 10 V V for voltage output (0 - 10V) RS485...
  • Page 19 OPERATION AND APPLICATION Keypad The keypad of SINAMICS V50 series drives is the main unit of accepting command, displaying and modifying parameters. The LED keypad outline is as follows. LED keypad model name: BOP-3 SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 20 Run the drive under keypad operation mode. Stop the drive at running status; Reset STOP Stop/reset operation in the fault alarm status. Its function is limited to setting of code FE.02. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 21 Blinking: Current value is the setup PID value Digital display zone It is four-digit LED display. Be able to display setup frequency, output frequency, various monitoring data and alarm code. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 22 Operation and application Function code viewing and modification The keypad of the SINAMICS V50 drive adopts three levels menu structure to carry out operations such as parameter setting. The three levels are: Groups of function code (level-1 menu) Function code (level-2 menu)
  • Page 23 “0000”. Correct password should be input to unlock the protection status to enter FP group again. To disable this password protection, user need to input the correct password first and then change FP.00=0. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 24 Waiting for the rotary tuning completed (if the encoder with Z signal, users do not have to set the encoder pulse, encoder direction related parameters, these parameters can be gotten from rotary tuning, but need to set the related function of parameter. Resolver encoder(F3.46=3) SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 25 (120*f/P)-rated rotation speed, so the set rated rotation speed should be lower than motor synchronous rotation speed. A part of drivers of SINAMICS V50 can share DC common bus, please to contact our technic support engineer if you want to share DC common bus. While sharing bus, the master driver is АС-in and AC-out, connect the DC bus of the slaver driver to the...
  • Page 26 6.0. Group 0 Basic Function F0.00 Reserved Range: Drive type display 0-1 [0] This parameter of SINAMICS V50 is reserved. 0: Type G (Heavy duty) 1: Type P (Normal duty) F0.01 Control mode Range: 0 - 2 [0] 0: No vector Sensor vector control-1 This mode offers excellent vector control performance while insensitive to motor parameters.
  • Page 27 7: PID When PID is selected to be reference, Group F8 “PID Parameters” shall be set. The running frequency of the drive is the value after PID regulation. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 28 The adjustment of carrier frequency will have influences on motor noise, motor temperature rising, and drive temperature rising as shown. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 29 F0. 17 Keypad direction Range: 0 - 1 [0] This parameter is used to select the motor rotation direction when the drive running command channel is keypad. 0: Forward rotation 1: Reverse rotation SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 30 Acc/Dec time 2-4 can be defined in F2.03—F2.08. User can select different Acc/Dec time by external multifunction input terminal. Acc.1/Dec.1 is taken as default. Schematic diagram for acceleration/deceleration time SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 31 DC brake F1.10 waiting time 0.00~10.00s 0.00s 020AH at stop DC brake 0.0~100.0% rated F1.11 current at 0.00% 020BH current stop DC brake F1.12 0.0~30.0s 0.0s 020CH time at stop SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 32 Waiting time F1.16 0.0~3600s 2.0s 0210H for restart Rotational speed 0: Disable F1.18 tracking 0212H 1: Enable direction inspection Rotational speed tracking F1.19 10~1000ms 50ms 0213H direction inspection time SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 33 1: Enable 0: Disabled 1: Enabled F2.17 AVR Function 0311H 2: Disabled only at speed-down Over 0: Enabled F2.18 0312H modulation 1: Disabled F2.19 Droop control 0.00~10.00Hz 0.00Hz о 0313H SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 34 1: FWD/REV switching ENTER key F2.26 2: RUN for 031AH о function forward; Enter for reverse; STOP for stop 3: Jog running 0: 0.01Hz F2.27 Freq. resolution 031BH 1: 0.1Hz SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 35 31DH 1: Synchronous mode modulation 0: According to IO output Freq. the Freq. after baseline select F2.31 ACC/DEC speed о 031FH while vector 1: According to control the current value SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 36 (7-stage mode) Threshold value F2.33 of Zero Freq. 0.00~550.0Hz 0.00Hz о 0321H running Range between start Freq. and F2.34 0.00~550.0Hz 0.00Hz о 0322H threshold value of Zero Freq. