Download Print this page

ABB EMERGI-LITE Guideway Instruction Leaflet

Recessed luminaires

Advertisement

Quick Links

NOTE: The information on this page applies to
Self Contained luminaires
INSTALLATION & COMMISSIONING
Connect mains
230 - 240V / 50Hz
0-30%
60h
60h
Wait
After 60 hours the luminaire is fully commissioned.
.
EXPLANATIONS
Maintained
Non-maintained
Manual testing
Push test button < 1 sec. to set luminaire in test mode (5 sec. test).
Setup even or odd testing schedule
Push test button > 3 sec. to enter the setup mode for even or odd testing schedule.
If LED's flash in phase the luminare is set to even schedule.
If LED's flash out of phase the luminare is set to odd schedule.
Toggle between even and odd by pushing the test button.
Reset luminaire
Push test button > 10 sec. to reset test schedule.
SELFTEST SCHEDULE
Installation test
1
Duration test after 36 hours, 3 hours.
Functional test
2
.
Every 7 days, 1 minute.
3
Autonomy test
Every 26 weeks, 3 hours.
Contacts
ABB Emergi-Lite Ltd
100%
Bruntcli e Lane
Morley, Leeds
West Yorkshire LS27 9LL
United Kingdom
Sales +44 (0) 333 999 9900
Technical +44 (0) 113 281 0600
Email: LV.Enquiries@gb.abb.com
Switched
www.emergi-lite.co.uk
maintained
OK
ABB United Arab Emirates
Emergency mode
P.O. Box 11070
Dubai,
United Arab Emirates
In test
Tel: +971 (4) 3147500
Fax: +971 (4) 3401541
E-mail: info@ae.abb.com
Failure
www.abb.com/lowvoltage
We reserve the right to make technical changes or modify the
contents of this document without prior notice. With regard to
purchase orders, the agreed particulars shall prevail. ABB AG
does not accept any responsibility whatsoever for potential
errors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter
and illustrations contained therein. Any reproduction, disclosure
to third parties or utilization of its contents – in whole or in
parts – is forbidden without prior written consent of ABB AG.
Copyright© 2017 ABB
All rights reserved
RECESSED LUMINAIRES
05
KM 655958
G
u
INSTRUCTION LEAFLET
EN
®
d i
e
w
a
y

Advertisement

loading

Summary of Contents for ABB EMERGI-LITE Guideway

  • Page 1 Any reproduction, disclosure Functional test to third parties or utilization of its contents – in whole or in Every 7 days, 1 minute. parts – is forbidden without prior written consent of ABB AG. INSTRUCTION LEAFLET Copyright© 2017 ABB All rights reserved Autonomy test Every 26 weeks, 3 hours.
  • Page 2 CONNECTING SELF CONTAINED DIMENSIONS - EBOXES Connect Dimensions - Ebox Self contained max. Ø 2,5 mm² red wire 230 - 240V 50Hz MAX 10A Maintained ca. 30% dimmer Place 2L 1L 0 - 10V pictogram plates ca. 30% - 100% Switched DIM CIS DALI...