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 37 0: Torque control Disabled 1: Torque digital setting F3.10 Torque control (F3.11) о 040AH 2: AI1 3: AI2 4: Pulse 5: Comm. Torque digital F3.11 0.0~200.0% 50.00% 040BH о setting SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 38 1: Enable selection Torque limit compensation F3.22 coefficient 30.0~300.0% 200% о 0413H while constant power output F3.23 Reserved Reserved Reserved Reserved Torque ref. F3.24 terminal single 0.0~10% 0.00% о 0418H modulation SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 39 Initial position F3.33 detection 0~1200us о 0421H pulse width Initial position detection F3.34 0~1200us 0422H pulse width actual value Synchronous F3.35 motor braking 0.0~300.0% 150.0% 0423H о torque limit SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 40 V/F Start F3.43 switching 0~50.00Hz 0.00Hz 042BH о frequency Synchronous motor position F3.44 2~100 о 042CH evaluating low speed filter Synchronous motor position F3.45 evaluating 2~100 042DH о high speed filter SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 41 3: AI2 4: Pulse 5: Comm. V/F separation F4.12 voltage digital 0V~max output voltage 380V о 050CH setting V/F separation F4.13 voltage rising 0.0s~1000.0s 0.0s о 050DH time SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 42 0.1~6553.5 mOhm 0606H о resistance R1 model Leakage Depends on F5.07 inductive 0.001~65.535 mH о 0607H model reactance X Rotor Depends on F5.08 0.1~6553.5 mOhm 0608H о model resistance R2 SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 43 060CH model inductance Ld Synchronous Depends on motor Q-axis F5.13 0.001 ~65.535 mH о 060DH model inductance Lq Synchronous F5.14 motor counter 0.0~6553.5 V 300.0 V о 060EH EMF constant SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 44 ®X8 terminal terminal 4 F6.08 function Reserved 0708H 21: Torque control selection disable 22: Acc./Dec. time ©AI1 terminal selector 1 F6.09 function Reserved 0709H 23: Acc./Dec. time selection selector 2 SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 45 35: PID pause 36: PID parameters switching 37: PID direction reversion; Active this terminal to reverse PID direction set by F8.04. 38: Timing drive input 39: Counter signal input SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 46 0.05s о 070FH time F6.16 AI2 Min. input 0.00~F6.18 0.00V 0710H о AI2 Min. input F6.17 corresponding -200.0~200.0% 0.00% о 0711H setup F6.18 AI2 Max. input F6.16~10.00V 10.00V 0712H о SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 47 F6.31 of X2 terminal 0.0~100.0s 0.0s о 071FH open Pos. logic of Xi Pos. and Neg. terminal: F6.32 logic terminal Be valid while 0000 0720H connecting between Xi and COM. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 48 Pos. and Neg. Thousands: Logic F6.33 logic terminal 0721H of X8 terminal Note: Terminal 24, 25, 26, 27 , 42 , 43 , 44 and 49 are not impacted by this parameter. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 49 17: Under voltage Relay 2 status output F7.04 (BRA/BRB/BRC) о 0804H output selection 18: Drive overload pre-warning 19: Fixed-length arrived, level signal 20: PID in dormancy 21: AI1>AI2 22: AI1<F7.16 SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 50 F7.10 0.00 ~ 550.0Hz 50.00H z о 080AH frequency Down detection F7.11 0.00 ~ 550.0Hz 0.00Hz о 080BH frequency Torque detection F7.12 0.0 ~ 200.0% 100.00 % о 080CH reference SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 51 7: Calibrating signal (5V) 8: Output torque (0 ~ 2 times of motor rated torque) 9: Output power (0 ~ 2 times of drive rated power) 10: Bus voltage (0~1000V) SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 52 о 081DH stop lag time 0: 50.00kHz F7.30 DO Max. output 081EH 1: 500.0Hz 0: Include Jog signal FDT/RUN signal F7.31 1: Do not 081FH Jog selection include Jog signal SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 53 о 0900H selection 3: Pulse input 4: Serial communication 0: AI1 1: AI2 PID feedback 2: Pulse input F8.01 channel 3: Serial о 0901H selection communication 4: AI1-AI2 5: AI1+AI2 SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 54 о 0911H negative limit F8.18 PID preset freq. 0.00 550.0Hz 0.00Hz 0912H Hold time of PID F8.19 preset 0.0~3600s 0.0s 0913H frequency Enable 0: Disabled F8.20 0914H dormancy 1: Enabled SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 55 0.00 ~ Max F9.03 20.00 Hz 0A03H о freq.4 frequency Multi-step 0.00 ~ Max F9.04 30.00 Hz о 0A04H freq.5 frequency Multi-step 0.00 ~ Max F9.05 40.00 Hz о 0A05H freq.6 frequency SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 56 PLC 1: Minute processing PLC step1 F9.11 0.1 ~3600 о 0A0BH duration (T1) PLC step2 F9.12 0.0-3600 о 0A0CH duration (T2) PLC step3 F9.13 0.0-3600 о 0A0DH duration (T3) SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 57 1 F/r - 4 F/r 0A15H о running setting Step T5 program F9.22 1 F/r - 4 F/r о 0A16H running setting Step T6 F9.23 1 F/r - 4 F/r о 0A17H program SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 58 0.00 ~ Max F9.30 50.00 Hz 0A1EH о freq.11 frequency Multi-step 0.00 ~ Max F9.31 50.00 Hz 0A1FH о freq.12 frequency Multi-step 0.00 ~ Max F9.32 50.00 Hz о 0A20H freq.13 frequency SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 59 0.1~999.9s 5.0s о 0B03H time Wobble freq. FA.04 0.1~999.9s 5.0s о 0B04H down time 0: Relative to the central freq. FA.05 Amplitude mode о 0B05H 1: Relative to Max. frequency SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 60 О amplitude limit speed invalid 2: Valid all the time Current FC.05 amplitude limit 80.0~200.0% 160.0% О 0D05H level 0: Invalid Over voltage stall FC.06 (Recommended 0D06H function if braking SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 61 (Auto run time interval is F1.16) 50.0%~100.0% (100% means this Depends FC.15 Fast current limit о 0D0FH function is on model disabled.) Fast current limit FC.16 0.01~1.00s 0.10s о 0D10H time SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 62 0: Warning and Treatment select running still FC.19 while overvoltage 0D13H о 1: Fault cause forewarning stopping Reminding or not 0: Yes FC.20 while о 0D14H 1: No undervoltage SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 63 Freq. setting 0.0~200.0% 100.00 % о 0E06H coefficient 0: Time interval between 2 Communication packets Fd.07 interrupt receiving. о 0E07H detection mode 1: Time interval of 0005H Add. data writing SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 64 0: Y Fd.08 о 0E08H writing into 1: N COMMS setting Save the COMMS setting 0: N Fd.09 or not (Y or N) о 0E09H 1: Y While power down SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 65 12: OL2 Drive overload 13: EF0 communication fault 14: EF1 external terminal fault 15: SP1 Input phase failure or input phases unbalance 16: SPO Output phase failure or Unbalance SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 66 FF.01 0.00Hz 1001H at latest fault limit Reference 0~Frequency upper FF.02 frequency at 0.00Hz 1002H limit latest fault Output 0~2 drive rated FF.03 current at 0.0A 1003H current latest fault SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 67 FF.14 Flux current -200.0~200.0% 100EH Torque FF.15 -200.0~200.0% 100FH current Accumulated kilowatt- FF.17 0~65535kWH 0kWH 1011H hours (Upper 16 bits) Accumulated kilowatt- FF.18 0~65535kWH 0kWH 1012H hours (Low 16 bits) SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 68 (all parameters) Parameter 0: Protection enabled FP.04 upload 1: Protection disabled protection G/P model 0: Type G FP.05 selection 1: Type P User 0: Invalid FP.07 parameters 1: Valid backup SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 69 Parameter description 6.F Running History Record Modbus Code Description Setting range Default Modify Address FP.08 User 0: Invalid parameters 1: Valid recovery SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 70 The series of frequency converter has 22 kinds of faults, which is shown together with their respective solutions in Table below. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 71 2. Add suitable brake 2.Large load inertia devices. 1. Check the input power 1. Power supply Over voltage in source. abnormal constant speed 2. Add suitable braking 2. Large load inertia devices. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 72 2. Load too heavy drive. Drive overload 3. Acceleration too fast 3. Increase the acceleration 4. Restart the motor time still in turning 4. Avoid restarting when the motor is in rotation. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 73 1. The current IDE Hall current 1. Ask for service from sensoring or hall detection fault supplier device get damaged. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 74 1. Frequency drive function(FC.19=0) Overload pre- output current is 2. Increase pre-alarm OLP2 alarm error higher than set pre- threshold value (FC.02) 3. alarm threshold 3. Increase pre-alarm detection time(FC.03) SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 75 Heat-sink temperature Temperature in the radiator higher than the is high OH2 standard Function codes setup is Output terminal DO, Y1, Y2 does not not appropriate simultaneously select No.10 function SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 76 1. Lubrication is not good or 1. Repair or replace the noise bearing wear electric motor. motor 2. Carrier frequency is too 2. Increase the carrier loud frequency of the drive SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 77 CHARGER indictor is OFF, otherwise there may be risks of electric shock. 3. Do not leave metal components and parts in the drive, or it may damage the equipment. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 78 Special test There are no overheat fault Overheat instrument and and burning smell. smell. Motor Sound Listen There is no abnormal sound. Special test There is no abnormal Vibration instrument oscillation. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 79 The cooling fan and electrolytic capacitor are vulnerable components and shall be conducted routine inspection as per the table below. If any fault occurs, please conduct immediate replacement SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 80 3) The fault is caused by using the drive in a wrong way, such as wiring mistakes. 4) The fault is caused by fire, salt corrosion, gas corrosion, earthquake, storms, floods, lightning, abnormal voltage, or other force majeure causes. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 81 AI1 AI2 Output Freq. 0.0~550.0Hz Starting frequency 0.0~60.00Hz Acc./Dec. time 0.1~3600s 400V Breaking unit action voltage 650~750V Dynamic braking 200V Breaking unit action voltage 360~390V braking activation DC braking frequency:0.00~550.0Hz; SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 82 Protections Power supply under/over-voltage, Analog input/output abnormal, Temperature sampling devices offline faults, Drives/motor Abnormal power failure in running overload Overcurrent Under/over voltage, Relay contact error Heat sink over-heat, EEPROM abnormal SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 83 10 m/s , 9~200Hz; 15 m/s , 200~500Hz 0~2000m; Altitude Derating use above 1000m; Derate 1% every 100m higher. Storage temperature -40~ +70°C 9.2 Dimensions and weight Dimensions drawing FSD…FSF SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 84 Top Bottom Lateral (Nm) 4 x M8/13 4 x M8/13 4 x M8/13 4 x M8/13 4 x M8/13 SINAMICS V50 wire connections Power connections Grounding terminal (R, S, T, P1, PB, (+), (-), U, V, W) (PE) Frame size Terminal...
  • Page 85 – The TN line system with grounded neutral point can also be supplied using an isolation transformer. – The phase-to-phase voltage does not have to be reduced. 9.3.2 Current derating as a function of the ambient temperature SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 86 Excessively high temperatures can damage the converter or reduce the converter service life. ● Never operate the converter continuously with an output frequency = 0 Hz. ● Only operate the converter in the permissible operating range. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 87 Power Drive System (PDS) of rated voltage less than 1000 V, which is neither a plug-in device nor a movable device, and when used in the first environment, is only intended to be installed and commissioned by a professional. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 88 This product can cause high-frequency interferences in a residential environment that can require radio interference suppression measures. ● Have the installation and commissioning with appropriate radio interference suppression measures performed by qualified personnel. SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 89 According to Directive 2013/35/EU, 500 µT (RMS) at 50 Hz is applicable here. 4. Compliance with the limit values was assessed for the following frequencies: – Line frequency 47 ... 63 Hz SINAMICS V50 converter Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB...
  • Page 90 Description The following information regarding electromagnetic fields relates solely to converters supplied by Siemens. The converters are normally used in machines. The assessment and testing is based on DIN EN 12198. The indicated minimum distances apply to the head and complete torso of the human body.
  • Page 91 Further information SINAMICS converters: www.siemens.com/sinamics Siemens Electrical Drives Ltd. No.1 Haitaichuangxin 5th Road Huanyuan Industry Development Area Tianjin Hi-Tech Industry Park China Scan the QR code for additional information about SINAMICS V50.